https://www.phoenixcontact.com/gb/products/2320102
DC/DC converters - QUINT-PS/24DC/24DC/20 - 2320102
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Primary-switched QUINT DC/DC converter for DIN rail mounting with SFB (Selective Fuse Breaking)
Technology, input: 24 V DC, output: 24 V DC/20 A
Product Description
QUINT DC/DC converter with maximum functionality
DC/DC converters alter the voltage level, regenerate the voltage at the end of long cables or enable the creation of independent supply systems by
means of electrical isolation.
QUINT DC/DC converters magnetically and therefore quickly trip circuit breakers with six times the nominal current, for selective and therefore
cost-effective system protection. The high level of system availability is additionally ensured, thanks to preventive function monitoring, as it reports
critical operating states before errors occur.
Why buy this product
Reliable starting of difficult loads, thanks to the static POWER BOOST power reserve with up to 125% nominal current permanently
Preventive function monitoring indicates critical operating states before errors occur
Constant voltage: output voltage regenerated even at the end of long cables
Support conversion to various voltage levels
Electrical isolation: for setting up independent supply systems
Key Commercial Data
Packing unit
1 STK
GTIN
GTIN
4046356481892
Weight per Piece (excluding packing)
1,700.000 g
Custom tariff number
85044030
Country of origin
China
Technical data
Dimensions
Width
82 mm
Height
130 mm
Depth
125 mm
12/23/2016 Page 1 / 10
https://www.phoenixcontact.com/gb/products/2320102
DC/DC converters - QUINT-PS/24DC/24DC/20 - 2320102
Technical data
Dimensions
Width with alternative assembly
122 mm
Height with alternative assembly
130 mm
Depth with alternative assembly
85 mm
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C (> 60 °C derating, 2.5 %/K, startup at -40°C type-tested)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Noise immunity
EN 61000-6-2:2005
Input data
Nominal input voltage range
24 V DC
Input voltage range
18 V DC ... 32 V DC
Current consumption
28 A (24 V, IBOOST)
Inrush surge current
< 26 A (typical)
Power failure bypass
> 10 ms (24 V DC)
Choice of suitable circuit breakers
40 A ... 50 A (Characteristics B, C, D, K)
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Output data
Nominal output voltage
24 V DC ±1 %
Setting range of the output voltage (USet)
18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN)
20 A (-25 °C ... 60 °C)
POWER BOOST (IBoost)
25 A (-25°C ... 40°C permanent, UOUT = 24 V DC )
Selective Fuse Breaking (ISFB)
120 A (12 ms)
Derating
60 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
yes
Max. capacitive load
Unlimited
Active current limitation
Approximately 29 A
Control deviation
< 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple
< 20 mVPP
Peak switching voltages nominal load
< 10 mVPP (20 MHz)
Maximum power dissipation in no-load condition
2.2 W
Power loss nominal load max.
39 W
General
Net weight
1.7 kg
Efficiency
> 93 %
12/23/2016 Page 2 / 10
https://www.phoenixcontact.com/gb/products/2320102
DC/DC converters - QUINT-PS/24DC/24DC/20 - 2320102
Technical data
General
Insulation voltage input/output
1.5 kV (type test)
1 kV (routine test)
Protection class
III
> 554000 h (40°C)
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
Alignable: 5 mm horizontally, 15 mm next to active components, 50 mm
vertically
Connection data, input
Connection method
Screw connection
Conductor cross section solid min.
0.5 mm²
Conductor cross section solid max.
16 mm²
Conductor cross section flexible min.
0.5 mm²
Conductor cross section flexible max.
16 mm²
Conductor cross section AWG min.
8
Conductor cross section AWG max.
6
Stripping length
10 mm
Screw thread
M3
Connection data, output
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
6 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
4 mm²
Conductor cross section AWG min.
12
Conductor cross section AWG max.
10
Stripping length
8 mm
Screw thread
M3
Connection data for signaling
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Screw thread
M3
Standards and Regulations
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Shock
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Noise immunity
EN 61000-6-2:2005
12/23/2016 Page 3 / 10
https://www.phoenixcontact.com/gb/products/2320102
DC/DC converters - QUINT-PS/24DC/24DC/20 - 2320102
Technical data
Standards and Regulations
Connection in acc. with standard
CUL
Standards/regulations
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
Standard - Electrical safety
EN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage
EN 60950-1 (SELV)
EN 60204 (PELV)
Standard - Safe isolation
DIN VDE 0100-410
Shipbuilding approval
Germanischer Lloyd (EMC 1)
UL approvals
UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D
(Hazardous Location)
Vibration (operation)
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Rail applications
EN 50121-4
Drawings
Block diagram
+
+
-
+
-
UIN>19,2 V
DC OK
I