AXL E IOL RTD1 M12 S
Axioline E IO-Link/analog converter for connecting
an RTD, straight version
Data sheet
8597_en_07
1
© PHOENIX CONTACT 2015-04-28
Description
The IO-Link/analog converter is an IO-Link slave that converts analog signals into the IO-Link protocol.
It therefore offers the option of acquiring the signals of analog sensors via an IO-Link master.
Features
–
–
–
–
–
–
–
–
Straight version
1 IO-Link interface
1 analog input for connecting resistance temperature
detectors (RTDs)
Connection of the sensor in 3-wire technology
IO-Link and sensor connections via M12 connectors
FE connection for local connection to functional earth
ground
Supply of the module electronics and the sensor via the
IO-Link interface of the IO-Link master
Diagnostic indicator
Make sure you always use the latest documentation.
It can be downloaded from the product at phoenixcontact.net/products.
AXL E IOL RTD1 M12 S
2
Table of contents
1
Description .............................................................................................................................. 1
2
Table of contents ..................................................................................................................... 2
3
Ordering data .......................................................................................................................... 3
4
Technical data ......................................................................................................................... 3
5
Additional tables ...................................................................................................................... 5
6
Internal circuit diagram ............................................................................................................ 5
7
Pin assignment ........................................................................................................................ 6
7.1
Connections on the device ..................................................................................................... 6
7.2
Pin assignment of the IO-Link interface ..................................................................................... 6
7.3
Pin assignment of the analog input ........................................................................................... 6
8
Connection notes .................................................................................................................... 6
9
Connection example................................................................................................................ 6
10
Assembly................................................................................................................................. 7
11
Local status indicator............................................................................................................... 7
12
Process data............................................................................................................................ 8
12.1 IN process data ................................................................................................................... 8
12.2 OUT process data................................................................................................................ 8
12.3 Parameterization via OUT process data .................................................................................... 9
12.4 Example ............................................................................................................................ 9
13
Significant values in various formats...................................................................................... 10
13.1 IB IL format ...................................................................................................................... 10
13.2 IB IL format ...................................................................................................................... 10
13.3 S7-compatible format ......................................................................................................... 10
14
IO-Link objects ...................................................................................................................... 11
14.1 Overview of the objects ....................................................................................................... 11
14.2 Parameterization (80hex: ParaWord) ....................................................................................... 12
8597_en_07
PHOENIX CONTACT
2
AXL E IOL RTD1 M12 S
3
Ordering data
Description
Type
Order No.
Pcs. / Pkt.
Axioline E-IO-Link/analog converter for connecting a temperature measurement resistor, M12 fast connection technology, straight version
AXL E IOL RTD1 M12 S
2700352
1
4
Technical data
Dimensions (nominal sizes in mm)
79,5
29
16,5
16,6
28
50
Width
16.6 mm
Height
29 mm
Depth
79.5 mm
General data
Weight
34 g
Ambient temperature (operation)
-25 °C ... 60 °C
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
5 % ... 95 %
Permissible humidity (storage/transport)
5 % ... 95 %
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection
IP65/67
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Pollution degree
2
IO-Link
Specification
V1.1.1
Protection against polarity reversal
Yes
Transmission speed
230,4 kBit/s (COM3)
Frame type
1
Cycle Time
min. 2 ms
Process data update
2 ms
Amount of process data
16 Bit (Input data)
IO-Link ports
Number of ports
1
Connection method
M12 connector, A-coded
8597_en_07
PHOENIX CONTACT
3
AXL E IOL RTD1 M12 S
IO-Link port supply
Typical current consumption
16.5 mA ±15% (at 24 V DC)
Current consumption
max. 25 mA
Protection against polarity reversal
Yes
Short-circuit protection
Yes
Overload protection
Yes
I/O supply voltage
24 V DC
This supply voltage is provided via the IO-Link interface of the IO-Link master.
Analog RTD inputs
Number of inputs
1 (for resistance temperature detectors)
Connection method
M12 connector, A-coded
Connection method
3-wire (optionally 4-wire)
Sensor types (RTD) that can be used
Pt 100, Pt 1000
Linear resistance measuring range
IB IL format: 0 Ω ... 500 Ω, 0 Ω ... 5 kΩ
S7-compatible format: 0 Ω ... 600 Ω, 0 Ω ... 6 kΩ
Resolution A/D
12 bit
Data formats
IB IL, S7-compatible
Relative accuracy
< 0.3 % (From the measuring range final value in the nominal range)
Permissible cable length
max. 30 m (Shielded cable)
Protection against polarity reversal
yes
Short-circuit protection
yes
Overload protection
yes
Error messages to the higher level control or computer system
Overrange or underrange
Message in the diagnostic code (in the IB IL format)
Measured value invalid/no valid measured value present
Message in the diagnostic code (in the IB IL format)
Configuration invalid
Message in the diagnostic code (in the IB IL format)
Module faulty
Message in the diagnostic code (in the IB IL format)
Mechanical tests
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6
Operation: 2g
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6
Storage/transport: 5g
Shock in acc. with EN 60068-2-27/IEC 60068-2-27
Operation: 30g, 11 ms, three shocks in each space direction
Shock in acc. with EN 60068-2-27/IEC 60068-2-27
Storage/transport: 50g, 11 ms, three shocks in each space direction
Continuous shock according to EN 60068-2-27/IEC 60068-2-27
10g, 16 ms, 1000 shocks, in all space directions
Approvals
For the latest approvals, please visit phoenixcontact.net/products.
