S5/S7 ADAPTER
VARIOFACE S5/S7 Adapters for
Siemens SIMATIC® S7
INTERFACE
Data Sheet
101976_en_05
1
© PHOENIX CONTACT 2010-06-28
Description
For systems that are automated with SIMATIC® S5-115 and
135/155, various Phoenix Contact VARIOFACE S5/S7
adapters can be used to connect the existing SIMATIC® S5
field wiring directly to SIMATIC® S7. This saves both time
and money. Costly rewiring of individual modules is not
required.
During downtimes, such as weekends, systems can be
tested with SIMATIC® S7 and can also be operated during
production times with SIMATIC® S5. Once the changeover
is complete, SIMATIC® S7 controls the system via
VARIOFACE S5/S7 adapters and the old SIMATIC® S5 field
wiring.
2
Table of Contents
1
Description ............................................... 1
2
Table of Contents ..................................... 1
3
Adapters for Converting S5-115 to
S7-400 ................................................................. 2
3.1
4
6ES5 420... to 6ES5 465.......................... 2
Adapters for Converting S5-115 to
S7-300 ................................................................. 3
4.1
6ES5 420... to 6ES5 451.......................... 3
5
Commissioning adapters for extending
the existing S5-115 field wiring....................... 4
6
Adapters for Converting S5-135/155 to
S7-400 ................................................................. 5
VARIOFACE S5/S7 adapters ensure safe system operation
using modern control systems.
6.1
6.2
6.3
6.4
7
Adapters for Converting S5-135 to
S7-300 ................................................................. 9
7.1
8
Make sure you always use the latest documentation.
It can be downloaded at www.phoenixcontact.net/catalog.
6ES5 420... to 6ES5 432.......................... 5
6ES5 436... to 6ES5 453.......................... 6
6ES5 454... to 6ES5 460.......................... 7
6ES5 465... to 6ES5 470.......................... 8
6ES5 420... to 6ES5 451.......................... 9
Commissioning adapters for extending
the existing S5-135 field wiring .................... 10
S5/S7 ADAPTER
3
Adapters for Converting S5-115 to S7-400
FLKM S115/... adapters provide a direct connection
between a SIMATIC® S5 connector wired with individual
wires and the SIMATIC® S7-400 base board. The
SIMATIC® S5 connector is plugged directly into an S7-400
I/O card with the aid of the FLKM S115/... adapter. A new
3.1
SIMATIC® S7-400 is installed in place of the SIMATIC® S5.
The existing field wiring remains intact.
Attention: Due to the geometry, it is only possible to use
every other slot. The LEDs of the S7-400 module are hidden
by the S5-115 adapter.
6ES5 420... to 6ES5 465...
Ordering Data
Description
Type
Order No.
Pcs./Pck.
FLKM S115/S400/SO155
2307248
1
6ES5 454-7LA12 to 6ES7 422 1BH11-0AA0
FLKM S115-454-7LA/S400
2314901
1
Analog IN (current and voltage measurement only) from S5-115 to S7400
FLKM S115-465-7LA/UI/S400
2314914
1
Digital IN and OUT 24 V DC from S5-115 to S7-400
IN
6ES5 420-7LA11 to 6ES7-421-1BL01-0AA0
6ES5 430-7LA11 to 6ES7-421-1BL01-0AA0
OUT
6ES5 441-7LA11 to 6ES7 422-1BL00-0AA0
6ES5 451-7LA11 to 6ES7 422-1BL00-0AA0
Digital OUT 24 V DC from S5-115 to S7-400
6ES5 465-7LA13 to 6ES7 431 0HH00-0AB0
6ES5 465-7LA13 to 6ES7 431 7QH00-0AB0
Technical Data
Maximum permissible operating voltage
24 V AC/DC
Maximum permissible current (per branch)
4A
Maximum permissible current (separate power supply)
