QUINT4-UPS/1AC/1AC/1KVA
Uninterruptible power supply
Data sheet
107563_en_00
1
© PHOENIX CONTACT 2018-05-02
Description
The QUINT-UPS uninterruptible power supply (UPS) is
used to ensure that power for critical electrical loads
continues to be supplied in the event of disturbances in the
power supply network, e.g., due to mains breakdown or
failure.
In doing so, the UPS switches to battery operation without
interruption so that connected loads continue to be
consistently supplied.
When mains power is restored, the UPS automatically
returns to normal operation. The connected loads are again
supplied via the power supply network and the battery is
charged.
– Worldwide use, thanks to wide-range input
– Online UPS with pure sine wave voltage at output
– Parallel connection possible for increased performance
and redundancy
– Optimum use of the buffer time and preventive battery
monitoring
– Maximum energy efficiency
– Extensive signaling and parameterization
– Flexible configuration
Technical data (short form)
Nominal input voltage
100 V AC , 110 V AC , 120 V AC ,
130 V AC
200 V AC , 210 V AC , 220 V AC ,
230 V AC , 240 V AC
Input voltage range
90 V AC ... 264 V AC
Frequency range
45 Hz ... 65 Hz
Current consumption (for nominal
values) typical *
10.5 A (120 V AC) / 5.5 A (230 V AC)
Nominal output voltage (UN) *
120 V AC / 230 V AC
Nominal output current (IN) *
8.3 A (120 V AC) / 4.3 A (230 V AC)
Degree of efficiency ( Nominal load )
( with charged energy storage
device )
92 % ( 120 V AC )
94 % ( 230 V AC )
MTBF (IEC 61709, SN 29500)
217546 h (230 V AC, at 40 °C)
Ambient temperature (operation)
-25 °C ... 60 °C ( > 50 °C Derating:
2.5 %/K )
Dimensions W/H/D
290 mm / 130 mm / 125 mm
Weight
5 kg
Battery technology
VRLA, VRLA-WTR, LI-ION
Nominal voltage ( Energy storage )
2x 24 V DC
Nominal capacity range
3.4 Ah ... 200 Ah
* for further information, see the section on device connection
Make sure you always use the latest documentation.
It can be downloaded from the product at phoenixcontact.net/products.
QUINT4-UPS/1AC/1AC/1KVA
2
Table of contents
1
Description .............................................................................................................................. 1
2
Table of contents ..................................................................................................................... 2
3
Ordering data .......................................................................................................................... 3
4
Technical data ......................................................................................................................... 5
5
Safety and installation notes .................................................................................................. 11
6
Structure................................................................................................................................ 13
7
Mounting and removing ......................................................................................................... 16
8
Device connection ................................................................................................................. 18
9
Device operation ................................................................................................................... 22
10
Method of operation............................................................................................................... 26
11
Signaling................................................................................................................................ 27
12
Interfaces............................................................................................................................... 31
13
Parallel operation................................................................................................................... 32
14
Derating................................................................................................................................. 34
107563_en_00
PHOENIX CONTACT 2 / 34
QUINT4-UPS/1AC/1AC/1KVA
3
Ordering data
Description
Type
Order No.
Pcs./Pkt.
Uninterruptible power supply with IQ technology for DIN QUINT4-UPS/1AC/1AC/
rail mounting. Input: 120/230 V AC, output: 120/230 V AC/ 1KVA
1 kVA. Provides information regarding the state of charge,
remaining runtime, and service life of the rechargeable
battery module at any time, thereby increasing system
availability.
2320283
1
Accessories
Type
Order No.
Pcs./Pkt.
Used for communication between an industrial PC and
Phoenix Contact devices with USB-Mini-B connection.
MINI-SCREW-USBDATACABLE
2908217
1
Fuse, nominal current: 25 A,
FUSE 25A/58V TAC ATO
1021340
2
2901664
1
VS-IP20/10G-IP20/10G-94F/1 1418866
1
Energy storage device, lead AGM, VRLA technology, 24 V UPS-BAT/VRLA/24DC/3.4AH 2320306
DC, 3.4 Ah, tool-free battery replacement, automatic
detection, and communication with QUINT UPS-IQ
1
Energy storage device, lead AGM, VRLA technology, 24 V UPS-BAT/VRLA/24DC/7.2AH 2320319
DC, 7.2 Ah, tool-free battery replacement, automatic
detection, and communication with QUINT UPS-IQ
1
Energy storage device, lead AGM, VRLA technology, 24 V UPS-BAT/VRLA/24DC/12AH
DC, 12 Ah, tool-free battery replacement, automatic
detection, and communication with QUINT UPS-IQ
2320322
1
Energy storage device, lead AGM, VRLA technology, 24 V UPS-BAT/VRLA/24DC/38AH
DC, 38 Ah, automatic detection, and communication with
QUINT UPS-IQ
2320335
1
Energy storage device, lead AGM, VRLA technology, 24 V UPS-BAT/VRLA-WTR/24DC/
DC, 13 Ah, tool-free battery replacement, automatic
13AH
detection, and communication with QUINT UPS-IQ
2320416
1
Energy storage device, lead AGM, VRLA technology, 24 V UPS-BAT/VRLA-WTR/24DC/
DC, 26 Ah, tool-free battery replacement, automatic
26AH
detection, and communication with QUINT UPS-IQ
2320429
1
2-piece universal wall adapter for securely mounting the UWA 130
power supply in the event of strong vibrations. The profiles
that are screwed onto the side of the power supply are
screwed directly onto the mounting surface. The universal
wall adapter is attached on the left/right.
Patch cable, CAT6A, 4-pair, shielded, connection not
crossed (Line), assembled at both ends with RJ45/IP20
connectors; outer sheath material: PUR; length: 1 m
107563_en_00
PHOENIX CONTACT 3 / 34
QUINT4-UPS/1AC/1AC/1KVA
Accessories
Type
Order No.
Pcs./Pkt.
Energy storage device, LI-ION technology, 24 V DC, 120 UPS-BAT/LI-ION/24DC/
Wh, for ambient temperatures of -20°C ... 60°C, automatic 120WH
detection and communication with QUINT UPS-IQ
2320351
1
Energy storage device, LI-ION technology, 24 V DC, 924 UPS-BAT/LI-ION/24DC/
Wh, for ambient temperatures of -25 °C ... 60 °C,
924WH
automatic detection and communication with QUINT
UPS-IQ
2908232
1
Our range of accessories is being continually extended, our current range can be found in the download area.
