https://www.phoenixcontact.com/us/produkte/2700606
Safety module - IB IL 24 LPSDO 8 V2-PAC - 2700606
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the
user's documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
Safety-related digital output module, IP20 protection, for the SafetyBridge system. The module has four
safe digital outputs with two-channel occupancy or 8 safe digital outputs with single-channel occupancy
Product description
The safety module is an output module from the Inline product range and is used in a SafetyBridge system. The safety module can be
used as a part of an Inline station at any point within an INTERBUS, PROFINET or PROFIBUS system. The transmission speed of the
safety module can be set to 500 kbaud or 2 Mbaud using a switch. Only one transmission speed must be used uniformly within a station.
The module has four safe digital outputs with two-channel occupancy or eight safe digital outputs with single-channel occupancy. In
the SafetyBridge system, you can achieve the following safety integrity by using this safety module depending on the installation and
parameterization:
– up to category 4 according to EN 954-1 standard,
– up to SIL 3 according to EN 61508 standard,
– up to SIL CL 3 according to EN 62061 standard,
– up to PL e according to EN ISO 13849-1 standard.
Product Features
Generation and monitoring of the SafetyBridge protocol
Processing of the parameterized safety logic
Key commercial data
GTIN
Technical data
Note:
Utilization restriction
EMC: class A product, see manufacturer's declaration in the
download area
Interface
Fieldbus system
Lokalbus
Name
INTERBUS
Connection method
Inline data jumper
Transmission speed
500 kbaud/2 Mbaud, can be selected
Transmission speed
500 kBit/s / 2MBit/s
Digital outputs
18.03.2013 Page 1 / 6
https://www.phoenixcontact.com/us/produkte/2700606
Safety module - IB IL 24 LPSDO 8 V2-PAC - 2700606
Technical data
Digital outputs
Output name
Digital outputs
Connection method
Spring-cage connection
Connection method
2, 3, 4-wire
Number of outputs
4 (with two-channel assignment)
Number of outputs
8
Protective circuit
Overload protection, short-circuit protection of outputs
Output voltage
24 V DC (US - 1 V)
Nominal output voltage
24 V DC
Output current
max. 6 A (Total current of all outputs, -25 °C ... 50 °C)
Output current
max. 4 A (Total current of all outputs, >50 °C ... 55 °C)
Maximum output current per channel
2A
Maximum output current per group
3A
Nominal load, inductive
(see safety data)
Nominal load, lamp
(see safety data)
Nominal load, ohmic
(see safety data)
Power supply for module electronics
Supply voltage
24 V DC (via voltage jumper)
Supply voltage range
19.2 V DC ... 30 V DC
Communications power UL
7.5 V (via voltage jumper)
Current consumption
max. 230 mA (from the local bus)
SafetyBridge properties
Connection to I/O modules
max. 5 (safe digital I/O modules)
Logic memory
24 kByte
General data
Width
48.8 mm
Height
119.8 mm
Depth
71.5 mm
Note on dimensions
Housing dimensions
Weight
200 g
Note on weight specifications
with male connectors
Mounting type
DIN rail
Ambient temperature (operation)
-25 °C ... 55 °C
Ambient temperature (storage/transport)
-25 °C ... 70 °C
Permissible humidity (operation)
10 % ... 85 % (Take suitable measures against increased air humidity
within the permitted temperature range.)
Permissible humidity (storage/transport)
10 % ... 85 % (Take suitable measures against increased air humidity
within the permitted temperature range.)
18.03.2013 Page 2 / 6
https://www.phoenixcontact.com/us/produkte/2700606
Safety module - IB IL 24 LPSDO 8 V2-PAC - 2700606
Technical data
General data
Air pressure (operation)
80 kPa ... 108 kPa (up to 2000 m above sea level)
Air pressure (storage/transport)
66 kPa ... 108 kPa (up to 3500 m above mean sea level)
Degree of protection
IP20
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Test section
5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V AC
50 Hz 1 min
Test section
5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V AC
50 Hz 1 min
Test section
7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min
Test section
24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min
Category according to EN 13849-1
4
Diagnostics messages
Short-circuit / overload of the digital outputs Error message in
diagnostics code (bus) and display by means of the LED on the
motor
Inline potential routing
Communications power UL
7.5 V DC (see safety data)
Current consumption from UL
max. 230 mA (see safety data)
Main circuit supply UM
24 V DC (see safety data)
Supply voltage range UM
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumption from UM
typ. 30 mA (all outputs set including actuator current)
Current consumption from UM
max. 6.03 A
Segment supply voltage US
24 V (see safety data)
Classifications
ETIM
ETIM 2.0
EC001433
ETIM 3.0
EC001599
ETIM 4.0
EC001599
ETIM 5.0
EC001601
UNSPSC
UNSPSC 11
39121311
UNSPSC 12.01
39121311
UNSPSC 13.2
39121311
UNSPSC 6.01
43172015
UNSPSC 7.0901
43201404
18.03.2013 Page 3 / 6
https://www.phoenixcontact.com/us/produkte/2700606
Safety module - IB IL 24 LPSDO 8 V2-PAC - 2700606
Classifications
eCl@ss
eCl@ss 4.0
27240404
eCl@ss 4.1
27240404
eCl@ss 5.0
27242204
eCl@ss 5.1
27242604
eCl@ss 6.0
27242604
eCl@ss 7.0
27242604
Approvals
Approvals
Approvals
UL Listed / cUL Listed / Functional Safety / cULus Listed
Ex Approvals
Approvals submitted
Approval details
UL Listed
cUL Listed
Functional Safety
cULus Listed
Accessories
Accessories
18.03.2013 Page 4 / 6
https://www.phoenixcontact.com/us/produkte/2700606
Safety module - IB IL 24 LPSDO 8 V2-PAC - 2700606
Accessories
Marking
Labeling field - IB IL FIELD 2 - 2727501
Labeling field, width: 12.2 mm
Labeling field - IB IL FIELD 8 - 2727515
Labeling field, width: 48.8 mm
Insert strip - ESL 62X10 - 0809492
Insert strip, Sheet, white, Unlabeled, Can be labeled with: Office-Drucksysteme, Plotter: Laser printer, Mounting
type: Insert, Lettering field: 62 x 10 mm
Insert strip - ESL 62X46 - 0809502
Insert strip, Sheet, white, Unlabeled, Can be labeled with: Office-Drucksysteme, Plotter: Laser printer, Mounting
type: Insert, Lettering field: 62 x 46 mm
Plug/Adapter
Connector set - IB IL 24 SDO 8-PLSET/CP - 2916927
Connector set (yellow), color coded, for safe SDO boards.
18.03.2013 Page 5 / 6
https://www.phoenixcontact.com/us/produkte/2700606
Safety module - IB IL 24 LPSDO 8 V2-PAC - 2700606
Accessories
User manual - UM DE IB IL 24 SDO 8-PAC - 2888835
User Manual, German, for INTERBUS Safety output modules
User manual - UM EN IB IL 24 SDO 8-PAC - 2888864
User Manual, English for PLCopen-certified INTERBUS Safety function blocks
User manual - UM QS EN IB IL 24 PSDX - S7 - 2910648
User manual, English
User manual - UM QS DE IB IL 24 PSDX - S7 - 2910651
User manual, german
© Phoenix Contact 2013 - all rights reserved
http://www.phoenixcontact.com
18.03.2013 Page 6 / 6