https://www.phoenixcontact.com/us/products/2688048
I/O module - AXL F DO16/3 2F - 2688048
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Axioline F, Digital output module, Digital outputs: 16, 24 V DC, 500 mA, connection method: 3-wire, transmission
speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F
connectors
Product Description
The module is designed for use within an Axioline F station.
It is used to output digital signals.
The outputs are protected against short circuit and overload.
Your advantages
16 digital outputs
24 V DC, 500 mA
Connection of actuators in 2 and 3-wire technology
Minimum update time of < 100 μs
Device rating plate stored
Approved for use in applications which meet functional safety requirements
Key Commercial Data
Packing unit
1 pc
GTIN
GTIN
4046356501583
Weight per Piece (excluding packing)
280.000 g
Custom tariff number
85389091
Country of origin
Germany
Technical data
Dimensions
Width
53.6 mm
09/08/2019 Page 1 / 11
https://www.phoenixcontact.com/us/products/2688048
I/O module - AXL F DO16/3 2F - 2688048
Technical data
Dimensions
Height
129.9 mm
Depth
54 mm
Note on dimensions
The depth is valid when a TH 35-7,5 DIN rail is used (according to
EN 60715).
Ambient conditions
Ambient temperature (operation)
-25 °C ... 60 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)
5 % ... 95 % (non-condensing)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection
IP20
Connection data
Designation
Axioline F connector
Connection method
Push-in connection
Note on the connection method
Please observe the information provided on conductor cross sections in
the “Axioline F: system and installation” user manual.
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
1.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
1.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
16
Stripping length
8 mm
General
Mounting type
DIN rail
Net weight
234 g
Note on weight specifications
with connectors and bus base module
Interfaces
Designation
Axioline F local bus
No. of channels
2
Connection method
Bus base module
Transmission speed
100 Mbps
Axioline potentials
Designation
Axioline F local bus supply (UBus)
Supply voltage
5 V DC (via bus base module)
09/08/2019 Page 2 / 11
https://www.phoenixcontact.com/us/products/2688048
I/O module - AXL F DO16/3 2F - 2688048
Technical data
Axioline potentials
Current consumption
max. 120 mA (up to HW 04)
max. 60 mA (from HW 05)
Power consumption
max. 600 mW (up to HW 04)
max. 300 mW (from HW 05)
Designation
Supply for digital output modules (UO)
Supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumption
max. 8 A (provide external protection)
Power consumption
max. 240 W (of which 560 mW with internal losses)
Type of protection
Surge protection of the supply voltage
Polarity reversal protection of the supply voltage
Protection
max. 8 A (polarity reversal protection up to 5 A)
Digital outputs
Output name
Digital outputs
Connection method
Push-in connection
Connection technology
3-wire
Number of outputs
16
Type of protection
Short-circuit protection, overload protection of the outputs
Output voltage
24 V
Nominal output voltage
24 V DC
Maximum output current per channel
500 mA
Maximum output current per module
8 A (provide external protection)
Nominal load, inductive
max. 12 VA (1.2 H, 48 Ω, with nominal voltage)
Nominal load, lamp
max. 12 W (at nominal voltage)
Nominal load, ohmic
max. 12 W (48 Ω, with nominal voltage)
Electrical isolation
Test section
5 V communications power (logic), 24 V supply (I/O) 500 V AC 50 Hz 1
min.
5 V supply (logic)/functional earth ground 500 V AC 50 Hz 1 min.
24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min.
Standards and Regulations
Mechanical tests
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g
Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Environmental Product Compliance
09/08/2019 Page 3 / 11
https://www.phoenixcontact.com/us/products/2688048
I/O module - AXL F DO16/3 2F - 2688048
Technical data
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values
Drawings
Block diagram
Internal wiring of the terminal points
09/08/2019 Page 4 / 11
https://www.phoenixcontact.com/us/products/2688048
I/O module - AXL F DO16/3 2F - 2688048
Connection diagram
Connection example
09/08/2019 Page 5 / 11
https://www.phoenixcontact.com/us/products/2688048
I/O module - AXL F DO16/3 2F - 2688048
Diagram
Maximum energy consumption of the outputs when switching off inductive loads
The diagram shows the maximum amount of energy that may be fed back into the corresponding output groups (outputs 1 to 4, 5 to 8, 9 to 12, 13 to 16)
for each switch off procedure when switching off an inductive load without external freewheeling circuit.
The current data refers to the ohmic DC voltage component of the inductive load.