107563_en_00
PHOENIX CONTACT 4 / 34
QUINT4-UPS/1AC/1AC/1KVA
4
Technical data
Input data
Nominal input voltage
100 V AC , 110 V AC , 120 V AC , 130 V AC
Input voltage range
90 V AC ... 264 V AC
200 V AC , 210 V AC , 220 V AC , 230 V AC , 240 V AC
Frequency range
45 Hz ... 65 Hz
Current consumption (for nominal values) typical *
10.5 A (120 V AC) / 5.5 A (230 V AC)
Permissible backup fuse
20 A (120 V AC, Listed breaker) / B16 ( 230 V AC )
Activation threshold
Can be configured using UPS-CONF software
* for further information, see the section on device connection
Output data
Power factor (cos phi)
0.9
Crest factor
2.8
Switch-over time
0 ms
Classification according to IEC 62040-3
VFI-SS-111
Output data (mains operation)
Nominal output voltage (UN) *
120 V AC / 230 V AC
Frequency
60 Hz ±5 % (At an input frequency of 55 Hz to 2000 m, observe derating)
Degree of pollution
2
Vibration (operation)
5 Hz ... 100 Hz, 0.7g (EN 60068-2-6)
Shock
15g in all directions (EN 60068-2-27)
Climatic class
3K3 (EN 60721)
107563_en_00
PHOENIX CONTACT 7 / 34
QUINT4-UPS/1AC/1AC/1KVA
Approvals
UL approvals
UL/C-UL Recognized UL 1778
Current approvals/permissions for the product can be found in the download area under
phoenixcontact.net/products
107563_en_00
PHOENIX CONTACT 8 / 34
QUINT4-UPS/1AC/1AC/1KVA
Electromagnetic compatibility
Noise emission
CE basic standard
Minimum normative
requirements
Higher requirements in
practice (covered)
Noise emission
EN 62040-02 (Class C2)
--
Conducted noise emission
EN 62040-02 (Class C2)
--
Harmonic currents
EN 61000-3-2 (Class A)
0 kHz ... 2 kHz
not required
not required
Flicker EN 61000-3-3
Immunity according to EN 61000-6-1 (residential), EN 61000-6-2 (industrial)
CE basic standard
Minimum normative
requirements
Higher requirements in
practice (covered)
Housing contact discharge
4 kV (Test Level 2)
6 kV (Test Level 3)
Housing air discharge
8 kV (Test Level 3)
8 kV (Test Level 3)
none
Criterion A
80 MHz ... 1 GHz
80 MHz ... 6 GHz
Electrostatic discharge EN 61000-4-2
Comments
Electromagnetic HF field EN 61000-4-3
Frequency range
Test field strength
10 V/m
10 V/m
Criterion A
Criterion A
Input
2 kV (Test Level 3 asymmetrical)
2 kV (Test Level 3 asymmetrical)
DC input
2 kV (Test Level 3 asymmetrical)
2 kV (Test Level 3 asymmetrical)
Output
2 kV (Test Level 3 asymmetrical)
2 kV (Test Level 3 asymmetrical)
Signal
2 kV (Test Level 3 asymmetrical)
2 kV (Test Level 3 asymmetrical)
Signal USB
2 kV (Test Level 3 asymmetrical)
2 kV (Test Level 3 asymmetrical)
Comments
Criterion B
Criterion A (B for USB)
Input/Output
1 kV (Test Level 2 symmetrical)
2 kV (Test Level 3 asymmetrical)
1 kV (Test Level 2 symmetrical)
2 kV (Test Level 3 asymmetrical)
Signal
1 kV (Test Level 2 asymmetrical)
1 kV (Test Level 2 asymmetrical)
Criterion B
Criterion A
0.15 MHz ... 80 MHz
0.15 MHz ... 80 MHz
10 V
10 V
Comments
Fast transients (burst) EN 61000-4-4
Surge voltage load (surge) EN 61000-4-5
Comments
Conducted interference EN 61000-4-6
Frequency range
Voltage
107563_en_00
PHOENIX CONTACT 9 / 34
QUINT4-UPS/1AC/1AC/1KVA
Immunity according to EN 61000-6-1 (residential), EN 61000-6-2 (industrial)
CE basic standard
Minimum normative
requirements
Higher requirements in
practice (covered)
Criterion A
Criterion A
Frequency range
50 Hz , 60 Hz
50 Hz , 60 Hz
Test field strength
30 A/m
100 A/m
Criterion B
Criterion A
Comments
Power frequency magnetic field EN 61000-4-8
Comments
Key
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected by the device itself.
All technical specifications are nominal and refer to a room temperature of 25 °C and 70% relative humidity at
2000 m above sea level.
107563_en_00
PHOENIX CONTACT 10 / 34
QUINT4-UPS/1AC/1AC/1KVA
5
Safety and installation notes
5.1
Symbols used
5.2
WARNING: Danger to life by electric
shock!
Instructions and possible hazards are indicated by
corresponding symbols in this document.
–
This is the safety alert symbol. It is used to
alert you to potential personal injury hazards.
Obey all safety measures that follow this
symbol to avoid possible personal injuries.
There are different categories of personal injury that are
indicated by a signal word.
–
–
–
–
WARNING
This indicates a hazardous situation which, if
not avoided, could result in death or serious
injury.
–
CAUTION
–
This indicates a hazardous situation which, if
not avoided, could result in minor or moderate
injury.
The following symbols are used to indicate potential
damage, malfunctions, or more detailed sources of
information.
–
–
–
NOTE
This symbol together with the signal word
NOTE and the accompanying text alert the
reader to a situation which may cause
damage or malfunction to the device,
hardware/software, or surrounding property.
This symbol and the accompanying text
provide the reader with additional information
or refer to detailed sources of information.
107563_en_00
Safety and warning notes
–
–
Only skilled persons may install, start up, and operate
the device.
Never carry out work when voltage is present.
Establish connection correctly and ensure protection
against electric shock.
Connect the protective conductor device terminal block
with ground.
Operation of the device is only permitted in mains
network systems with grounded neutral conductor. This
mainly complies with the TN-C-S mains network type.
National regulations must be observed.
Cover termination area after installation in order to avoid
accidental contact with live parts (e. g., installation in
control cabinet).
This unit receives power from more than one source Disconnection of AC source and the energy storage
devices is required to de-energize this unit before
servicing.
Keep flames, embers or sparks away from the module.
When connecting the batteries, observe the polarity and
do not short circuit the pole terminals.
Provide a switch/circuit breaker close to the device at
the AC input, AC output and at the battery terminals,
which are labeled as the disconnecting device for this
device.
Do not disconnect the fuse and / or battery connection
under hazardous location conditions.
Use copper cables for operating temperatures of
75 °C.
CAUTION: Hot surface
The housing can become very hot depending
on the ambient temperature and load of the
power supply (T > 65 °C).
PHOENIX CONTACT 11 / 34
QUINT4-UPS/1AC/1AC/1KVA
More follows
NOTE
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
Observe the national safety and accident prevention
regulations.
Assembly and electrical installation must correspond to
the state of the art.
The uninterruptible power supply is a built-in device.
The protection class IP20 of the device is meant to be
applied in a clean and dry environment.
The device must be installed in a control cabinet that
can be locked and only opened by specialist staff.
Horizontal mounting position (normal mounting
position)
Observe mechanical and thermal limits.
Ensure sufficient convection (minimum gap above/
below: 50 mm). Housing can become hot.
Ensure that the primary-side wiring and secondary-side
wiring are the correct size and have sufficient fuse
protection.
You can find the connection parameters, such as the
necessary stripping length for the wiring with and
without ferrule, in the associated table.
Protect the device against foreign bodies penetrating it,
e.g., paper clips or metal parts.
Depending on the ambient temperature and load on the
uninterruptible power supply, the housing can become
hot.
To reduce the risk of fire, replace only with same type
and rating of fuse.
To reduce the risk of fire, connect the device only to a
circuit provided with the maximum branch circuit
overcurrent protection in accordance with the National
Electrical Code, ANSI/NFPA 70. See the values in the
technical data.
The uninterruptible power supply is maintenance-free.
Repairs may only be carried out by the manufacturer.
The warranty no longer applies if the housing is opened.
The uninterruptible power supply may only be used for
its intended use.
Improper use invalidates the device protection.
Before transporting the uninterruptible power supply,
always disconnect the battery connecting cable from a
battery contact or remove the DC fuse in the battery
compartment.
107563_en_00
–
–
–
–
–
Use current-limited source or suitable fuse.
Use ferrules for flexible cables.
The switching outputs are active outputs according to
SELV. These may only be operated on permitted SELV
circuits.
This equipment is an open-type device meant to be
installed in an enclosure suitable for the environment
that is only accessible with the use of a tool.
Keep these instructions in a safe place – this data sheet
contains important safety notes which must be
observed during installation and maintenance of the
device.
