24 V DC Nanoline base unit. Equipped with 6 digital input and 4 relay output channels. Additional I/O
channels can be added using a maximum of three I/O expansion modules. Optional communication
modules provide network or serial connectivity. Optional Operator Panel provides user interface.
Programming is via nanoNavigator.
Why buy this product
An operator panel can be integrated in the basic unit or installed remotely on a panel as an option
Intuitive programming language with options for flowcharts and ladder diagrams
Basic unit has integrated digital inputs, relay outputs, and analog inputs, including high-speed counters
Key commercial data
Packing unit
1
Minimum order quantity
270
Catalog page
Page 11 (AX-2011)
GTIN
Custom tariff number
85371099
Country of origin
INDIA
Technical data
Supply
Power supply connection
Screw connection
Supply voltage
24 V DC (Power available to the I/O and Communications
modules)
Supply voltage range
19 V DC ... 30 V DC
Max. current consumption
250 mA
Typical current consumption
96 mA
Software interfaces
Programming tool
nanoNavigator 1 or 2
Digital inputs
Input name
Digital inputs
Description of the input
EN 61131-2 type 1 NPN/PNP
Connection method
Screw connection
26.09.2012 Page 1 / 4
https://www.phoenixcontact.com/us/produkte/2701043
base unit - nLC-050-024D-06I-04QRD-05A - 2701043
Technical data
Digital inputs
Number of inputs
6
Typical response time
on 60 µs
Typical response time
off 70 µs
Input voltage range "0" signal
0 V DC ... 5 V DC
Input voltage range "1" signal
15 V DC ... 30 V DC
Nominal input current at UIN
5 mA DC (On)
Digital outputs
Output name
Relay output
Output description
Relay output
Connection method
Screw connection
Number of outputs
4
Protective circuit
Short-circuit and overload protection
Maximum output current per channel
5A
Maximum output current per module / terminal block
20 A
Maximum output current per module
5A
Nominal load, ohmic
600 W (@ 24 ohms)
General data
Width
80.5 mm
Height
103.5 mm
Depth
60 mm
Mounting type
DIN rail
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 60 °C
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
90 %
Classifications
eclass
eCl@ss 4.0
27240101
eCl@ss 4.1
27240101
eCl@ss 5.0
27242216
eCl@ss 5.1
27242216
eCl@ss 6.0
27242216
eCl@ss 7.0
27242216
etim
ETIM 2.0
EC001417
ETIM 3.0
EC001417
ETIM 4.0
EC001417
26.09.2012 Page 2 / 4
https://www.phoenixcontact.com/us/produkte/2701043
base unit - nLC-050-024D-06I-04QRD-05A - 2701043
Classifications
unspsc
UNSPSC 6.01
43172015
UNSPSC 7.0901
43201404
UNSPSC 11
43172015
UNSPSC 12.01
43201404
UNSPSC 13.2
43201404
Approvals
Approvals
Approvals
UL Recognized / cUL Recognized / UL Listed / cUL Listed / cUL Listed
Ex Approvals
Approvals submitted
Approval details
UL Recognized
cUL Recognized
UL Listed
cUL Listed
cUL Listed
26.09.2012 Page 3 / 4
https://www.phoenixcontact.com/us/produkte/2701043
base unit - nLC-050-024D-06I-04QRD-05A - 2701043
Accessories
Accessories
Covering hood - NLC-MOD-CAP-PXC - 2701292
Replacement cover for slot 2 in base unit.
Covering hood - NLC-MOD-CAP - 2701289
Replacement cover for slot 1 in base unit.
Drawings
Connection diagram
Dimensioned drawing
80,5
60
PWR
nanoLine
RUN
Q0
+
–
Q1
+
–
Q2
+
–
Q3
+
–
2
103,5
+
1
+ –
© Phoenix Contact 2012 - all rights reserved