4A
Test voltage
500 V (50 Hz, 1 min.)
Ambient temperature (operation)
-20°C ... +50°C
Mounting position
Vertical
Standards/specifications
DIN EN 50178/IEC 62103
Connection Schemes
FLKM S115/S400/SO155
FLKM S115-465-7LA/UI/S400
3 4 5 6 7 8 9 10 11 12
13 15 16 17 18 19 20 21 22 23
S5-115
1 3 4 5 6 7 8 9 10 11
13 15 16 17 18 19 20 21 22 23
S7-400
25 27 28 29 30 31 32 33 34 35
37 39 40 41 42 43 44 45 46 48
S7-400
1 2
S5-115
25 27 28 29 30 31 32 33 34 35
S5-115 1 2 3 4 5 6 7 8 9 10 1112 13 14 15 16 17 18 19 202122 23 24
S7-400 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 4748
L+
L-
37 39 40 41 42 43 44 45 46 47
FLKM S115-454-7LA/S400
S5-135 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 424344 45 46 47
S7-400 1 2 3 4 5 6 7 8 9 10 11 12
1314 15 16 17 18 19 20 21 22 2324
S5-115 1 2 3 4 5 6 7 8 9 10 1112
13 14 15 16 17 18 19 202122 23
S7-400 25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42 43 44 45 46 4748
S5-115 25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42 43 44 45 46 47
101976_en_05
S7-400 1 2 3 4 5 6 7 8 9 10 11 12 1314 15 16 17 18 19 20 21 22 2324
PHOENIX CONTACT
2
S5/S7 ADAPTER
4
Adapters for Converting S5-115 to S7-300
S5/S7 adapters connect S5-115 front adapters wired with
individual wires to S7-300 I/O modules. With the aid of the
FLKM S115/S7/FLK50/SO13 converter module, the signals of
the S5-115 front adapter can be converted to a 50-pos. strip.
4.1
An FLK 50/EZ-DR/.../KONFEK 50-pos. system cable and a
front adapter for SIMATIC® S7-300 (FLKM 50-PA-S300)
connect the signals to the I/O module.
6ES5 420... to 6ES5 451...
Ordering Data
Description
Type
Order No.
Pcs./Pck.
FLKM S115/S7/FLK50/PLC/SO137
2306294
1
Digital IN and OUT 24 V DC from S5-115 via converter, system cable,
and front adapter to S7-300
IN
6ES5 420-7LA11 to 6ES7 321-1BL00-0AA0
6ES5 430-7LA11 to 6ES7 321-1BL00-0AA0
OUT
6ES5 441-7LA11 to 6ES7 322-1BL00-0AA0
6ES5 451-7LA11 to 6ES7 322-1BL00-0AA0
Technical Data
Maximum permissible operating voltage
24 V AC/DC
Maximum permissible current (per branch)
1A
Maximum permissible current (separate power supply)
2A
Test voltage
500 V (50 Hz, 1 min.)
Ambient temperature (operation)
-20°C ... +50°C
Mounting position
Any
Standards/specifications
DIN EN 50178/IEC 62103
Connection Scheme
Application Example
FLKM S115/S7/FLK50/PLC/SO137
FLK50 1 2
3 4 5 6 7 8 9 10 1112
1314 1516171819202122 2324
S5-115 1 2 3 4 5 6 7 8 9 10 1112
1314 1516171819 202122 23
FLK50 2526 27282930 31323334 3536
3738 394041 4243444546 4748
S5-115 2526 27282930 31323334 3536
3738 394041 4243444546 47
101976_en_05
PHOENIX CONTACT
3
S5/S7 ADAPTER
5
Commissioning adapters for extending the existing S5-115 field wiring
All signals of the existing S5-115 wiring are extended 3 or
5 meters with the help of the universal commissioning adapters. The open cable end can be connected to various controllers such as S7-400 or S7-300. Thus, the existing field
wiring of S5-115 can communicate with the new controller
for test purposes.
Since the new control unit is temporarily arranged before the
control cabinet, the original status of the system can be
restored if required.
If the system functions with the new controller without problems, the S5-115 can now be replaced.
Ordering Data
Description
Type
Order No.
Pcs./Pck.