PHOENIX CONTACT 12 / 34
QUINT4-UPS/1AC/1AC/1KVA
6
Structure
6.1
Function elements
QUINT AC-UPS 1000VA Ord.No.2320283
4
6
T 15A
250V
7
3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9
A
Ba lar
t. - m
M
od
AC e
O
Re K
ad
Ba
t.- P> y
St P
Ba ar n
t. - t 2
St 30
ar
V
t1
2
Re 0V
m
ot
e
SG
nd
16
5
Link
8
Parallel Port
USB
5.2
9
5.1
Master 2kVA Power
Master
1kVA
Redundancy
Slave
Single
Alarm
10
Service
SOC
15 20
10
3
2
1
Custom
(Default 0.5)
Bat.-Mode
Bat.-Charge
Service
Input AC 100-240V
L
1.1 1.2
1
Figure 1
Battery 1 DC 24V
Output AC 120/230V
N
L
1.3
N
2.1 2.2
120V
AC OK
230V
P>Pn/Remote
4.1 4.2 4.3
2.3
2
+ -
3
11
PCMode
5
Battery 2 DC 24V
12
Press >6s
13
+ -
4.4
4.5
4.6
14
15
Position of the function elements
Key
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Designation
Connection terminal blocks for AC input
Connection terminal blocks for AC outputs
LED AC OK and LED remote
Bypass fuse
USB interface
Signaling connection terminal blocks
LED parallel run
Communication interface parallel run
Rotary selector switch parallel run mode
LED alarm / service
Rotary selector switch
LED bat. mode / bat. charge
Bar graph for displaying the current charging state of
the energy storage device
Service mode button
Battery terminal blocks
2x base latch (rear side of the device)
107563_en_00
PHOENIX CONTACT 13 / 34
QUINT4-UPS/1AC/1AC/1KVA
6.2
Device dimensions and keep-out areas
132
125
290
5
60
QUINT AC-UPS 1000VA Ord.No.2320283
130
50
90
140
5
T 15A
250V
Ba Ala
t.-M rm
od
AC e
O
Re K
ad
Ba
t.-S P y
>
Ba ta Pn
t.-S rt 2
3
ta 0V
rt
12
Re 0V
m
ote
SG
nd
3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9
Link
Parallel Port
USB
5.2
5.1
Master 2kVA Power
Master
1kVA
Redundancy
Slave
Single
Alarm
Service
SOC
15 20
10
PCMode
5
3
2
1
Custom
(Default 0.5)
Bat.-Mode
Bat.-Charge
Service
Input AC 100-240V
L
N
L
N
120V
AC OK
230V
P>Pn/Remote
2.1 2.2 2.3
Battery 1 DC 24V
Battery 2 DC 24V
4.1 4.2 4.3
4.4 4.5 4.6
+ -
Press >6s
+ -
140
90
50
1.1 1.2 1.3
Output AC 120/230V
60
Figure 2
107563_en_00
Device dimensions and keep-out areas
PHOENIX CONTACT 14 / 34
QUINT4-UPS/1AC/1AC/1KVA
6.3
Block diagram
1.1
L
Input
1.2
N
AC
1.3
PE
2.1
=
=
=
+ 4.1
Battery
4.2
1 DC 4.3
2.2
2.3
=
3.3
C
COM1
3.6
3.7
3.8
COM2
Parallel 5.2
Port
3.4
3.5
+ 4.4
Battery 4.5
2 DC
4.6
3.1
3.2
3.9
L
Output
N
PE AC
Alarm
Bat.-Mode
AC OK
Ready
P>Pn
Bat.-Start 230V
Bat.-Start 120V
Remote
SGnd
5.1
Figure 3
Block diagram
Key
Element
Meaning
Bypass fuse
Switch
Rectifier
DC/DC converter with electrical isolation
=
=
Inverter
Microcontroller
µC
LED
J
Temperature sensor
Selector switch
Battery communication (COM1)
COM1
Battery communication (COM2)
COM2
107563_en_00
PHOENIX CONTACT 15 / 34
QUINT4-UPS/1AC/1AC/1KVA
7
Mounting and removing
7.2
Normal mounting position
The device can be snapped onto all DIN rails
according to EN 60715 and should only be
mounted in the normal mounting position.
NOTE
The device must be installed in a control
cabinet that can be locked and only opened
by specialist staff.
NOTE: enable convection
Depending on the ambient temperature and
load on the uninterruptible power supply, the
housing can become hot.
Ord.No.2320283
Convection
QUINT AC-UPS 1000VA
7.1
In order to ensure sufficient convection, we
recommend a minimum vertical distance of
50 mm to the other devices.
T 15
25 A
0V
3.1
Inpu
tA
L C 10
N 0-240V
US
B
1.1
1.2
Alarm e 3.2 3.
od
3
Bat.-M AC OK y 3.4 3.
Read Pn 5 3.6
P> 0V 3.7
tart 23 120V 3.8
te 3.9
Bat.-S
tart
Remo nd
Bat.-S
SG
5.1
1.3
Out
pu
t
L AC 12
N 0/230V
2.1
2.2
2.3
Pa
12
0V
23
0V
ralle
5.2
AC
OK
P>
Pn
/
Lin
l Po
k
rt
Mas
Sing
ter
le
Re
mo
te
2k
VA
Po
we
r
M
Slav Re 1kaster
e du VA
nd
an
Alar
SO
C
Se
10 15
20
5
3
Bat
2
+tery 1 DC
- 24V
Ord.No.2320283
Se
Bat
4.1
4.2
4.3
ce
ce
PC
M -
1
Cu od
(De sto e
fau m
lt
Ba 0.5
Ba
rvi
+tery 2 DC
- 24V
cy
m
rvi
t.-M )
od
e
t.-Ch
arge
Pres
s >6
s
4.4
4.5
QUINT AC-UPS 1000VA
4.6
T 15
25 A
0V
Figure 5
7.3
3.1
Alarm e 3.2 3.
od
3
Bat.-M AC OK y 3.4 3.
Read Pn 5 3.6
P> 0V 3.7
tart 23 120V 3.8
te 3.9
Bat.-S
tart
US
Remo nd
Bat.-S
B
SG
Inpu
tA
L C 10
N 0-240V
1.1
1.2
5.1
1.3
Out
pu
t
L AC 12
N 0/230V
2.1
2.2
2.3
Pa
12
0V
23
0V
ralle
5.2
Lin
l Po
k
rt
AC
OK
P>
Pn
/R
em
ote
Mas
Sing
ter
le
2k
VA
Po
we
r
M
Slav Re 1kaster
e du VA
nd
an
Alar
SO
C
Se
10 15
20
5
3
Bat
2
+tery 1 DC
- 24V
Se
Bat
4.1
4.2
4.3
ce
4.4
4.5
4.6
Figure 4
Convection
ce
PC
M -
1
Cu od
(De sto e
fau m
lt
Ba 0.5
Ba
rvi
+tery 2 DC
- 24V
cy
m
rvi
t.-M )
od
e
t.-Ch
arge
Pres
s >6
s
Normal mounting position
Mounting the uninterruptible power supply
Proceed as follows to mount the device:
1. In the normal mounting position the device is mounted
on the DIN rail from above. When doing so, ensure that
the base latch engages correctly behind the DIN rail (A).
2. Push the front of the device in the direction of the
mounting surface until the base latch audibly snaps in
(B).
3. Check that the UPS is securely attached to the DIN rail.
A
Click
Figure 6
107563_en_00
B
Snapping onto the DIN rail
PHOENIX CONTACT 16 / 34
QUINT4-UPS/1AC/1AC/1KVA
7.4
Removing the uninterruptible power supply
Proceed as follows to remove the device:
1. Take a suitable screwdriver and insert this into the lock
hole on the base latch (A).
2. Release the lock by lifting the screwdriver (B).
3. Perform these procedures (A) and (B) for the second
base latch.
4. Carefully swivel the device forward (C) so that the lock
slides back into the starting position.
5. Then separate the device from the DIN rail (D).
D
A
Figure 7
7.5
B
7.5.1
Mounting the UWA 130 2-piece universal wall
adapter
The UWA 130 universal wall adapter (Order
No. 2901664) is attached to the device using
the Torx screws provided.
Proceed as follows to install the universal wall adapter:
1. Position the two-piece universal wall adapter on the
right and left side of the housing.
2. Insert the Torx screws into the appropriate hole pattern
on the universal wall adapter so that the necessary
mounting holes of the device can be accessed.
3. Screw the two-piece universal wall adapter onto the
uninterruptible power supply.
C
Removing from the DIN rail
Wall mounting
The UWA 130 universal wall adapter (Order No. 2901664) is
used to attach the uninterruptible power supply directly to
the mounting surface.
The use of the universal wall adapter is recommended under
extreme ambient conditions, e.g., strong vibrations. Thanks
to the tight screw connection between the uninterruptible
power supply and the universal wall adapter or the actual
mounting surface, an extremely high level of mechanical
stability is ensured.
Figure 8
Mounting the UWA 130 universal wall adapter
The maximum tightening torque of the Torx
screw (Torx® T10) is 0.7 Nm.
Make sure you use suitable mounting material
when attaching to the mounting surface.
