https://www.phoenixcontact.com/us/products/2692076
I/O module - ILB S3 AI4 AO2-2TX - 2692076
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Inline Block IO Analog I/O module, Sercos III, inputs: 0-20 mA, 4-20 mA, ±20 mA, 0-5 V, ±5 V, 0-10 V, ±10
V, Pt 100, Pt 1000, Ni 1000..., outputs: 0-5 V, ±5 V, 0-10 V, ±10 V, 0-20 mA, ±20 mA, 4-20 mA, 2-, 3-, 4-wire
connection
Product description
The multifunctional, analog Inline Block I/O modules can be used universally. The four inputs either offer the difference measured between analog
current / voltage signals or the option of connecting resistance thermometers (RTDs). Furthermore, the current or voltage actuators can be connected at
the two outputs. In addition, all channels are equipped with shield connections as a standard and are provided with the 2, 3 or 4-conductor system. The
analog signals are made available with a resolution of 16 bits.
The plugs can be labeled using hinged labeling fields. The fields have insert cards that can be labeled individually to suit the application. Additionally,
there is the proven ZBFM-6... Zack marker strip for labeling the terminal points.
Product Features
Short-circuit-proof outputs
2 shielded analog signal outputs with 4 voltage and 3 current ranges
Sensor supply with channel-specific integrated short-circuit and overload protection
Adjustable filter times
4 voltage measuring ranges and 3 current measuring ranges
4 shielded analog differential signal inputs or 4 universal RTD inputs
Connection of actuators in 2-wire technology
Connection of sensors in 2, 3, and 4-wire technology
Key commercial data
Packing unit
1 pc
Custom tariff number
85176200
Country of origin
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
09/03/2014 Page 1 / 6
https://www.phoenixcontact.com/us/products/2692076
I/O module - ILB S3 AI4 AO2-2TX - 2692076
Technical data
Dimensions
Width
156 mm
Height
136.8 mm
Depth
57 mm
Ambient conditions
Ambient temperature (operation)
-25 °C ... 60 °C
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 85 % (non-condensing)
Permissible humidity (storage/transport)
10 % ... 95 % (non-condensing)
Air pressure (operation)
70 kPa ... 108 kPa (up to 3500 m above mean sea level)
Air pressure (storage/transport)
70 kPa ... 108 kPa (up to 3500 m above mean sea level)
Degree of protection
IP20
General
Weight
465 g
Mounting type
DIN rail
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Test section
Sercos III/logic area 500 V AC 50 Hz 1 min
Sercos III/analog I/O 500 V AC 50 Hz 1 min
Sercos III/communications power 500 V AC 50 Hz 1 min
Sercos III/initiator supply 500 V AC 50 Hz 1 min
Sercos III/functional earth ground 500 V AC 50 Hz 1 min
Logic/analog I/O 500 V AC 50 Hz 1 min
Logic area/initiator supply 500 V AC 50 Hz 1 min
Logic area/functional earth ground 500 V AC 50 Hz 1 min
Analog I/O/communications power 500 V AC 50 Hz 1 min
Analog I/O/initiator supply 500 V AC 50 Hz 1 min
Functional earth ground/analog I/O (isolating distance) 500 V AC 50 Hz 1
min
Functional earth ground/communications power 500 V AC 50 Hz 1 min
Functional earth ground/initiator supply 500 V AC 50 Hz 1 min
Mechanical tests
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g
Interfaces
Fieldbus system
Sercos
Designation
Inline local bus
Connection method
RJ45 socket, shielded
Transmission speed
100 MBit/s
09/03/2014 Page 2 / 6
https://www.phoenixcontact.com/us/products/2692076
I/O module - ILB S3 AI4 AO2-2TX - 2692076
Technical data