Note: Restrict freewheeling voltage to a maximum of -15 V when using an external freewheeling circuit. The external freewheeling circuit has no
function in the event of a higher negative voltage.
09/08/2019 Page 6 / 11
https://www.phoenixcontact.com/us/products/2688048
I/O module - AXL F DO16/3 2F - 2688048
Dimensional drawing
Classifications
eCl@ss
eCl@ss 4.0
27240400
eCl@ss 4.1
27240400
eCl@ss 5.0
27242200
eCl@ss 5.1
27242600
eCl@ss 6.0
27242600
eCl@ss 7.0
27242604
eCl@ss 8.0
27242604
eCl@ss 9.0
27242604
ETIM
ETIM 3.0
EC001599
ETIM 4.0
EC001599
09/08/2019 Page 7 / 11
https://www.phoenixcontact.com/us/products/2688048
I/O module - AXL F DO16/3 2F - 2688048
Classifications
ETIM
ETIM 5.0
EC001599
ETIM 6.0
EC001599
ETIM 7.0
EC001599
UNSPSC
UNSPSC 6.01
43172015
UNSPSC 7.0901
43201404
UNSPSC 11
39121311
UNSPSC 12.01
39121311
UNSPSC 13.2
32151602
Approvals
Approvals
Approvals
DNV GL / PRS / BV / LR / KR / NK / ABS / RINA / UL Listed / cUL Listed / EAC / LR / UL Listed / cUL Listed / NK / ABS / PRS / DNV GL / BV / RINA /
KR / BSH / EAC
Ex Approvals
Approval details
DNV GL
https://approvalfinder.dnvgl.com/
TAA00000DF
PRS
http://www.prs.pl/
TE/2239/880590/19
BV
http://www.veristar.com/portal/veristarinfo/generalinfo/
approved/approvedProducts/equipmentAndMaterials
36433/B0 BV
09/08/2019 Page 8 / 11
https://www.phoenixcontact.com/us/products/2688048
I/O module - AXL F DO16/3 2F - 2688048
Approvals
LR
http://www.lr.org/en
14-20019
KR
http://www.krs.co.kr/eng/main/main.aspx
HMB17372-AC002
NK
http://www.classnk.or.jp/hp/en/
14A006
http://www.eagle.org/eagleExternalPortalWEB/
18-HG1767360-PDA
ABS
RINA
http://www.rina.org/en
ELE256518XG
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
EAC
EAC-Zulassung
LR
http://www.lr.org/en
14-20019
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
09/08/2019 Page 9 / 11
https://www.phoenixcontact.com/us/products/2688048
I/O module - AXL F DO16/3 2F - 2688048
Approvals
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
NK
http://www.classnk.or.jp/hp/en/
14A006
http://www.eagle.org/eagleExternalPortalWEB/
18-HG1767360-PDA
ABS
PRS
http://www.prs.pl/
TE/2239/880590/19
DNV GL
https://approvalfinder.dnvgl.com/
TAA00000DF
BV
http://www.veristar.com/portal/veristarinfo/generalinfo/
approved/approvedProducts/equipmentAndMaterials
36433/B0 BV
RINA
http://www.rina.org/en
ELE256518XG
KR
http://www.krs.co.kr/eng/main/main.aspx
HMB17372-AC002
http://www.bsh.de/de/index.jsp
840
EAC-Zulassung
BSH
EAC
Accessories
Accessories
09/08/2019 Page 10 / 11
https://www.phoenixcontact.com/us/products/2688048
I/O module - AXL F DO16/3 2F - 2688048
Accessories
DIN rail connector
Bus connector - AXL F BS F - 2688129
Axioline F bus base module for housing type F
Terminal marking
Zack marker strip - ZB 20,3 AXL UNPRINTED - 0829579
Zack marker strip for Axioline F (device labeling), in 2 x 20.3 mm pitch, unprinted, 25-section, for individual labeling with
B-STIFT 0.8, X-PEN, or CMS-P1-PLOTTER
Zack Marker strip, flat - ZBF 10/5,8 AXL UNPRINTED - 0829580
Zack Marker strip, flat, Strip, white, unlabeled, can be labeled with: PLOTMARK, CMS-P1-PLOTTER, mounting type:
snap into flat marker groove, for terminal block width: 10.15 mm, lettering field size: 4 of 10.15 x 5 mm and 1 of 5.8 x 5
mm, Number of individual labels: 50
Phoenix Contact 2019 © - all rights reserved
http://www.phoenixcontact.com
09/08/2019 Page 11 / 11
很抱歉,暂时无法提供与“2688048”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格 香港价格
- 1+3287.120661+409.51733