107563_en_00
PHOENIX CONTACT 17 / 34
QUINT4-UPS/1AC/1AC/1KVA
8
8.1
Device connection
The working ranges of the uninterruptible power supply are
specified in the following table.
AC input
The supply voltage is connected via "Input AC 100 - 240 V"
connection terminal blocks.
Input
Output
Voltage
pos. tol.
Current
Voltage
100V 50Hz / 60Hz 10 %
20 %
10,4 A
100 V
7,8 A
110V 50Hz / 60Hz 10 %
20 %
10,5 A
110 V
8,1 A
889 VA / 800 W
120V 50Hz / 60Hz 10 %
20 %
10,5 A
120 V
8,3 A
1000 VA / 900 W
Voltage
Voltage
neg. tol.
Current
Power
QUINT AC-UPS 1000VA
Ord.No.2320283
Note the different performance and tolerance
values for the various voltages.
T 15
25 A
0V
778 VA / 700 W
130V 50Hz / 60Hz 10 %
20 %
9,7 A
130 V
7,7 A
1000 VA / 900 W
200V 50Hz / 60Hz 20 %
20 %
6,4 A
200 V
5,0 A
1000 VA / 900 W
3.1
Inpu
tA
L C 10
N 0-240V
US
B
1.1
1.2
5.1
1.3
Out
pu
t
L AC 12
N 0/230V
2.1
2.2
210V 50Hz / 60Hz 20 %
20 %
6,0 A
210 V
4,8 A
2.3
1000 VA / 900 W
220V 50Hz / 60Hz 20 %
20 %
5,7 A
220 V
4,5 A
1000 VA / 900 W
230V 50Hz / 60Hz 20 %
15 %
5,5 A
230 V
4,3 A
1000 VA / 900 W
240V 50Hz / 60Hz 20 %
10 %
5,3 A
240 V
4,2 A
1000 VA / 900 W
Alarm e 3.2 3.
od
3
Bat.-M AC OK y 3.4 3.
Read Pn 5 3.6
P> 0V 3.7
tart 23 120V 3.8
te 3.9
Bat.-S
tart
Remo nd
Bat.-S
SG
Pa
12
0V
23
0V
ralle
5.2
AC
OK
P>
Pn
/
Lin
l Po
Mas
Sing
ter
le
Re
mo
te
2k
VA
Alar
Se
10 15
20
5
3
Bat
4.3
Working range of the uninterruptible power
supply
Se
Bat
4.2
The following output voltages are preset by default:
– 120 V AC at an input voltage in the 100 V range
– 230 V AC at an input voltage in the 200 V range
2
+tery 1 DC
- 24V
4.1
The uninterruptible power supply automatically detects if
there is an input voltage from the 100 V range or from the
200 V range.
Po
we
r
M
Slav Re 1kaster
e du VA
nd
an
SO
C
Figure 9
k
rt
ce
ce
PC
M -
1
Cu od
(De sto e
fau m
lt
Ba 0.5
Ba
rvi
+tery 2 DC
- 24V
cy
m
rvi
t.-M )
od
e
t.-Ch
arge
Pres
s >6
s
4.4
4.5
4.6
Figure 10
8.1.1
Connection terminal blocks for input
Protection of the primary side
The uninterruptible power supply automatically detects if
there is a frequency in the 50 Hz or 60 Hz range.
It must be possible to switch the device off using a suitable
disconnection device outside the power supply. For
example, the primary-side line protection is suitable for this
(see technical data).
The following frequency is set at the output:
– 50 Hz +/- 5 % at an input frequency of 45 Hz to 0V 3.7
tart 23 120V 3.8
te 3.9
Bat.-S
tart
US
Remo nd
Bat.-S
B
SG
Inpu
tA
L C 10
N 0-240V
1.1
1.2
tA
L C 10
N 0-240V
1.1
1.2
Out
Out
2.1
2.2
2.3
pu
t
L AC 12
N 0/230V
2.1
2.2
2.3
Pa
12
0V
23
0V
pu
t
L AC 12
N 0/230V
5.1
1.3
5.1
1.3
3.1
Alarm e 3.2 3.
od
3
Bat.-M AC OK y 3.4 3.
Read Pn 5 3.6
P> 0V 3.7
tart 23 120V 3.8
te 3.9
Bat.-S
tart
US
Remo nd
Bat.-S
B
SG
Inpu
ralle
5.2
Lin
l Po
Pa
12
0V
23
0V
5.2
Mas
Mas
ter
le
2k
VA
Alar
Se
3
Bat
4.2
4.3
20
3
Bat
2
ce
1
ce
PC
Mod-
Cu
(De sto e
fau m
lt
Ba 0.5
Ba
rvi
+tery 2 DC
- 24V
rvi
t.-M )
od
e
t.-Ch
arge
Pres
s >6
s
4.4
PC
M -
1
Se
Bat
4.1
ce
5
2
+tery 1 DC
- 24V
cy
m
rvi
cy
Alar
m
Se
20
5
Po
we
r
M
Slav Re 1kaster
e du VA
nd
an
k
Po
we
r
M
Slav Re 1kaster
e du VA
nd
an
k
VA
10 15
4.5
Cu od
(De sto e
fau m
lt 0.5
4.6
Ba
Se
Bat
4.3
2k
10 15
SO
C
4.2
ter
le
SO
C
Sing
+tery 1 DC
- 24V
Lin
rt
Sing
rt
AC
OK
P>
Pn
/R
em
ote
4.1
ralle
l Po
AC
OK
P>
Pn
/R
em
ote
Ba
rvi
ce
+tery 2 DC
- 24V
t.-M )
od
e
t.-Ch
arge
Pres
s >6
s
4.4
4.5
4.6
Figure 11
Connection terminal blocks for output
Figure 12
8.2.1
Battery connection
Protection of the secondary side
The uninterruptible power supply is electronically shortcircuit-proof and idling-proof.
It must be ensured that all output cables are dimensioned
appropriately for the maximum output current or have
separate protection.
107563_en_00
PHOENIX CONTACT 19 / 34
QUINT4-UPS/1AC/1AC/1KVA
8.4
Connection terminal block signaling
The uninterruptible power supply has the signal outputs:
– Alarm (can be inverted via software)
– Bat. Mode (can be inverted and parameterized via
software)
– AC OK (can be inverted and parameterized via
software)
– Ready (can be inverted and parameterized via
software)
– P > Pn (can be inverted and parameterized via software)
QUINT AC-UPS 1000VA
Ord.No.2320283
The uninterruptible power supply also features the signal
inputs:
– Remote
– Bat.-Start 120 V
– Bat.-Start 230 V
T 15
25 A
0V
3.1
Inpu
tA
L C 10
N 0-240V
US
B
1.1
1.2
Alarm e 3.2 3.
od
3
Bat.-M AC OK y 3.4 3.
Read Pn 5 3.6
P> 0V 3.7
tart 23 120V 3.8
te 3.9
Bat.-S
tart
Remo nd
Bat.-S
SG
5.1
1.3
Out
pu
t
L AC 12
N 0/230V
2.1
2.2
2.3
Pa
12
0V
23
0V
ralle
5.2
AC
OK
P>
Pn
/
Lin
l Po
k
rt
Mas
Sing
ter
le
Re
mo
te
2k
VA
Po
we
r
M
Slav Re 1kaster
e du VA
nd
an
Alar
SO
C
Se
10 15
20
5
3
Bat
2
+tery 1 DC
- 24V
Se
Bat
4.1
4.2
4.3
ce
1
ce
PC
M Cu od
(De sto e
fau m
lt
Ba 0.5
Ba
rvi
+tery 2 DC
- 24V
cy
m
rvi
t.-M )
od
e
t.-Ch
arge
Pres
s >6
s
4.4
4.5
4.6
Figure 13
8.5
Signal inputs and outputs
Conductor cross sections
L
[Nm]
[lb in]
8
0.5-0.6
5-7
8
0.5-0.6
5-7
8
0.5-0.6
5-7
0.2-4
30-10
8
0.5-0.6
0.2-1.5
30-12
8
0.5-0.6
5-7
5-7
[mm²]
[mm²]
AWG
[mm]
Input AC 1.1...1.3
0.2-6
0.2-4
30-10
Output AC 2.1...2.3
0.2-6
0.2-4
30-10
0.2-6
0.2-4
30-10
0.2-6
0.2-1.5
Battery 1 DC 4.1...4.3
Battery 2 DC 4.4...4.6
Signals 3.1...3.9
Figure 14
107563_en_00
Screw
Conductor cross sections
PHOENIX CONTACT 20 / 34
QUINT4-UPS/1AC/1AC/1KVA
8.6
Installation of individual components
Installation of uninterruptible power supply units must
correspond to EN 60950 regulations.
