ELR W3- 24DC/500AC- 9I
Order No.: 2297057
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2297057
"4 in 1" three-phase solid-state reversing contactor with 24 V DC input,
9 A output current and adjustable overload switching
Product notes
WEEE/RoHS-compliant since:
06/21/2007
Commercial data
GTIN (EAN)
4
046356
170581
sales group
G421
Pack
1 pcs.
Customs tariff
85371099
Catalog page information
Page 164 (IF-2009)
http://
www.download.phoenixcontact.com
Please note that the data given
here has been taken from the
online catalog. For comprehensive
information and data, please refer
to the user documentation. The
General Terms and Conditions of
Use apply to Internet downloads.
Technical data
Input data
Rated control supply voltage US
24 V DC
Rated control supply voltage range with reference
to US
0.8 ... 1.25
Rated control supply current IS
35 mA
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 1 / 6
Feb 2, 2011
ELR W3- 24DC/500AC- 9I Order No.: 2297057
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2297057
Rated actuating voltage UC
24 V DC
Rated actuating voltage range with reference to
UC
0.8 ... 1.25
Rated actuating current IC
3 mA
Switching threshold "0" signal, voltage
9.6 V
Switching threshold "1" signal voltage
19.2 V
Protective circuit
Protection against polarity reversal Parallel polarity protection
diode
Surge protection
Typical response time
< 35 ms
Typical turn-off time
< 40 ms
Operating voltage display
Green LED
Status display
Yellow LED
Indication
Red LED
Output data, load relay
Output name
AC output
Nominal output voltage
500 V AC
Nominal output voltage range
48 V AC ... 550 V AC
Load current
max. 9 A (see derating curve)
Leakage current
0 mA
Residual voltage
< 0.5 V
Surge current
100 A (t = 10 ms)
Type of protection
Surge protection
Output name
Acknowledge output
Note
Confirmation 01: Floating PDT contact
Nominal output voltage
max. 253 V AC 0% ... 100% (300 V DC)
Residual voltage
< 0.5 V
Output data, signaling contact
Measuring via
Current transformer for line current on L1 and L3
Current range
1 A ... 45 A
Connection data
Type of connection
Screw connection
Conductor cross section solid min.
0.14 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.14 mm²
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 2 / 6
Feb 2, 2011
ELR W3- 24DC/500AC- 9I Order No.: 2297057
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2297057
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
26
Conductor cross section AWG/kcmil max
12
General data
Width
22.5 mm
Height
99 mm
Depth
114.5 mm
Test voltage input/output
4 kVrms
Ambient temperature (operation)
-25 °C ... 70 °C
Ambient temperature (storage/transport)
-25 °C ... 70 °C
Mounting position
Vertical (horizontal DIN rail)
Assembly instructions
Can be aligned with spacing = 20 mm
Operating mode
100% operating factor
Degree of protection
IP20
Name
Standards/regulations
Standards/regulations
DIN EN 50178
EN 60947
Name
Power station requirements
Standards/regulations
DWR 1300 / ZXX01/DD/7080.8d
Name
Air and creepage distances between the power circuits
Standards/regulations
DIN EN 50178
Rated surge voltage / insulation
6 kV/safe isolation
Rated insulation voltage
500 V
Pollution degree
2
Surge voltage category
III
Category in acc. with EN 954-1
3
Certificates / Approvals
Certification
BV, CB, CUL Listed, GL, LR, UL Listed
Certification Ex:
PTB
Certifications applied for:
UL-EX LIS / CUL-EX LIS
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 3 / 6
Feb 2, 2011
ELR W3- 24DC/500AC- 9I Order No.: 2297057
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2297057
Diagrams/Drawings
Block diagram
Diagram
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 4 / 6
Feb 2, 2011
ELR W3- 24DC/500AC- 9I Order No.: 2297057
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2297057
Circuit diagram
Conventional structure
Main current path for reversing contactor
according to category 3
K1 + K2 = Emergency stop contactor
K3 = Left contactor
K4 = Right contactor
F4 = Motor protection relay
Conventional structure
Control current path for reversing
contactor according to category 3
K1 + K2 = Emergency stop contactor
K3 = Left contactor
K4 = Right contactor
K5 = PSR SCP-24DC.../safety relay
T1 = Left, T2 = Right, T3 = Reset
S2 = Emergency stop
F4 = Motor protection relay
Structure with CONTACTRON
Main and control current path for "4 in 1" hybrid motor starter
with reversing function according to category 3
K1 = "4 in 1" hybrid motor starter with reversing function
K5 = PSR SCP-24DC.../safety relay
T1 = Left, T2 = Right, T3 = Reset
S2 = Emergency stop
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 5 / 6
Feb 2, 2011
ELR W3- 24DC/500AC- 9I Order No.: 2297057
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2297057
Address
PHOENIX CONTACT Deutschland GmbH
Flachsmarktstr. 8
32825 Blomberg,Germany
Phone +49 5235 3 12000
Fax +49 5235 3 41200
http://www.phoenixcontact.de
© 2010 Phoenix Contact
Technical modifications reserved;
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 6 / 6
Feb 2, 2011
很抱歉,暂时无法提供与“2297057”相匹配的价格&库存,您可以联系我们找货
免费人工找货