8597_en_07
PHOENIX CONTACT
4
AXL E IOL RTD1 M12 S
Internal circuit diagram
The data is valid for nominal operation (supply voltage = 24 V) in the default configuration.
Sensor
type
Measuring range
Drift
Lower
limit
Upper
limit
Typical
C/Q
IO-Link
IC
µC
1
4
3
FE
L-
Maximum
Pt 100 DIN
-200 °C
+850 °C
±5 ppm/K
±95 ppm/K
Pt 1000
SAMA
-200 °C
+850 °C
±20 ppm/K
±95 ppm/K
Linear resistor RLin 500
Ω (linear
range 1)
0Ω
500 Ω
±5 ppm/K
±95 ppm/K
Linear resistor RLin 5000
Ω (linear
range 2)
0Ω
FE
Figure 1
Internal wiring of connections
Key:
Protective circuit
5000 Ω
±34 ppm/K
±95 ppm/K
Protection
IO-Link
IC
The tolerance values refer to the measuring range final
value.
Tolerances influenced by electromagnetic interference
Type of electromagnetic interference
Standard
Tolerance
Criterion
Electromagnetic fields
EN 61000-4-3/
IEC 61000-4-3
< ±1.5%
A
Fast transients (burst)
EN 61000-4-4/
IEC 61000-4-4
< ±0.5%
A
Conducted interference
EN 61000-4-6/
IEC 61000-4-6
< ±1.0%
A
8597_en_07
IO-Link
Tolerance and temperature response at TA = -25°C to
+60°C
L+
Analog
6
Protection
Additional tables
Protection
5
µC
IO-Link circuit
Microprocessor
Analog/digital converter
PHOENIX CONTACT
5
AXL E IOL RTD1 M12 S
7
Pin assignment
7.1
Connections on the device
7.3
Pin assignment of the analog input
2
1
5
3
4
Figure 4
3
2
Figure 2
Connections on the converter
No. Connection
1
IO-Link interface
(indicated by IO-Link symbol)
2
Fixing options;
options for connection to functional earth ground
3
Analog input
Pin
1
2
3
4
5
Assignment
U+
RTD sensor +
I+
Constant current supply +
URTD sensor IConstant current supply Not used
8
Connection notes
Pin assignment of the IO-Link interface
1
9
Figure 3
Pin assignment of the I/O link interface
(M12 A-coded, pin)
Pin
1
Signal
L+
2
3
4
LC/Q
8597_en_07
Meaning
+24 V supply voltage;
from IO-Link master
Not used
GND, reference potential for L+
IO-Link data transmission channel
1
5
4
2
2
1
3
3
4
U+
IUI+
4
3
Connection example
Figure 5
C/Q
L+
2
Always connect the analog sensors using shielded, twisted
pair cables.
L-
7.2
Pin assignment of the analog input
(M12 A-coded, socket)
1
Connection example
PHOENIX CONTACT
6
AXL E IOL RTD1 M12 S
10
Assembly
11
Local status indicator
COM
Figure 6
•
•
•
Connection of a sensor to an IO-Link master
via the converter
Connect the IO-Link interface of the converter to an IOLink port of the higher-level IO-Link master using a standardized 3-pos. cable.
Connect the analog sensor directly to the analog converter input or using a shielded 4-pos. cable.
Fasten each connection using the M12 connectors.
In environments with high levels of interference, in particular, Phoenix Contact recommends connecting the converter to an
appropriate functional earth ground point
using an M4 screw.
8597_en_07
Figure 7
Local status indicator
Designation
COM
Color Mean- State
ing
Green Status
ON
of IOFlashing
Link device
OFF
Description
Supply voltage OK
Supply voltage OK,
SDCI communication active
No supply voltage,
no communication
PHOENIX CONTACT
7
AXL E IOL RTD1 M12 S
12
Process data
The device occupies one word of IN process data and
one word of OUT process data.
12.1
IN process data
The measured values are depicted in IB IL or
S7-compatible format.