Interfaces
Transmission physics
Copper
Inline potentials
Communications power UL
24 V DC
Power supply at UL
max. 8 A
Current consumption from UL
max. 220 mA (AO-I nominal load)
Segment supply voltage US
24 V DC
Power supply at US
max. 8 A
Current consumption from US
max. 220 mA (Maximum full load)
Axioline potentials
Analog inputs
Number of inputs
max. 4 (Differential inputs, voltage or current can be chosen separately)
Connection method
Spring-cage connection
2, 3, 4-wire (shielded)
Input name
Analog inputs
A/D conversion time
typ. 180 µs
Resolution A/D
16 bit
Limit frequency (3 dB)
120 Hz (default for 4.5 ms filter)
450 Hz (for 1.1 ms filter)
Data formats
IB IL, S7-compatible
Measured value resolution
16 bits (15 bits + sign bit)
Current input signal
0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
Input resistance current input
typ. 107 Ω
Voltage input signal
0 V ... 5 V
-5 V ... 5 V
0 V ... 10 V
-10 V ... 10 V
Input resistance of voltage input
typ. 276 kΩ
Number of inputs
4 (differential inputs, voltage)
Type of protection
Overload protection, short-circuit protection of sensor supply
Open circuit response
Goes to 0 V
Voltage input signal
0 V ... 5 V
-5 V ... 5 V
0 V ... 10 V
-10 V ... 10 V
09/03/2014 Page 3 / 6
https://www.phoenixcontact.com/us/products/2692076
I/O module - ILB S3 AI4 AO2-2TX - 2692076
Technical data
Analog inputs
Input resistance of voltage input
typ. 276 kΩ
Number of inputs
4 (differential inputs, current)
Type of protection
Short-circuit protection for the sensor supply
Open circuit response
Going to 0 mA; open-circuit detection from 4 mA ... 20 mA
Current input signal
0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
Input resistance current input
typ. 107 Ω
Number of inputs
4
Input name
Analog RTD inputs
Sensor types (RTD) that can be used
Pt100, Pt500, Pt1000, Ni100, Ni1000, Ni1000 L&G
Linear resistance measuring range
0 Ω ... 3200 Ω
0 Ω ... 9500 Ω
Protective circuit
Overload protection, short-circuit protection of sensor supply
Analog outputs
Number of outputs
2
Connection method
Spring-cage connection
2-wire (shielded)
Output name
Analog outputs
D/A conversion time
typ. 70 µs
D/A resolution
16 bit
Type of protection
Short-circuit protection of outputs
Process data update
17 ms
Current output signal
0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
Voltage output signal
0 V ... 5 V
-5 V ... 5 V
0 V ... 10 V
-10 V ... 10 V
Load/output load voltage output
> 2 kΩ
Classifications
eCl@ss
eCl@ss 4.0
27250303
eCl@ss 4.1
27250303
09/03/2014 Page 4 / 6
https://www.phoenixcontact.com/us/products/2692076
I/O module - ILB S3 AI4 AO2-2TX - 2692076
Classifications
eCl@ss
eCl@ss 5.0
27250303
eCl@ss 5.1
27250303
eCl@ss 6.0
27242601
eCl@ss 7.0
27242601
eCl@ss 8.0
27242601
ETIM
ETIM 2.0
EC001431
ETIM 3.0
EC001596
ETIM 4.0
EC001596
ETIM 5.0
EC001596
UNSPSC
UNSPSC 6.01
43172015
UNSPSC 7.0901
43201404
UNSPSC 11
43172015
UNSPSC 12.01
43201404
UNSPSC 13.2
43201404
Approvals
Approvals
Approvals
UL Listed / cUL Listed / UL Listed / cUL Listed / cULus Listed
Ex Approvals
Approvals submitted
Approval details
UL Listed
09/03/2014 Page 5 / 6
https://www.phoenixcontact.com/us/products/2692076
I/O module - ILB S3 AI4 AO2-2TX - 2692076
Approvals
cUL Listed
UL Listed
cUL Listed
cULus Listed
Drawings
Connection diagram
Dimensioned drawing
AI RTD AI RTD AI RTD AI RTD AO
141
US
-
OUT2
- -
+
UL
+
+
U
SERCOS III
59
120
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com
09/03/2014 Page 6 / 6