Connection of all S5-115 connections (1 to 23, 25 to 47) at the open
cable end, cable length 3 m
FLKM S115/47X0,75/3,0M/OE
2314985
1
Connection of all S5-115 connections (1 to 23, 25 to 47) at the open
cable end, cable length 5 m
FLKM S115/47X0,75/5,0M/OE
2314998
1
Technical Data
Maximum permissible operating voltage
250 V AC/DC
Maximum permissible current (per branch
6A
Ambient temperature (operation)
-20 °C … 50 °C
Ambient temperature (storage/transport)
-20 °C … 80 °C
Mounting position
Any
Standards/specifications
EN 60664-1
Application Example
Connection Scheme
FLKM S115/47X0,75/...M/OE
1
2
3
22
23
25
26
1
2 3
1 2 3
S5-115
101976_en_05
22 23 25 26
22 23 25 26
45 46 47
45
46
47
45 46 47
PHOENIX CONTACT
4
S5/S7 ADAPTER
6
Adapters for Converting S5-135/155 to S7-400
FLKM S135/... adapters provide a direct connection
between a SIMATIC® S5 connector wired with individual
wires and the SIMATIC® S7-400 base board. The
SIMATIC® S5 connector is plugged directly into an S7-400
I/O card with the aid of the FLKM S135/... adapter. A new
6.1
SIMATIC® S7-400 is installed in place of the SIMATIC® S5.
The existing field wiring remains intact.
Attention: The LEDs of the S7-400 module are hidden.
6ES5 420... to 6ES5 432...
Ordering Data
Description
Type
Order No.
Pcs./Pck.
Digital IN 24 V/60 V from S5-135/155 to S7-400
6ES5 420-4UA14 to 6ES7 421-1BL01-0AA0
1 FLKM S135/S400/S0120
2301723
1
6ES5 430-4UA14 to 6ES7 421-1BL01-0AA0
2 FLKM S135/S400/SO121
2301736
1
6ES5 431-4UA12 to 6ES7 421-7DH00-0AB0
3 FLKM S135-431-4UA/S400
2314846
1
6ES5 432-4UA12 to 6ES7 421-1BL01-0AA0
4 FLKM S135/S400/SO122
2301749
1
Technical Data
Maximum permissible operating voltage
1
2
3
4
24 V AC/DC
60 V DC
24 V DC
24 V AC/DC
Maximum permissible current (per branch)
4A
2A
4A
4A
Maximum permissible current (separate power supply)
4A
2A
4A
4A
500 V
(50 Hz, 1 min.)
1.25 kV
(50 Hz, 1 min.)
1.25 kV
(50 Hz, 1 min.)
1.25 kV
(50 Hz, 1 min.)
Test voltage
Ambient temperature (operation)
-20°C ... +50°C
Mounting position
Any
Standards/specifications
DIN EN 50178/IEC 62103
Connection Schemes
FLKM S135/S400/S0120
S7-400 1 2
3
4 5 6 7 8 9 10 11
FLKM S135-431-4UA/S400
15 16 17 18 19 20 21 22
L+
S5-135 1
4 5 6 7 8 9 10 11
13 14 15 16 17 18 19 20
S7-400
27 28 29 30 31 32 33 34
39 40 41 42 43 44 45 46 48
S7-400 1 2 3 4 5 6 7 8 9 10 11 12
1314 15 16 17 18 19 20 21 22 2324
S5-135 1 2 3 4 5 6 7 8 9 10 1112
13 14 15 16 17 18 19 202122 23 24
S7-400 25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42 43 44 45 46 4748
S5-135 25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42
M
25 26 27 28 29 30 31 32
S5-135
34 35 36 37 38 39 40 41
FLKM S135/S400/SO121
S7-400 1 2
3
FLKM S135/S400/SO122
4 5 6 7 8 9 10 11 15 16 17 18 19 20 21 22
S7-400 1 2
3
4 5 6 7 8 9 10 11 151617181920 21 22
L+
S5-135 1 2 3
4 5 6 7 8 9 10 11 13 14 15 16 17 18 19 20
S7-400
27 28 29 30 31 32 33 34
39 40 41 42 43 44 45 46 48
S5-135
4 5 6 7 8 9 10 11 13 14 15 16 1718 19 20
S7-400
272829 30 31 32 33 34
39 40 41 42 43 44 45 46 48
M
M
S5-135
101976_en_05
25 26 27 28 29 30 31 32
34 35 36 37 38 39 40 41 21 42
M
S5-135
252627 28 29 30 31 32
34 35 36 37 38 39 4041 21 42 12 33
PHOENIX CONTACT
5
S5/S7 ADAPTER
6.2
6ES5 436... to 6ES5 453...
Ordering Data
Description
Type
Order No.
Pcs./Pck.
