https://www.phoenixcontact.com/us/products/2297044
Solid-state reversing contactor - ELR W3-230AC/500AC- 2I - 2297044
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
"4 in 1" three-phase semiconductor reversing contactor with 230 V AC input, 2 A output current, emergency stop
function, and adjustable overload shutdown.
The figure shows 2297031 ELR W324DC/500AC-2I
Product Features
■
■
■
■
■
■
■
22.5 mm wide
Safety level according to IEC 61508-1: SIL 3, ISO 13849: PL e
Long service life
Space saving
Reduction in wiring
3-phase loop bridges
Bimetal function can be set up to 9 A
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
283.1 g
Custom tariff number
85371099
Country of origin
Germany
Technical data
Input data
Input name
Device supply
Mains frequency
40 Hz
100 Hz
Rated control circuit supply voltage US
230 V AC
Voltage range with reference to US
0.4 ... 1.1
04/27/2016 Page 1 / 7
https://www.phoenixcontact.com/us/products/2297044
Solid-state reversing contactor - ELR W3-230AC/500AC- 2I - 2297044
Technical data
Input data
Control supply voltage range
92 V AC ... 253 V AC
Rated control supply current IS
4 mA
Rated actuating voltage UC
230 V AC
Voltage range with reference to UC
0.4 ... 1.1
Rated actuating current IC
7 mA
Protective circuit
Surge protection
Typical response time
< 35 ms
Typical turn-off time
< 80 ms
Operating voltage display
Green LED
Status display
Yellow LED
Indication
Red LED
Input name
Control input right/left
Switching threshold
44 V AC (“0” signal)
85 V AC (“1” signal)
Output data load output
Nominal output voltage
500 V AC
Nominal output voltage range
42 V AC ... 550 V AC
Load current range
180 mA ... 2.4 A (see to derating)
Rated operating current at AC-51
2.4 A
Rated operating current at AC-53a
2.4 A
Leakage current
0 mA
Residual voltage
< 0.3 V
Surge current
100 A (t = 10 ms)
Protective circuit
Surge protection
Output data reply output
Note
Confirmation 01: Floating PDT contact
Measuring technology and signaling contact
Measuring via
Current transformer for line current on L1 and L3
Connection data, control circuit
Connection name
Control circuits
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section solid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
04/27/2016 Page 2 / 7
https://www.phoenixcontact.com/us/products/2297044
Solid-state reversing contactor - ELR W3-230AC/500AC- 2I - 2297044
Technical data
Connection data, control circuit
Conductor cross section AWG
24 ... 14
Connection data load circuit
Connection name
Load circuit
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section solid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
General
Test voltage input/output
4 kVrms
Mounting position
Vertical (horizontal DIN rail)
Assembly instructions
Can be aligned with spacing = 20 mm
Operating mode
100% operating factor
Designation
Standards/regulations
Standards/regulations
DIN EN 50178
EN 60947
Designation
Power station requirements
Standards/regulations
DWR 1300 / ZXX01/DD/7080.8d
Designation
Air clearances and creepage distances between the power circuits
Standards/regulations
DIN EN 50178
Insulation
safe isolation
Degree of pollution
2
Overvoltage category
III
Reversing frequency
≤ 2 Hz
Dimensions
Width
22.5 mm
Height
99 mm
Depth
114.5 mm
Ambient conditions
Ambient temperature (operation)
