AXL E IOL AI1 U M12 S
Axioline E IO-Link/analog converter for connecting
an analog sensor, 0 V ... 10 V, straight version
Data sheet
8593_en_04
1
© PHOENIX CONTACT 2015-04-28
Description
The IO-Link/analog converter is an IO-Link slave that converts analog signals into the IO-Link protocol.
It therefore offers the option of acquiring the signals of analog sensors via an IO-Link master.
Features
–
–
–
–
–
–
–
–
–
Straight version
1 IO-Link interface
1 analog input
Connection of the sensor in 3-wire technology
Voltage range: 0 V ... 10 V
IO-Link and sensor connections via M12 connectors
FE connection for local connection to functional earth
ground
Supply of the module electronics and the sensor via the
IO-Link interface of the IO-Link master
Diagnostic indicator
Make sure you always use the latest documentation.
It can be downloaded from the product at phoenixcontact.net/products.
AXL E IOL AI1 U M12 S
2
Table of contents
1
Description .............................................................................................................................. 1
2
Table of contents ..................................................................................................................... 2
3
Ordering data .......................................................................................................................... 3
4
Technical data ......................................................................................................................... 3
5
Additional tables ...................................................................................................................... 5
6
Internal circuit diagram ............................................................................................................ 5
7
Pin assignment ........................................................................................................................ 6
7.1
Connections on the device ..................................................................................................... 6
7.2
Pin assignment of the IO-Link interface ..................................................................................... 6
7.3
Pin assignment of the analog input ........................................................................................... 6
8
Connection notes .................................................................................................................... 6
9
Connection example................................................................................................................ 6
10
Assembly................................................................................................................................. 7
11
Local status indicator............................................................................................................... 7
12
Process data............................................................................................................................ 8
12.1 IN process data ................................................................................................................... 8
12.2 OUT process data................................................................................................................ 8
12.3 Parameterization via OUT process data .................................................................................... 9
12.4 Example for changing from S7-compatible (default) to IB IL and for forming 16-sample mean value ......... 9
13
Significant values in various formats...................................................................................... 10
13.1 IB IL format ...................................................................................................................... 10
13.2 S7-compatible format ......................................................................................................... 10
14
IO-Link objects ...................................................................................................................... 11
14.1 Overview of the objects ....................................................................................................... 11
14.2 Parameterization (80hex: ParaWord) ....................................................................................... 12
8593_en_04
PHOENIX CONTACT
2
AXL E IOL AI1 U M12 S
3
Ordering data
Description
Type
Order No.
Pcs. / Pkt.
Axioline E-IO-Link/analog converter for connecting an analog sensor,
0 V ... 10 V, M12 fast connection technology, straight version
AXL E IOL AI1 U M12 S
2700336
1
4
Technical data
Dimensions (nominal sizes in mm)
79,5
29
16,5
16,6
28
50
Width
16.6 mm
Height
29 mm
Depth
79.5 mm
General data
Weight
34 g
Ambient temperature (operation)
-25 °C ... 60 °C
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
5 % ... 95 %
Permissible humidity (storage/transport)
5 % ... 95 %
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection
IP65/67
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Pollution degree
2
IO-Link
Specification
V1.1.1
Protection against polarity reversal
Yes
Transmission speed
230,4 kBit/s (COM3)
Frame type
1
Cycle Time
min. 2 ms
Process data update
2 ms
Amount of process data
16 Bit (Input data), 16 Bit (Output data)
IO-Link ports
Number of ports
1
Connection method
M12 connector, A-coded
8593_en_04
PHOENIX CONTACT
3
AXL E IOL AI1 U M12 S
IO-Link port supply
Typical current consumption
16.5 mA ±15% (at 24 V DC)
Current consumption
max. 120 mA
Protection against polarity reversal
Yes
Short-circuit protection
Yes
Overload protection
Yes
I/O supply voltage
24 V DC
This supply voltage is provided via the IO-Link interface of the IO-Link
Sensor supply voltage
24 V DC (max. 100 mA)
This supply voltage is provided via the I/O supply voltage.
master.