1 FLKM S135/S400/SO123
2301752
1
6ES5 441-4UA12 to 6ES7 422-1BL00-0AA0
2 FLKM S135/S400/SO125
2301778
1
6ES5 451-4UA14 to 6ES7 422-1BL00-0AA0
3 FLKM S135/S400/SO126
2301781
1
4 FLKM S135/S400/SO127
2301794
1
Digital IN 120/230 V UC from S5-135/155 to S7-400
6ES5 436-4UA12 to 6ES7 421-1FH20-0AA0
Digital OUT 24 V from S5-135/155 to S7-400
Digital OUT 24 V DC/2 A from S5-135/155 to S7-400
6ES5 453-4UA12 to 6ES7 422-1HH00-0AA0
Technical Data
Maximum permissible operating voltage
1
2
3
4
230 V AC/DC
24 V AC/DC
24 V DC
24 V DC
1.25 kV
(50 Hz, 1 min.)
500 V
(50 Hz, 1 min.)
Maximum permissible current (per branch)
4A
Maximum permissible current (separate power supply)
4A
Test voltage
1.5 kV
(50 Hz, 1 min.)
500 V
(50 Hz, 1 min.)
Ambient temperature (operation)
-20°C ... +50°C
Mounting position
Any
Standards/specifications
DIN EN 50178/IEC 62103
Connection Schemes
FLKM S135/S400/SO123
FLKM S135/S400/SO126
S7-400
1 2
20 4
S5-135
1
43
4536 48
S7-400
39
4125
S7-400 1 2
4
6
8
10
15
17
19
21 13 24
S5-135 1 2
6
8
10
12
14
16
18
S7-400
27
29
31
33
39
41
S5-135
27
29
31
33
35
37
S5-135
FLKM S135/S400/SO125
1 2
S5-135
1 2 3 4 5 6 7 8 9 10 11
S7-400
3 4 5 6 7 8 9 10 11
1L+
13 14 15 16 17 18 19 20
26 27 28 29 30 31 32 33 34 38 39 40 41 42 43 44 45 46 48
24 25 26 27 28 29 30 31 32
2L+
34 35 36 37 38 39 40 41 2 21
M
FLKM S135/S400/SO127
3 4 5 6 7 8 9 10 11 14 15 16 17 18 19 20 21 22
S7-400
3 4 5 6 7 8 9 10 11 14 15 16 17 18 19 20 21 22
13 14 15 16 17 18 19 20
26 27 28 29 30 31 32 33 34 38 39 40 41 42 43 44 45 46 48
S7-400
1 2
6 11 4 5
9 10 15 16 20 21 17 22
S5-135
1 3 6 10 5 7
9 11 14 16 18 20 15 19
S7-400
27 28 32 33 39 40 44 45 29 34 41 46
S5-135
26 28 30 32 35 37 39 41 27 31 36 40
M
S5-135
101976_en_05
24 25 26 27 28 29 30 31 32
34 35 36 37 38 39 40 41
PHOENIX CONTACT
21
6
S5/S7 ADAPTER
6.3
6ES5 454... to 6ES5 460...
Ordering Data
Description
Type
Order No.
Pcs./Pck.
1 FLKM S135-454-4UA/S400
2314859
1
2 FLKM S135/S400/SO124
2301765
1
3 FLKM S135-460-4UA/I/S400
2314613
1
4 FLKM S135-460-4UA/U/S400
2314862
1
Digital OUT 24 V DC/2 A from S5-135/155 to S7-400
6ES5 454-4UA14 to 6ES7 422-1BH11-0AA0
Digital OUT 230 V UC/2 A from S5-135/155 to S7-400
6ES5 456-4UA12 to 6ES7 422-1FH00-0AA0
Analog IN (current measurement only) from S5-135/155 to S7-400
6ES5 460-4UA13 to 6ES7 431-1KF00-0AB0
Analog IN (voltage measurement only) from S5-135/155 to
S7-400
6ES5 460-4UA13 to 6ES7 431-1KF00-0AB0
Technical Data
Maximum permissible operating voltage
1
2
3
4
24 V DC
230 V AC
24 V DC
24 V DC
500 V
(50 Hz, 1 min.)
500 V
(50 Hz, 1 min.)