Provide a switch/circuit breaker close to the
device at the AC input, AC output and at the
battery terminals, which are labeled as the
disconnecting device for this device.
QUINT
AC UPS
Input AC
L N 5
1.1 1.2 1.3
Output AC
L N 5
2.1 2.2 2.3
Unbuffered
AC load
Battery 1 DC
+ -
Battery 2 DC
+ -
4.1 4.2 4.3
4.4 4.5 4.6
Energy
storage
1
Energy
storage
2
+
+
-
-
Buffered
AC load
5 Protective conductor
Figure 15
Schematic design
The image is a schematic representation of
the design and does not contain all parts.
Observe the installation instructions.
107563_en_00
PHOENIX CONTACT 21 / 34
QUINT4-UPS/1AC/1AC/1KVA
9
Device operation
Basic settings for commissioning can be made directly via
the rotary selection switch on the device. Advanced settings
can be made via the UPS-CONF PC software.
UIN
UOUT
The latest software version is to be found in
the product download area.
t0
9.1
t
Setting the operating mode
You can set the following functions via the rotary selector
switch on the front of the device:
– Buffer period
– PC mode
15 20
10
3
2
Figure 16
PCMode
5
1
Custom
(Default 0.5)
Rotary selector switch
Use a suitable screwdriver to set the rotary
selector switch.
9.1.1
t1
(unlimited,
delivery state)
107563_en_00
t0: mains power failure
t1: after the preset buffer time has expired, the output is
switched off
9.1.2
PC mode
In PC mode, you can individually parameterize the
chronological sequence of the UPS functions via the UPSCONF configuration software.
To access the PC mode of the UPS, set the rotary selector
switch to PC mode.
The following components are required for the
PC mode function:
Data cable MINI-SCREW-USB-DATACABLE
(Order No. 2908217)
Configuration software UPS-CONF (Order
No. 2320403)
Buffer time
Rotary selector
switch setting
1, 2, 3, 5, 10, 15,
20
Custom (default
0.5)
Figure 17
Meaning
The UPS switches off after the set
buffer time.
The UPS switches off after the
individual buffer time set via UPSCONF.
If a buffer time is not set, the UPS
shuts down after 30 seconds.
Buffering with the total stored energy.
An alarm is generated as soon as the
voltage of the energy storage falls
below 20.4 V (default).
In the event of a mains failure, one PC can continue to work,
perform a controlled shutdown, and restart automatically.
1. Delay time
If the mains supply is not restored during the delay time, the
PC is shut down.
2. Program start
After the delay time has expired, it is possible to start a
program.
3. PC shutdown
The time required for PC shutdown is set here.
PHOENIX CONTACT 22 / 34
QUINT4-UPS/1AC/1AC/1KVA
1+2
9.1.3
3
UIN
Service mode
When working in a system, it may be necessary to switch the
uninterruptible power supply unit over to service mode.
UOUT
Service
Press >6s
PC
Figure 20
t0
Figure 18
t1
t2
Service mode buttons
t
In this operating mode, DC battery connection
terminal blocks are deactivated using
software. The active signal output is always
activated when the unit is switched over to
service mode.
t0: mains power failure
t1: delay time and program runtime have expired, PC will be
shut down
Energy storage device replacement
t2: the PC has shut down, the output will be switched off
4. PC idle time
WARNING
Only if the PC is shut down and the mains supply is restored
in the meantime is the output voltage interrupted for the
reset time and the PC then started automatically.
When connecting the batteries take note of
the polarity.
1+2
3
Do not short circuit the pole terminals.
The batteries are maintenance free and may
not be opened.
4
UIN
NOTE
UOUT
When replacing batteries, always use new
batteries from the same production batch.
PC
When replacing batteries, you should always
replace all of the batteries in use.
t0
Figure 19
t1
t2
t3 t4
t
t0: mains power failure
t1: delay time and program runtime have expired, PC will be
shut down
t2: mains restored while PC is shutting down
t3: the PC has shut down and the output will be switched off,
PC idle time starts
t4: the PC idle time has expired, PC is starting back up
107563_en_00
When storing the battery modules, observe
the latest startup date and recharge the
batteries if necessary. The batteries may only
be recharged using the uninterruptible power
supply.
To replace the energy storage device, proceed as follows:
1. Press and hold down the Service Mode button more
than 6 s.
2. Remove the fuses.
3. Remove the cabling of the battery blocks.
4. Remove the batteries.
5. Install the new batteries.
6. Connect the cabling of the battery blocks.
7. Insert the fuses.
8. Exit Service mode.
a) With acknowledgment of the battery replacement:
Press and hold down the Service Mode button for
more than 6 s (the LED bar graph flashes 6 times
and the red LED goes out).
PHOENIX CONTACT 23 / 34
QUINT4-UPS/1AC/1AC/1KVA
9.
Acknowledge the battery replacement to confirm it.
Assuming that there are new batteries, the SOH
(State of Health) and SOC (State of Charge) are
recalculated.
b) Without acknowledgment of the battery
replacement:
Press and hold down the Service Mode button for
more than 1 s and less than 6 s (the red LED goes
out).
Set the buffer time or PC mode.
Remote
UIN
UOUT
t0
t1
t
Notes on disposal
Figure 21
Do not dispose of the UPS and battery
modules in household waste! They should be
disposed of according to the currently
applicable national regulations.
You can return used batteries and
accumulators to Phoenix Contact or the
manufacturer.
t0: remote signal is set in mains operation
t1: no input voltage, output will be switched off
If the Remote signal is set in battery operation, battery
operation is exited immediately. The UPS output is switched
off. This procedure cannot be reversed. The UPS is only
activated once the input voltage is applied.
Remote
9.2
Remote
You can use the Remote signal terminal to:
1. Deactivate and exit battery operation.
2. Perform controlled shutdown of the PC in mains
operation and battery operation.
3. Perform controlled shutdown of the PC in battery
operation.
To perform these steps, you must connect the Remote
signal terminal to the SGnd signal terminal.
UIN
UOUT
t0
Figure 22
t1
t2
t
1. Remote deactivates battery operation
t0: no input voltage
You can deactivate battery operation using this function.
This function is always active when a buffer time has been
preset.
t1: remote signal is set in battery operation, output will be
switched off
t2: input voltage restored, output will be switched on
This function is the default setting in PC mode.
In mains operation, the Remote signal is indicated by the
flashing green LED (see Signaling section).
In the event of mains failure, battery operation is not started.
2. Remote starts undelayed PC-Shutdown
You can shut down the PC immediately via the UPS-CONF
configuration software.
This setting only applies in PC mode.
The Remote signal is indicated by the flashing green LED
(see Signaling section).
The PC shuts down, and the delay time under Item 1 is
skipped (see PC mode section).
Once the PC has shut down, the UPS output is switched off.
When input voltage is present, the connected energy
storage devices remain charged and the system is ready to
use. When you reset the Remote signal, the UPS output is
switched on again.
107563_en_00
PHOENIX CONTACT 24 / 34
QUINT4-UPS/1AC/1AC/1KVA
Remote
Remote
UIN
UIN
UOUT
UOUT
PC
PC
t0
Figure 23
t1
t2
t0
t
Figure 24
t1
t2
t0: remote signal is set during mains operation, PC will be
shut down
t0: remote signal is set in mains operation
t1: PC has shut down, output will be switched off
t2: the PC has shut down, the output will be switched off
t2: remote signal will be reset, output will be switched back
on
9.3
Once the PC has shut down in battery
operation, the uninterruptible power supply
output is switched off. This procedure cannot
be reversed. The uninterruptible power supply
is not activated until the input voltage is
applied.
