Inline controller with integrated pulse/direction/PWM interface, RS-485/RS-422, fast counters, and incremental
encoder inputs, with programming options according to IEC 61131-3
Product Description
The ILC 191 ME/INC modular small-scale controller for the Inline I/O system is at the heart of Easy Automation. The new ILC 1X1 series is characterized
by its support for the Modbus/TCP and PROFINET Ethernet-based protocols. A new feature is the support for an optional SD card. The controller
already has 8 digital inputs and 4 outputs, a two-channel pulse/direction/PWM interface, an integrated RS-232 interface and RS-485/RS-422 interface, a
two-channel fast counter with a cut-off frequency of up to 200 kHz, and two incremental encoder inputs for asymmetrical incremental encoders.
Product Features
■
■
■
■
■
■
■
■
■
■
■
Numerous protocols supported such as: HTTP, FTP, SNTP, SNMP, SMTP, SQL, MySQL, etc.
MODBUS TCP Client
PROFINET-Device
Large program memory and mass storage (1024 kB/1024 kB)
Modbus TCP server
HTML 5
Free engineering with PC Worx Express (IEC 61131-3)
Integrated pulse/direction/PWM interface
Integrated RS-485/RS-422 interface
Integrated fast counters and incremental encoder inputs
Web server, FTP server, and Flash file system
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
620.0 g
Custom tariff number
85371091
Country of origin
Germany
04/18/2016 Page 1 / 5
https://www.phoenixcontact.com/us/products/2700075
Controller - ILC 191 ME/INC - 2700075
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
164 mm
Height
136.8 mm
Depth
71.5 mm
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 55 °C
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above mean sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above mean sea level)
Shock
25g, Criterion 1, according to IEC 60068-2-27
Vibration (operation)
5g
Control system
Programming tool
PC WORX / PC WORX EXPRESS
Diagnostics tool
DIAG+
Configuration tool
Config+ Version 1.01 or later
Mechanical design
Weight
285 g
Diagnostics display
No
Controller redundancy
No
Data interfaces
Interface
INTERBUS local bus (master)
Connection method
Inline data jumper
Transmission speed
500 kBaud / 2 MBaud (can be switched)
Interface
Parameterization/operation/diagnostics
Connection method
RS-232-C, 6-pos. MINI-DIN socket (PS/2), Ethernet 10/100 (RJ45)
Transmission speed
max. 115,2 kBit/s
Interface
RS-422/485
Connection method
4-pos. for full duplex
2-pos. for half duplex
Interface
Ethernet 10Base-T/100Base-TX
04/18/2016 Page 2 / 5
https://www.phoenixcontact.com/us/products/2700075
Controller - ILC 191 ME/INC - 2700075
Technical data
Data interfaces
Connection method
RJ45 socket
Transmission speed
10/100 MBit/s
PROFINET
Device function
PROFINET device
Power supply
Typical current consumption
350 mA
Supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC
Residual ripple
±5%
Power dissipation
max. 8.4 W
Fieldbus function
Amount of process data
max. 4096 Bit (INTERBUS)
max. 32768 Bit (internal Modbus Client)
Number of supported devices
max. 128
Number of local bus devices that can be connected
max. 63 (observe current consumption)
Number of devices with parameter channel
max. 24
Number of supported branch terminals with remote bus branch
max. 3
Direct I/Os
Input name
Digital inputs
Number of inputs
8
Connection method
Inline potential distributor
Description of the input
EN 61131-2 type 1 NPN/PNP
Output name
Digital outputs
Number of outputs
4
Connection method
2, 3, 4-wire
Maximum output current per channel
500 mA
Without analog input
yes
Without analog output
yes
Without pulse direction output
No
Number of pulse direction outputs
2 (can be used as an alternative to pulse width modulation)
Output voltage
5V
Limit frequency
150 kHz
Without counter input
No
Number of inputs
2
Input voltage range "1" signal
5 V DC ... 24 V DC
04/18/2016 Page 3 / 5
https://www.phoenixcontact.com/us/products/2700075
Controller - ILC 191 ME/INC - 2700075
Technical data
Direct I/Os
Input frequency
200 kHz
Number of inputs
2 (3-coil, asymmetrical)
Input voltage range "1" signal
5 V DC ... 24 V DC
General data
Processor
Altera Nios II 64 MHz
Diagnostics display
No
Standards and Regulations
Shock
25g, Criterion 1, according to IEC 60068-2-27
Vibration (storage/transport)
5g
Vibration (operation)
5g
Classifications
eCl@ss
eCl@ss 4.0
27240409
eCl@ss 4.1
27240409
eCl@ss 5.0
27242207
eCl@ss 5.1
27242207
eCl@ss 6.0
27242207
eCl@ss 7.0
27242207
eCl@ss 8.0
27242207
eCl@ss 9.0
27242207
ETIM
ETIM 4.0
EC000236
ETIM 5.0
EC000236
UNSPSC
UNSPSC 6.01
43172015
UNSPSC 7.0901
43201404
UNSPSC 11
43172018
UNSPSC 12.01
43201404
UNSPSC 13.2
43201404
Approvals
Approvals
04/18/2016 Page 4 / 5
https://www.phoenixcontact.com/us/products/2700075
Controller - ILC 191 ME/INC - 2700075
Approvals
Approvals
UL Listed / cUL Listed / EAC / cULus Listed
Ex Approvals
Approvals submitted
Approval details
UL Listed
cUL Listed
EAC
cULus Listed