Maximum permissible current (per branch)
4A
Maximum permissible current (separate power supply)
4A
Test voltage
1.25 kV
(50 Hz, 1 min.)
1.5 kV
(50 Hz, 1 min.)
Ambient temperature (operation)
-20°C ... +50°C
Mounting position
Vertical
Standards/specifications
DIN EN 50178/IEC 62103
Connection Schemes
FLKM S135-454-4UA/S400
FLKM S135-460-4UA/I/S400
S7-400 1 2 3 4 5 6 7 8 9 10 11 12 1314 15 16 17 18 19 20 21 22 2324
S7-400 1 2 3 4 5 6 7 8 9 10 11 12 1314 15 16 17 18 19 20 21 22 2324
S5-135 1 2 3 4 5 6 7 8 9 10 1112 13 14 15 16 17 18 19 202122 23 24
L-
S5-135 1 2 3 4 5 6 7 8 9 10 1112 13 14 15 16 17 18 19 202122 23 24
S7-400 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 4748
L-
S7-400 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 4748
S5-135 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42
S5-135 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42
FLKM S135/S400/SO124
S7-400 1 2 11 22 4
6
FLKM S135-460-4UA/U/S400
8
10
15
17
19
21 13 24 36 48
S7-400 1 2 3 4 5 6 7 8 9 10 11 12 1314 15 16 17 18 19 20 21 22 2324
N
S5-135 1 2 4
6
8
10
12
14
16
18
20
S5-135 1 2 3 4 5 6 7 8 9 10 1112 13 14 15 16 17 18 19 202122 23 24
S7-400
34 46 27
29
31
33
39
41
43
45
S7-400 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 4748
S5-135
25
27
29
31
33
35
37
39
41
S5-135 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42
101976_en_05
PHOENIX CONTACT
7
S5/S7 ADAPTER
6.4
6ES5 465... to 6ES5 470...
Ordering Data
Description
Type
Order No.
Pcs./Pck.
1 FLKM S135-465-4UA/T/S400
2314875
1
2 FLKM S135-465-4UA/UI/S400
2314888
1
3 FLKM S135-470-4UC/I/S400
2314626
1
4 FLKM S135-470-4UC/U/S400
2314891
1
Analog IN (Pt 100 only) from S5-135/155 to S7-400
6ES5 465-4UA13 to 6ES7 431-7KF10-0AB0
Analog IN (current and voltage measurement only) from
S5-135/155 to S7-400
6ES5 465-4UA13 to 6ES7 431-0HH00-0AB0
6ES5 465-4UA13 to 6ES7 431-7QH00-0AB0
Analog OUT (current output only) from S5-135/155 to S7-400
6ES5 470-4UA13 to 6ES7 432-1HF00-0AB0
6ES5 470-4UC13 to 6ES7 432-1HF00-0AB0
Analog OUT (voltage output only) from S5-135/155 to S7-400
6ES5 470-4UA13 to 6ES7 432-1HF00-0AB0
6ES5 470-4UB13 to 6ES7 432-1HF00-0AB0
6ES5 470-4UC13 to 6ES7 432-1HF00-0AB0
1
Technical Data
2
3
Maximum permissible operating voltage
4
24 V DC
Maximum permissible current (per branch)
2A
4A
4A
4A
Maximum permissible current (separate power supply)