3. Remote starts immediate PC shutdown only in
battery operation
You can perform immediate shutdown of the PC when
battery operation is entered via the UPS-CONF
configuration software.
This setting only applies in PC mode.
The Remote signal is indicated by the flashing green LED
(see Signaling section).
If the Remote signal is set in mains operation, the PC is shut
down when battery operation is entered. The delay time
under Item 1 is skipped (see section PC mode).
Once the PC has shut down in battery
operation, the uninterruptible power supply
output is switched off. This procedure cannot
be reversed. The uninterruptible power supply
is not activated until the input voltage is
applied.
107563_en_00
t
t1: no input voltage, PC shutdown begins immediately
Battery start (Bat.-Start 120 V / Bat.-Start 230 V)
You can use the signal terminal Bat.-Start 120 V or Bat.Start 230 V to start the UPS without supply voltage on the
input side and create an autonomous supply for the load. To
do this, you must connect the signal terminal Bat.-Start
120 V or Bat.-Start 230 V to the SGnd signal terminal.
– Bat.-Start 120 V: The output voltage is 120 V / 60 Hz
– Bat.-Start 230 V: The output voltage is 230 V / 50 Hz
The maximum duration of the autonomous supply for the
load depends on the charging state of the battery.
The signaling corresponds to the signaling for battery
operation (see Signaling section).
To exit autonomous operation, you must disconnect the
signal terminal Bat.-Start 120 V or Bat.-Start 230 V and the
SGnd signal terminal.
If PC Mode operating mode is set, then in this case the PC
shuts down immediately (see section Remote starts
immediate PC shutdown).
Do not connect the communication line during
a battery start, even for Phoenix Contact
battery types.
An alarm is always generated when
connecting a communication line to a noninitialized battery.
This does not negatively impact the supply to
the connected load.
PHOENIX CONTACT 25 / 34
QUINT4-UPS/1AC/1AC/1KVA
10
Method of operation
10.1
IQ technology
IQ Technology is an intelligent battery management system.
In order to use IQ Technology, one of the following Phoenix
Contact IQ battery types must be implemented:
– UPS-BAT/VRLA/24DC/...
– UPS-BAT/VRLA-WTR/24DC/...
– UPS-BAT/LI-ION/24DC/...
The respective battery type is connected to the
uninterruptible power supply via three connecting cables.
One cable each is connected to the plus (+) and minus (-)
contacts for power transmission. A data cable is provided for
communication.
The communication between the UPS and battery reveals
the UPS of the battery type and the number of connected
batteries. This uninterruptible power supply can use this
information to calculate and configure the following
parameters:
– SOC (State of Charge): current charging state and
remaining runtime of the battery is always available.
– SOH (State of Health): displays the remaining battery
life and warns of failures at an early stage.
– Optimal charging: the optimally set charging
characteristics maximize the remaining service life of
the battery and ensure the fastest possible recharge
time and a high availability.
The batteries of the aforementioned type must first be fully
charged (initialized) in order to determine the SOC and
SOH. After this initial charging process, all IQ Technology
functions are available.
10.2
Battery capacity Number/ Battery string Charging time
(approx.) [h]
Battery type
UPS-BAT/
VRLA/24DC/...
Figure 25
1
7.2AH
1
4
12AH
1
4
4
12AH
2
8
38AH
1
12
38AH
2
24
13AH
1
4
26AH
1
8
26AH
2
16
120WH
1
2
120WH
2
3
924WH
1
11
924WH
2
22
UPS-BAT/
VRLA-WTR/24DC/...
UPS-BAT/
LI-ION/24DC/...
3.4AH
Battery charging times for various battery
capacities
The battery changer for the uninterruptible power supply
operates according to the IUoU charge curve.
I
II
III
=U
=I
= SOC
t
Figure 26
Charging characteristic
Battery management
–
The uninterruptible power supply works with a 48 V battery
system. Connect at least two 24 V batteries.
You can connect up to 5 batteries of the same type per
battery string (battery connection terminals "Battery 1" and
"Battery 2").
–
The following table shows the charging times for different
battery capacitance levels:
–
Segment I: Base charge with a constant charging
current until the end-of-charge equalization voltage is
reached at the battery.
Segment II: Charging with an end-of-charge
equalization voltage until the charging current is
reduced to a specific value.
Segment III: Trickle charging with a constant trickle endof-charge voltage to prevent self-discharge.
When using the Phoenix Contact IQ energy storage
devices, all the necessary charging parameters are set
automatically.
When using standard energy storage devices (not IQ
Technology), you can set the following charging parameters
using the UPS-CONF configuration software:
107563_en_00
PHOENIX CONTACT 26 / 34
End-of-discharge voltage
Area
3 ... 200 Ah
0.2¨... 5 A
50 V to 60 V
Default
2.8 A
56 V
50 V to 60 V
0 mV / K ...
55.2 V
-42 mV / K
-200 mV / K
36 ... 48 V
38.4 V
QUINT AC-UPS 1000VA
Parameter
Nominal capacity
Initial charging current
Absorption charging end
voltage
Float charging end voltage
Temperature compensation
(of the charging voltages)
Ord.No.2320283
QUINT4-UPS/1AC/1AC/1KVA
T 15
25 A
0V
3.1
Inpu
tA
L C 10
N 0-24
0V
US
B
1.1
1.2
Alarm e 3.2 3.
od
3
Bat.-M AC OK y 3.4 3.
Read Pn 5 3.6
P> 0V 3.7
tart 23 120V 3.8
te 3.9
Bat.-S
tart
Remo nd
Bat.-S
SG
5.1
1.3
Out
pu
t
L AC 12
N 0/230V
When using Phoenix Contact IQ battery
types, the configurable parameters are
ignored. The values from the IQ battery types
are used to configure the charger.
2.1
2.2
2.3
Pa
ralle
l
12
0V
23
0V
5.2
Lin
k
Po
rt
AC
OK
P>
Pn
/R
em
ote
Mas
ter
Sing 2kVA
le
Po
we
r
M
Slav Re 1kaster
e du VA
nd
an
cy
SO
Alar
m
Se
rvi
ce
C
10 15
20
5
3
Bat
tery
+
2
1
- DC 24V
Bat
tery
4.1
+
4.2
4.3
If segment III (see the charging characteristic figure) is not
achieved within a specific period, an alarm is generated
(alarm: maximum charging time exceeded).
The uninterruptible power supply uses the charging
parameters to calculate the permitted time.
PC
M -
Cu od
(De sto e
fau m
lt
Ba 0.5)
t.-
Mod
e
Ba
t.-Ch
arge
Pres
s >6
s
4.4
4.5
4.6
Figure 28
11
Se
rvi
ce
2
- DC 24V
1
Signal inputs and outputs
Signaling
QUINT AC-UPS 1000VA
Ord.No.2320283
Various LED indicators are available for visual function
monitoring of the uninterruptible power supply. Active signal
outputs can be used to forward this data to a higher-level
control system.
T 15
25 A
0V
3.1
Inpu
tA
L C 10
N 0-240V
US
1.1
Alarm de 3.2 3.
3
Mo
Bat.- AC OK y 3.4 3.
Read Pn 5 3.6
P> 0V 3.7
23
3.8
Start
120V
3.9
Bat.Start Remote
Bat.B
SGnd
1.2
5.1
1.3
Out
pu
t
L AC 12
N 0/230V
2.1
Pa
ralle
l Po
5.2
12
2.2
2.3
0V
23
0V
AC
Lin
k
rt
Mas
OK
P>
P
n/
ter
Sing
le
Re
mo
te
2k
VA
Po
we
r
M
Slav Re 1kaster
e du VA
nd
an
cy
Alar
SO
m
C
Se
rvi
ce
10 15
20
5
3
Bat
2
+tery 1 DC
- 24V
4.2
4.3
PC
M -
1
Cu od
(De sto e
fau m
lt
Ba 0.5
t.-M )
od
e
t.-Ch
arge
Ba
Se
rvi
ce
Bat
4.1
+tery 2 DC
- 24V
Pres
s >6
s
4.4
4.5
4.6
Figure 27
107563_en_00
LED indicators
PHOENIX CONTACT 27 / 34
QUINT4-UPS/1AC/1AC/1KVA
11.1
LED indicators and signal outputs
For UPS signaling and the corresponding states, please
refer to the table below.