-25 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Degree of protection
IP20
UL data
SCCR
100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault)))
04/27/2016 Page 3 / 7
https://www.phoenixcontact.com/us/products/2297044
Solid-state reversing contactor - ELR W3-230AC/500AC- 2I - 2297044
Technical data
UL data
5 kA (480 V AC (fuse: 20 A RK5 (standard fault)))
Standards and Regulations
Designation
Standards/regulations
Standards/regulations
DIN EN 50178
EN 60947
Designation
Power station requirements
Standards/regulations
DWR 1300 / ZXX01/DD/7080.8d
Designation
Air clearances and creepage distances between the power circuits
Standards/regulations
DIN EN 50178
Insulation
safe isolation
Degree of pollution
2
Overvoltage category
III
Classifications
eCl@ss
eCl@ss 4.0
27371102
eCl@ss 4.1
27371102
eCl@ss 5.0
27371601
eCl@ss 5.1
27371601
eCl@ss 6.0
27371601
eCl@ss 7.0
27371601
eCl@ss 8.0
27371014
ETIM
ETIM 2.0
EC000066
ETIM 3.0
EC000066
ETIM 4.0
EC000066
ETIM 5.0
EC002055
UNSPSC
UNSPSC 6.01
30211915
UNSPSC 7.0901
39121514
UNSPSC 11
39121514
UNSPSC 12.01
39121514
UNSPSC 13.2
39121514
04/27/2016 Page 4 / 7
https://www.phoenixcontact.com/us/products/2297044
Solid-state reversing contactor - ELR W3-230AC/500AC- 2I - 2297044
Approvals
Approvals
Approvals
UL Listed / cUL Listed / GL / GL-SW / IECEE CB Scheme / UL Listed / cUL Listed / EAC / EAC / GL / cULus Listed
Ex Approvals
ATEX / ATEX
Approvals submitted
Approval details
UL Listed
cUL Listed
GL
GL-SW
IECEE CB Scheme
UL Listed
cUL Listed
04/27/2016 Page 5 / 7
https://www.phoenixcontact.com/us/products/2297044
Solid-state reversing contactor - ELR W3-230AC/500AC- 2I - 2297044
Approvals
EAC
EAC
GL
cULus Listed
Drawings
MAN
RES
AUTO
RES
Logik
µP
Diagram
1/L1
3/L2
Us
5/L3
Us
GND
2/T1
GNDE
& Error
R
4/T2
6/T3
Output current [A]
Block diagram
4
3,5
3
2,5
2
1,5
1
0,5
0,18
1
2
1 = mounted in rows with
spacing of 20 mm
2 = mounted in rows without spacing
97 96 95
Circuit diagram
L1
L2
L3
70
60
50
40
Ambient temperature [°C]
30
20
10
0
L
Circuit diagram
+24V DC F5
F1
F2
F3
K5
K5
K5
K5
S2
F4
K1
T1
K2
K5
T2
K3
T3
K4
K1
K4
K3
K5
K5
K1
K2
K2
F4
M
3~
M1
Conventional structure
K3
PE
K4
K5
K5
GND
Conventional structure
04/27/2016 Page 6 / 7
https://www.phoenixcontact.com/us/products/2297044
Solid-state reversing contactor - ELR W3-230AC/500AC- 2I - 2297044
Main current path for reversing contactor according to category 3
Control current path reversing contactor according to category 3
K1 + K2 = Emergency stop contactor
K3 = Left contactor
K4 = Right contactor
F4 = Motor protection relay
K1 + K2 = Emergency stop contactor
K3 = Left contactor
K4 = Right contactor
K5 = PSR SCP-24DC.../Safety relay
T1 = Right, T2 = Left, T3 = Reset
S2 = Emergency stop
F4 = Motor protection relay
Circuit diagram
L1 F1
F2
L2 F3
L3
+24V DC
K5
L1 L2 L3
T3
K1
T1 T2 T3
T1 T2
K5
M
3~
M1
K5
K1 +US R L
K5
K5
K5
K5
S2
E
PE
K5
GND
Structure with CONTACTRON
,
,
Main and control current path for 4 in 1 hybrid motor starter with reversing function according to category 3
,
,
K1 = 4 in 1 hybrid motor starter with reversing function
K5 = PSR SCP-24DC.../Safety relay
T1 = Right, T2 = Left, T3 = Reset
S2 = Emergency stop
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
04/27/2016 Page 7 / 7
很抱歉,暂时无法提供与“2297044”相匹配的价格&库存,您可以联系我们找货