Inline power measurement terminal for direct measurement of AC currents up to 5 A, including neutral conductor
current and phase conductor voltages up to 400 V AC (phase/neutral conductor) or 690 V AC (phase/phase)
complete with accessories (connectors and labeling fields)
Product Features
■
■
■
■
3 inputs for outer conductor voltages up to 690 V AC, direction connection supported
4 inputs, 1 A AC ... 5 A AC for phase currents and neutral conductor currents
Triggers for meas. intervals can be freely defined
Diagnostic and status indicators
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
240.0 g
Custom tariff number
85389099
Country of origin
Germany
Technical data
Dimensions
Width
48.8 mm
Height
119.8 mm
Depth
71.5 mm
Note on dimensions
Housing dimensions
Ambient conditions
Ambient temperature (operation)
-25 °C ... 60 °C
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation)
80 kPa ... 106 kPa (up to 2000 m above sea level)
03/14/2016 Page 1 / 4
https://www.phoenixcontact.com/us/products/2700965
Inline function terminal - IB IL PM 3P/N/EF-PAC - 2700965
Technical data
Ambient conditions
Air pressure (storage/transport)
80 kPa ... 106 kPa (up to 2000 m above sea level)
Degree of protection
IP20
General
Mounting type
DIN rail
Net weight
200 g
Note on weight specifications
with connectors
Interfaces
Designation
Inline local bus
Connection method
Inline data jumper
Transmission speed
500 kBit/s
Power supply for module electronics
Communications power UL
7.5 V (via voltage jumper)
Current consumption
typ. 130 mA (from the local bus)
Power consumption
typ. 1 W (at UL)
Inline potentials
Communications power UL
7.5 V (via voltage jumper)
Current consumption from UL
typ. 130 mA
Standards and Regulations
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Classifications
eCl@ss
eCl@ss 4.0
27250302
eCl@ss 4.1
27250302
eCl@ss 5.0
27250304
eCl@ss 5.1
27242605
eCl@ss 6.0
27242605
eCl@ss 7.0
27242605
eCl@ss 8.0
27242605
ETIM
ETIM 3.0
EC001599
ETIM 4.0
EC001601
ETIM 5.0
EC001601
03/14/2016 Page 2 / 4
https://www.phoenixcontact.com/us/products/2700965
Inline function terminal - IB IL PM 3P/N/EF-PAC - 2700965
Classifications
UNSPSC
UNSPSC 6.01
43172015
UNSPSC 7.0901
43201404
UNSPSC 11
43172015
UNSPSC 12.01
43201404
UNSPSC 13.2
43201404
Approvals
Approvals
Approvals
EAC
Ex Approvals
Approvals submitted
Approval details
EAC
Drawings
Connection diagram
Dimensional drawing
140,5
119,8
L1
L2
N
71,5
L3
Direct connection
03/14/2016 Page 3 / 4
https://www.phoenixcontact.com/us/products/2700965
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
03/14/2016 Page 4 / 4