2A
4A
4A
4A
Test voltage
500 V (50 Hz, 1 min.)
Ambient temperature (operation)
-20°C ... +50°C
Mounting position
Any
Standards/specifications
DIN EN 50178/IEC 62103
Connection Schemes
FLKM S135-465-4UA/T/S400
FLKM S135-470-4UC/I/S400
S7-400 1 2 3 4 5 6 7 8 9 10 11 12 1314 15 16 17 18 19 20 21 22 23 24
S7-400 1 2 3 4 5 6 7 8 9 10 11 12 1314 15 16 17 18 19 20 21 22 2324
S5-135 1 2 3 4 5 6 7 8 9 10 1112 13 14 15 16 1718 19 202122 23 24
S7-400 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 4041 4243 44 45 4647 48
S5-135 1 2 3 4 5 6 7 8 9 10 1112 13 14 15 16 17 18 19 202122 23 24
S7-400 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 4748
LL-
S5-135 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42
FLKM S135-465-4UA/UI/S400
S5-135 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42
FLKM S135-470-4UC/U/S400
S7-400 1 2 3 4 5 6 7 8 9 10 11 12
1314 15 16 17 18 19 20 21 22 2324
S5-135 1 2 3 4 5 6 7 8 9 10 1112
13 14 15 16 17 18 19 202122 23 24
S7-400 25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42 43 44 45 46 4748
S5-135 25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42
S7-400 1 2 3 4 5 6 7 8 9 10 11 12 1314 15 16 17 18 19 20 21 22 2324
S5-135 1 2 3 4 5 6 7 8 9 10 1112 13 14 15 16 17 18 19 202122 23 24
S7-400 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 4748
S5-135 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42
101976_en_05
PHOENIX CONTACT
8
S5/S7 ADAPTER
7
Adapters for Converting S5-135 to S7-300
S5/S7 adapters connect S5-135 front adapters wired with
individual wires to S7-300 I/O modules. With the aid of the
FLKM S135/S7/FLK50 converter module, the signals of the
S5-135 front adapter can be converted to a 50-pos. strip. An
7.1
FLK 50/EZ-DR/.../KONFEK 50-pos. system cable and a
front adapter for SIMATIC® S7-300 (FLKM 50-PA-S300)
connect the signals to the I/O module.
6ES5 420... to 6ES5 451...
Ordering Data
Description
Type
Order No.
Pcs./Pck.
FLKM S135/S7/FLK50/PLC
2314736
1
Digital IN and OUT 24 V DC from S5-135 to S7-300
IN
6ES5 420-4UA14 to 6ES7 321-1BL00-0AA0
6ES5 430-4UA14 to 6ES7 321-1BL00-0AA0
OUT
6ES5 441-4UA14 to 6ES7 322-1BL00-0AA0
6ES5 451-4UA14 to 6ES7 322-1BL00-0AA0
Technical Data
Maximum permissible operating voltage
30 V AC/DC
Maximum permissible current (per branch)
1A
Maximum permissible current (separate power supply)
2A
Test voltage
500 V (50 Hz, 1 min.)
Ambient temperature (operation)
-20°C ... +50°C
Mounting position
Any
Standards/specifications
DIN EN 50178/IEC 62103
Application Example
Connection Schemes
FLKM S135/S7/FLK50/PLC
FLK50
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 1819 20 21 22 23 24
L+
DR1
LL2+
S5-135
FLK50
DR2
1 2 3 4 5 6 7 8 9 10 11
12 13 14 1516 17 18 19 2021
DR3
DR4
25 26 27 28 2930313233 34 35 36 37 38 39 40 41 4243 44 45 46 47 48 49 50
S5-135 2223 242526272829 3031 32 33
101976_en_05
34 3536 37 3839 40 41 42
PHOENIX CONTACT
9
S5/S7 ADAPTER
8
Commissioning adapters for extending the existing S5-135 field wiring
All signals of the existing S5-135 wiring are extended 3 or
5 meters with the help of the universal commissioning adapters. The open cable end can be connected to various controllers such as S7-400 or S7-300. Thus, the existing field
wiring of S5-135 can communicate with the new controller
for test purposes.
Since the new control unit is temporarily arranged before the
control cabinet, the original status of the system can be
restored if required.
If the system functions with the new controller without problems, the S5-135 can now be replaced.
Ordering Data
Description
Type
Order No.
Pcs./Pck.
Connection of all S5-135 connections (1 to 42) at the open cable end,
cable length 3 m
FLKM S135/42X0,75/3,0M/OE
2315007
1
Connection of all S5-135 connections (1 to 42) at the open cable end,
cable length 5 m
FLKM S135/42X0,75/5,0M/OE
2318017
1
Technical Data
Maximum permissible operating voltage
250 V AC/DC
Maximum permissible current (per branch)
6A
Ambient temperature (operation)
-20 °C … 50 °C
Ambient temperature (storage/transport)
-20 °C … 80 °C
Mounting position
Any
Standards/specifications
EN 60664-1
Application Example
Connection Schemes
FLKM S135/42X0,75 /…M/OE
1
2
3
1
2 3
1 2 3
S5-135
101976_en_05
40 41 42
40
41
42
40 41 42
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49-(0) 5235-3-00
PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300
www.phoenixcontact.com
10