Analog input
Number of inputs
1 (voltage)
Connection method
M12 connector, A-coded
Connection method
3-conductor
Voltage input signal
0 V ... 10 V
Input resistance of voltage input
min. 100 kΩ
Resolution A/D
12 bit
Data formats
IB IL, S7-compatible
Filtering
None or mean-value generation over 4, 16, or 32 measured values
Precision
< 0.25% (From the measuring range final value in the nominal range)
Permissible cable length
max. 30 m (shielded cable)
Error messages to the higher level control or computer system
Overrange or underrange
Message in the diagnostic code (in the IB IL format)
Measured value invalid/no valid measured value present
Message in the diagnostic code (in the IB IL format)
Module faulty
Message in the diagnostic code (in the IB IL format)
Mechanical tests
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6
Operation: 2g
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6
Storage/transport: 5g
Shock in acc. with EN 60068-2-27/IEC 60068-2-27
Operation: 30g, 11 ms, three shocks in each space direction
Shock in acc. with EN 60068-2-27/IEC 60068-2-27
Storage/transport: 50g, 11 ms, three shocks in each space direction
Continuous shock according to EN 60068-2-27/IEC 60068-2-27
10g, 16 ms, 1000 shocks, in all space directions
Approvals
For the latest approvals, please visit phoenixcontact.net/products.
8593_en_04
PHOENIX CONTACT
4
AXL E IOL AI1 U M12 S
Internal circuit diagram
The data is valid for nominal operation
(supply voltage = 24 V) in the default configuration
(measurement range 0 V ... 10 V).
IO-Link
Tolerance and temperature response at TA = -25°C to
+60°C
L+
C/Q
IO-Link
IC
µC
1
4
3
FE
L-
Drift
Typical
Maximum
±45 ppm/K
±75 ppm/K
Analog
6
Protection
Additional tables
Protection
5
FE
The tolerance values refer to the measuring range final
value.
Figure 1
Internal wiring of connections
Key:
Tolerances influenced by electromagnetic interference
Type of electromagnetic interference
Standard
Tolerance
Criterion
Electromagnetic fields
EN 61000-4-3/
IEC 61000-4-3
< ±2.0%
A
Fast transients (burst)
EN 61000-4-4/
IEC 61000-4-4
< ±1.0%
A
Conducted interference
EN 61000-4-6/
IEC 61000-4-6
< ±0.5%
A
8593_en_04
Protective circuit
Protection
IO-Link
IC
µC
IO-Link circuit
Microprocessor
Analog/digital converter
PHOENIX CONTACT
5
AXL E IOL AI1 U M12 S
7
Pin assignment
7.1
Connections on the device
7.3
Pin assignment of the analog input
2
1
5
3
4
Figure 4
3
2
Figure 2
Connections on the converter
No. Connection
1
IO-Link interface
(indicated by IO-Link symbol)
2
Fixing options;
options for connection to functional earth ground
3
Analog input
Pin
1
2
3
4
5
Assignment
+24 V, 100 mA sensor supply
Not used
GND
Voltage input 0 V ... 10 V
Not used
8
Connection notes
Pin assignment of the IO-Link interface
1
9
Figure 3
Pin assignment of the I/O link interface
(M12 A-coded, pin)
Pin
1
Signal
L+
2
3
4
LC/Q
8593_en_04
Meaning
+24 V supply voltage;
from IO-Link master
Not used
GND, reference potential for L+
IO-Link data transmission channel
1
5
4
2
2
1
3
3
4
+24 V
0...10 V
4
3
Connection example
Figure 5
C/Q
L+
2
Always connect the analog sensors using shielded, twisted
pair cables.
L-
7.2
Pin assignment of the analog input
(M12 A-coded, socket)
1
Connection example
PHOENIX CONTACT
6
AXL E IOL AI1 U M12 S
10
Assembly
11
Local status indicator
COM
Figure 6
•
•
•
Connection of a sensor to an IO-Link master
via the converter
Connect the IO-Link interface of the converter to an IOLink port of the higher-level IO-Link master using a standardized 3-pos. cable.
Connect the analog sensor directly to the analog converter input or using a shielded 4-pos. cable.
Fasten each connection using the M12 connectors.
In environments with high levels of interference, in particular, Phoenix Contact recommends connecting the converter to an
appropriate functional earth ground point using an M4 screw.