15
V
V
14
13
12
11
10
9
8
Analog value
7
6
5
4
3
2
1
0
Sign bit (= 0, not relevant)
By some formats bit 2 ... bit 0 are not relevant
for the measured value. They are set to 0.
A diagnostic code is mapped to the input data in the event
of an error.
IB IL format
Values > 8000hex and 525
525
100
5
0.5
0.1
0
-
R 0 Ω ... 5 kΩ
1Ω
Ω
no (0 Ω)
yes
> 5250
5250
1000
50
5
1
0
-
0.1 °C *
°C
yes
yes
> 850
850
525
100
5
0.5
0
-100
-200
< -200
Temperature sensors
0.1 °F *
°F
yes
yes
>1562
1562
850
525
100
5
0.5
0
-100
-200
-328
< -328
R 0 Ω ... 600 Ω
0.17 Ω
Ω
no (0 Ω)
yes
> 705.4
705.4
339
184.5
21.7
1.1
0.17
0
-
R 0 Ω ... 6 kΩ
1.7 Ω
Ω
no (0 Ω)
yes
> 7054
7054
3390
1845
217
11
1.7
0
-
0.1 °C *
°C
yes
yes
> 850
850
100
50
0.5
0
-100
-200
< -200
Temperature sensors
0.1 °F *
°F
yes
yes
> 1562
1562
850
100
50
0.5
0
-100
-200
< -328
< -328
S7-compatible format
Input data
Resolution
hex
dec
8000 Short-circuit
8000 Wire break
7FFF Overrange
7EF8 32504
3D04 15620
2134 8500
03E8 1000
0032 50
0008 8
0005 5
0000 0
FC18 -1000
F830 -2000
F330 -3280
8000 Underrange
* The format representation is based on 0.1 °C/F. The actual resolution is 0.5 °C/F.
The measurement is thus always in 0.5 °C/F increments (steps).
8597_en_07
PHOENIX CONTACT
10
AXL E IOL RTD1 M12 S
14
IO-Link objects
14.1
Overview of the objects
Index (hex)
DPP
ISDU
Identification
07
08
09
0A
0B
10
11
12
13
14
15
Object name
Length in Access Meaning
bytes
Contents
Vendor ID
2
R
Manufacturer identification
Device ID
3
R
Device ID
VendorName
VendorText
ProductName
Product ID
ProductText
Max. 64
Max. 64
Max. 64
Max. 64
Max. 64
R
R
R
R
R
Manufacturer name
Notes
Product designation
Order No.
Product text
Serial number
Max. 16
R
Serial number
HardwareVersion
FirmwareVersion
Max. 64
Max. 64
R
R
Hardware version
Firmware version
00hex
B0hex
01hex
00hex
51hex
Phoenix Contact
www.phoenixcontact.com
AXL E IOL RTD1 M12 S
2700352
IO-Link/Analog-Converter
Temperature RTD Input
Straight
Stored in the production process.
E.g., 01
E.g., 001
16
17
Diagnostics
20
28
Parameter
80
Error count
InputProcessData
2
2
R
R
Errors since power up
Input process data
Number of errors
Last current data
ParaWord
2
R/W
Parameterization
0000hex
Abbreviation
R
W
Meaning
Read
Write
8597_en_07
PHOENIX CONTACT
11
AXL E IOL RTD1 M12 S
14.2
Parameterization (80hex: ParaWord)
Parameterize the device using this object.
In the case of valid parameters, the parameterization is permanently stored on the device.
After a reset, the device operates with the last permanently stored data. Upon delivery, the device operates with the default
data (default settings).
Saving data to the device leads to a communication failure of around 30 ms.
15
14
13
12
Reserved
11
10
9
8
7
6
Resolution for sensor
type
5
4
Format
3
2
1
Sensor type
0
In the following tables the values in bold are default settings.
Sensor type
Code (bin)
0000
0001
1110
1111
Meaning
Pt 100 DIN
Pt 1000 SAMA
IB IL format:
Linear R 0 Ω ... 500 Ω
S7-compatible format:
Linear R 0 Ω ... 600 Ω
IB IL format:
Linear R 0 Ω ... 5 kΩ
Other
S7-compatible format
Linear R 0 Ω ... 6 kΩ
Reserved
Format
Code (bin)
00
10
Other
Meaning
S7-compatible
IB IL
Reserved
Resolution for sensor type
Code (bin)
Temperature sensors
00
0.1 °C
10
(0.5 °C increments)
0.1 °F
Other
(0.5 °F increments)
Reserved
8597_en_07
Linear R 0 Ω ... 500 Ω / 600 Ω
IB IL format: 0,1 Ω
Linear R 0 Ω ... 5 kΩ / 6 kΩ
Format IB IL: 1,0 Ω
S7-compatible format: 0,17 Ω
Reserved
Format S7-kompatibel: 1,7 Ω
Reserved
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com
12