Switching output
Status LED
120V / 230V
Alarm
Bat.
D = 50%
D = 50%
D = 50%
D = 50%
D = 50%
D = 50%
D = 85%
D = 50%
Note
Bat.-Mode
Ready
Alarm
(active low)
AC OK
P>Pn
low
low
low
low
low
Device off
low
low
high
low
low
Initialization, LED test (~3 sec.)
low
high
high
high
low
Mains operation, battery is fully charged
low
low or high
high
high
low
Mains operation, battery charging in process
high
high or low
high
high
low
Battery mode
low
low
low
high
low
Mains operation, battery failure
low
low
low
high
low
Mains operation, service mode for battery change
high
low
low
high
low
Battery mode, battery voltage low
low
high
high
high
high
Mains operation, overload, battery is fully charged
high
high or low
high
high
high
Battery mode, overload
low
low or high
high
high
high
Mains operation, overload, battery charging in process
low
low
low
high
high
Mains operation, overload, battery failure
low
low
low
high
high
Mains operation, overload, service mode for battery
change
low
high
high
high
low
Mains operation, remote contact shorted to SGnd,
battery is fully charged
low
low or high
high
high
low
Mains operation, remote contact shorted to SGnd,
battery charging in process
high
high or low
high
high
low
Battery mode, remote contact shorted to SGnd,
(only PC-Mode)
low
low
low
high
low
Mains operation, remote contact shorted to SGnd,
battery failure
low
low
low
high
low
Mains operation, remote contact shorted to SGnd,
service mode for battery change
Link
Single mode
Parallel system in operation
Malfunction in parallel system
D = 50%
D = 50%
LED flashing
LED on
LED off
D = 85%
100%
Figure 29
107563_en_00
t
LED indicators and signal outputs
PHOENIX CONTACT 28 / 34
QUINT4-UPS/1AC/1AC/1KVA
11.2
Signal outputs
Alarm
In the event of an alarm, the signal output is active (low
level). The signal status can be inverted via the UPS-CONF
configuration software.
A digital transistor output is available as a signal contact.
This signal is indicated visually by a red LED.
Possible general alarms include:
– Shutdown when overloaded
– Service mode active
– Bypass fuse defective
Possible battery alarms include:
– No battery connected
– Batteries of different types connected
– Low battery voltage in the network operation
– Block voltage difference too large
– Permitted charging time exceeded
– End of the battery life reached SOH (State of Health),
can be adjusted using UPS-CONF
– Low battery voltage in battery operation, can be
adjusted using UPS-CONF
– Low SOC (State of Charge) in battery operation, can be
adjusted using UPS-CONF
– Low remaining buffer time in battery operation, can be
adjusted using UPS-CONF
Possible alarms in the parallel system include:
– Impermissible settings in the devices
– No redundancy present (in general, the total load is too
large)
– System error
Either the 120 V or 230 V LED lights up permanently
(depending on the detected voltage range).
You can assign other additional information to this signal
output using the UPS-CONF configuration software.
Ready
If the energy storage devices are fully charged
(SOC = 100 %), the signal output is active (high level).
The signal status can be inverted via the UPS-CONF
configuration software.
A digital transistor output is available as a signal contact.
You can assign other additional information to this signal
output using the UPS-CONF configuration software.
P>Pn
If the output power exceeds the maximum permitted output
power, the signal output is active (high level).
The signal status can be inverted via the UPS-CONF
configuration software.
A digital transistor output is available as a signal contact.
This signal is indicated visually by a green LED.
Either the 120 V or 230 V LED flashes (depending on the
detected voltage range).
You can assign other additional information to this signal
output using the UPS-CONF configuration software.
11.3
Signal inputs
Remote
You can activate and trigger various functions using the
remote signal input. For additional information, please refer
to the "Remote device operation" section.
This signal is indicated visually by a green LED.
Bat.-Mode
If there is a mains failure and the load is being supplied from
the energy storage device, the signal output is active (high
level). The signal status can be inverted via the UPS-CONF
configuration software.
A digital transistor output is available as a signal contact.
This signal is indicated visually by a yellow LED.
You can assign other additional information to this signal
output using the UPS-CONF configuration software.
AC OK
If the load is being supplied, the signal output is active (high
level). The signal status can be inverted via the UPS-CONF
configuration software.
Either the 120 V or 230 V LED flashes (depending on the
detected voltage range).
A change made to the remote function using
the UPS-CONF configuration software is not
applied until a corresponding status change of
the remote signal input or device restart has
been carried out.
Bat.-Start (Bat.-Start 120 V / Bat.-Start 230 V)
You can use the Bat.-Start 230 V or Bat.-Start 120 V signal
terminals to start the UPS without supply voltage on the
input side . For additional information, please refer to the
section "Device operation, battery start".
A digital transistor output is available as a signal contact.
This signal is indicated visually by a green LED.
107563_en_00
PHOENIX CONTACT 29 / 34
QUINT4-UPS/1AC/1AC/1KVA
11.4
LED bar graph display / Bat. LED
The LED bar graph display consists of five individual
segments and displays the SOC (state of charge) of the
energy storage device. In this case, each segment
corresponds to 20 % of the total capacity.
SOC
100%
The individual segments of the LED bar graph display are
illuminated based on the current state of charge (SOC) of
the energy storage device. The current charging state is
indicated by permanently illuminated segments. In this
case, each segment corresponds to 20 % of the total
capacity.
The flashing segment displays the charging process for the
next 20 % segment.
Standard energy storage devices (without IQ
technology)
80%
40%
The bottom LED bar graph display segment and bat. LED
flash during the charging process.
If the energy storage device is fully charged, the bottom
segment of the LED bar graph display continues to flash and
the bat. LED is off.
20%
11.4.2 Discharging
60%
IQ energy storage device - not initialized
Figure 30
Bar graph display (SOC)
The energy content is not displayed because the state of
charge of the energy storage device is unknown.
Depending on the type of energy storage device used
(whether it is equipped with IQ technology or not), the bar
graph display varies from the battery charging display to the
battery discharging display.
During the discharging process, the LED bar graph display
empties from top to bottom. The bat. LED lights up
permanently.
The battery LED (bat. mode / bat. charge) indicates whether
the battery is being charged or discharged.
IQ energy storage device - initialized
The energy storage device has already been fully charged
once. The energy storage characteristics are determined.
11.4.1 Charging
The charging time of the energy storage
device depends on the capacity and energy
supplied by the uninterruptible energy supply
unit. The maximum charging time can last up
to several hours.
IQ energy storage device - not initialized
As the state of charge (SOC) of the energy storage device is
still unknown when installing it for the first time, the device
must be fully charged once. Until the device has been fully
charged for the first time, the LED bar graph display fills up
repeatedly from bottom to top.
The bat. LED flashes during the charging process.
If the energy storage device is fully charged, all five
segments of the LED bar graph display light up and the bat.
LED is off.
The individual segments of the LED bar graph display are
illuminated based on the current state of charge (SOC) of
the energy storage device. The current charging state is
indicated by permanently illuminated segments. In this
case, each segment corresponds to 20 % of the total
capacity.
If the SOC (State of Charge) < 20 %, the bottom segment of
the LED bar graph display lights up in red.
During the discharging process, the bat. LED lights up
permanently.
Standard energy storage devices (without IQ
technology)
During the discharging process, the LED bar graph display
is off. The bat. LED lights up permanently.
IQ energy storage device - initialized
The energy storage device has already been fully charged
once. The energy storage characteristics are determined.
107563_en_00
PHOENIX CONTACT 30 / 34
QUINT4-UPS/1AC/1AC/1KVA
12
Interfaces
The uninterruptible power supply unit is equipped with
3 interfaces for data transmission.
1. USB interface MINI type B
2. Communication interface parallel run
3. Service USB interface Mini type B (bottom of the
device)
Designation
Mini type B USB connector with screw connection
USB plug type A
Cable length: 3 m
12.2
Communication interface parallel run
The uninterruptible power supply is equipped with a USB
Mini type B interface for data transmission.
A data cable is required for communicating with a PC or a
higher-level controller.