Figure 7
Local status indicator
Designation
COM
Color Mean- State
ing
Green Status of ON
IO-Link Flashing
device
OFF
8593_en_04
Description
Supply voltage OK
Supply voltage
OK, SDCI communication active
No supply voltage,
no communication
PHOENIX CONTACT
7
AXL E IOL AI1 U M12 S
12
Process data
The device occupies one word of IN process data and one word of OUT process data.
12.1
IN process data
The measured values are depicted in IB IL or S7-compatible format.
For both formats the measured value is represented in bits 14 to 3. Bit 15 is available as a sign bit. Bits 2 to 0 are not relevant
for the measured value.
15
V
V
x
14
13
12
11
10
9
Analog value
8
7
6
5
4
3
2
x
1
x
0
x
Sign bit (= 0, not relevant)
Not relevant for the measured value (are set to 0)
A diagnostic code is mapped to the input data in the event
of an error.
IB IL format
The values > 8000hex and 0008) accords 2.67 V
Input data
hex
8001
7EF8
7538
7530
3A98
0008
0000
8002
13.2
Range
dec
32769
32511
30008
30000
15000
8
0
32770
Overrange
Overdrive range (End)
Overrange (Start)
Nominal range (End)
Nominal range
Nominal range
Nominal range (Start)
Wire break
0 V ... 10 V
V
> 10.837
10.837
10.000267
10.0
5.0
0.00267
0
S7-compatible format
Resolution: 1 bit (0000 -> 0008) accords 2.89 V
Input data
hex
7FFF
7EF0
6C08
6C00
3600
0008
0000
8000
Range
dec
32767
32503
27656
27648
13824
8
0
32768
Overrange
Overdrive range (End)
Overrange (Start)
Nominal range (End)
Nominal range
Nominal range
Nominal range (Start)
Wire break/short circuit
0 V ... 10 V
V
> 11.756
11.756
10.00289
10.0
5.0
0.00289
0
The value 8000hex is specified in S7-compatible format for all errors for which diagnostic codes 8001hex to 8040hex are output
in IB IL format.
8593_en_04
PHOENIX CONTACT
10
AXL E IOL AI1 U M12 S
14
IO-Link objects
14.1
Overview of the objects
Index (hex)
DPP
ISDU
Identification
07
08
09
0A
0B
10
11
12
13
14
15
16
17
Diagnostics
20
28
Parameter
80
Abbreviation
R
W
8593_en_04
Object name
Length in Access Meaning
bytes
Contents
Vendor ID
2
R
Manufacturer identification
Device ID
3
R
Device ID
VendorName
VendorText
ProductName
Product ID
ProductText
Max. 64
Max. 64
Max. 64
Max. 64
Max. 64
R
R
R
R
R
Manufacturer name
Notes
Product designation
Order No.
Product text
Serial number
Max. 16
R
Serial number
00hex
B0hex
01hex
00hex
01hex
Phoenix Contact
www.phoenixcontact.com
AXL E IOL AI1 U M12 S
2700336
IO-Link/analog converter voltage
input straight
Stored in the production process.
HardwareVersion
FirmwareVersion
Max. 64
Max. 64
R
R
Hardware version
Firmware version
E.g., 01
E.g., 001
Error count
2
InputProcessData 2
R
R
Errors since power up
Input process data
Number of errors
Last current data
ParaWord
R/W
Parameterization
0000hex
2
Meaning
Read
Write
PHOENIX CONTACT
11
AXL E IOL AI1 U M12 S
14.2
Parameterization (80hex: ParaWord)
Parameterize the device using this object.
In the case of valid parameters, the parameterization is permanently stored on the device.
After a reset, the device operates with the last permanently stored data. Upon delivery, the device operates with the default
data (default settings).
Saving data to the device leads to a communication failure of around 30 ms.
15
14
13
12
Reserved
11
10
9
8
Filter
7
6
Reserved
5
4
Format
3
2
1
Reserved
0
In the following tables the values in bold are default settings.
Format
Code (bin)
00
10
Other
Meaning
S7-compatible
IB IL
Reserved
Filter
Code (bin)
00
01
10
11
Meaning
No filter
4-sample mean-value
16-sample mean-value
32-sample mean-value
8593_en_04
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com
12
很抱歉,暂时无法提供与“2700336”相匹配的价格&库存,您可以联系我们找货
免费人工找货