Ord.No.2320283
USB interface MINI type B
QUINT AC-UPS 1000VA
12.1
No.
1
2
3
T 15
25 A
0V
3.1
Inpu
tA
L C 10
N 0-240V
US
Ord.No.2320283
1.1
1.2
B
Alarm de 3.2 3.
3
Mo
Bat.- AC OK y 3.4 3.
Read Pn 5 3.6
P> 0V 3.7
23
3.8
Start
120V
3.9
Bat.Start Remote
Bat.SGnd
5.1
1.3
Out
pu
QUINT AC-UPS 1000VA
t
L AC 12
N 0/230V
2.1
Pa
ralle
5.2
12
2.2
2.3
0V
23
0V
AC
P>
Pn
T 15
25 A
0V
Lin
k
l Po
rt
Mas
OK
/R
Sing
em
ter
le
ote
2k
VA
Po
we
r
M
Slav Re 1kaster
e du VA
nd
an
cy
Alar
SO
m
C
Se
rvi
ce
10 15
20
5
3
Bat
2
+tery 1 DC
- 24V
4.2
4.3
3.1
Alarm e 3.2 3.
od
3
Bat.-M AC OK y 3.4 3.
Read Pn 5 3.6
P> 0V 3.7
tart 23 120V 3.8
te 3.9
Bat.-S
tart
US
Remo nd
Bat.-S
B
SG
Inpu
tA
L C 10
N 0-240V
1.1
1.2
PC
M -
1
Cu od
(De sto e
fau m
lt
Ba 0.5
t.-M )
od
e
t.-Ch
arge
Ba
Se
rvi
ce
Bat
4.1
+tery 2 DC
- 24V
Pres
s >6
s
4.4
4.5
4.6
5.1
1.3
Out
pu
t
L AC 12
N 0/230V
2.1
2.2
2.3
Pa
12
0V
23
0V
ralle
5.2
Lin
l Po
k
rt
AC
OK
P>
Pn
/R
em
ote
Figure 33
Mas
Sing
ter
le
2k
Po
we
r
M
Slav Re 1kaster
e du VA
nd
an
Alar
SO
C
Se
10 15
20
5
3
Bat
tery
+
2
1
Se
Bat
4.1
4.2
4.3
cy
m
rvi
ce
PC
M -
1
Cu od
(De sto e
fau m
lt 0.5
Ba
- DC 24V
Ba
rvi
Communication interface parallel run
VA
ce
+tery 2 DC
- 24V
t.-M )
od
e
t.-Ch
arge
Pres
s >6
You can find additional information on the communication
interface in the Parallel Operation section.
s
4.4
4.5
4.6
Figure 31
USB interface MINI type B
12.1.1 MINI-SCREW-USB-DATACABLE
The uninterruptible power supply unit is connected to the
USB PC connection with data cable MINI-SCREW-USBDATACABLE (Order No. 2908217) via USB interface mini
type B.
2
12.3
Service USB interface Mini type B
Connection via the service Mini type B USB
interface is not electrically isolated.
The uninterruptible power supply unit is connected to the
USB PC connection with data cable CABLE-USB/MINIUSB-3.0M (Order No. 2986135) via the service Mini Type B
USB interface.
You can find the interface on the right bottom side of the
device.
The data cable can be used to parameterize the
uninterruptible power supply, even if there is no input
voltage.
3
1
Figure 32
107563_en_00
MINI-SCREW-USB-DATACABLE
PHOENIX CONTACT 31 / 34
QUINT4-UPS/1AC/1AC/1KVA
13
Parallel operation
You can connect two UPS devices in parallel in order to
increase the power or to supply the loads redundantly.
Configuration is carried out using the parallel running mode
rotary selector switch on the front of the device.
Set the rotary selector switch of a UPS to "Master 2 kVA
Power" to increase its power. Set the rotary selector switch
of the second UPS to “Slave“.
Set the rotary selector switch of a UPS to "Master 1 kVA
Redundancy" to ensure a redundant load supply. Set the
rotary selector switch of the second UPS to “Slave“.
The rotary selector switch configuration is applied during
device startup. Changes to the rotary selector switch
configuration during operation have no effect on the proper
functioning of the UPS.
During parallel operation, connect the uninterruptible power
supplies with an RJ45 twisted pair patch cable via the
parallel running communication interfaces.
The outputs of the two UPS devices are connected to each
other directly. The output power is distributed symmetrically
to each UPS in all parallel running modes.
Observe the following points when carrying out parallel
connection:
1. Always connect the same number and same type of
energy storage devices to the UPS devices.
2. Use the parallel running rotary selector switch to
configure the individual UPS devices (see the section
"Parallel operation").
3. Use the same cable cross sections for wiring.
4. Use the same cable lengths up to the AC convergence
point.
5. Operate the UPS devices in the same temperature
conditions.
107563_en_00
PHOENIX CONTACT 32 / 34
QUINT4-UPS/1AC/1AC/1KVA
Parallel Port
5.2
Parallel Port
5.2
QUINT AC
UPS
(Master)
Input AC
L N
1.1 1.2 1.3
Output AC
L N
2.1 2.2 2.3
Battery 1 DC
+ 4.1 4.2 4.3
Input AC
L N
1.1 1.2 1.3
Battery 2 DC
+ 4.4 4.5 4.6
L
QUINT AC
UPS
(Slave)
Input AC
L N
2.1 2.2 2.3
Battery 1 DC
+ 4.1 4.2 4.3
Battery 2 DC
+ 4.4 4.5 4.6
L
N
N
PE
PE
Energy
storage
1
Energy
storage
2
Energy
storage
1
Energy
storage
2
Buffered
AC load
Figure 34
Schematic layout - parallel operation
During parallel operation, the following settings are
transferred from the master device to the slave device. The
settings of the slave device are ignored here:
– Selecting the operating mode (buffer time / PC mode)
using the rotary selector switch
– Remote signal terminal operation
– Configuration using UPS-CONF configuration software.
Changes to the settings can only be made using the
master device and are permanently transferred to the
slave device. Both of these devices can read
parameters.
The following alarm messages are available in parallel
operation:
– Parallel mode is not possible:
This combination of two master or slave devices is not
permitted.
– No redundancy:
The device fails in redundant operation or
the total power is too high in redundant operation. This
means that in the case of a device fault, the load cannot
be supplied using a device.
– System error:
Each alarm in parallel operation is displayed as a sum
message. All alarm signal outputs can be used.
107563_en_00
PHOENIX CONTACT 33 / 34
QUINT4-UPS/1AC/1AC/1KVA
14.2
Increasing power
Parallel connection for increased power is used when
extending existing systems. If the individual UPS does not
cover the current consumption of the most powerful
consumer, parallel connection of UPS devices is
recommended. The output power can be doubled for two
UPS devices connected in parallel.
Settings in the parallel running mode rotary selector switch:
– UPS 1: "Master 2 kVA Power"
– UPS 2: "Slave"
13.2
Redundant operation
Settings in the parallel running mode rotary selector switch:
– USV 1: „Master 1 kVA Redundancy”
– UPS 2: "Slave"
Derating
14.1
Ambient temperature
A power derating of 0.6%/100 m should be observed for
installation heights between 2000 and 3000 m.
105
100
95
Redundant operation of UPS devices is suitable for
supplying systems and system parts which place
particularly high demands on operational safety.
In the event of a fault, it must be ensured that one of the
uninterruptible power supplies is able to provide the total
required power for the load.
14
Installation height
The uninterruptible power supply can be operated at an
installation height of up to 2000 m without any limitations.
Different data applies for installation locations above
2000 m due to the differing air pressure and the reduced
convection cooling associated with this.
POut [%]
13.1
90
85
80
0
1000
2000
3000
H [m]
Figure 36
Altitude-dependent derating
POut [%]
At an ambient temperature of up to 50 °C, the uninterruptible
power supply supplies the continuous nominal power. At an
ambient temperature of > 50 °C, a power derating of 2.5%/K
should be observed for the uninterruptible power supply.
100
90
80
70
60
50
0
10
20
30
40
50
60
TA [°C]
Figure 35
107563_en_00
Temperature-dependent derating
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com
34 / 34