2701069 数据手册
https://www.phoenixcontact.com/us/produkte/2701069 base unit - nLC-050-100A-08I-04QRA-05A - 2701069 Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid (http://download.phoenixcontact.com) 100-240 V AC Nanoline base unit. Equipped with 8 digital input and 4 relay output channels. Additional I/O channels can be added using a maximum of three I/O expansion modules. Optional communication modules provide network or serial connectivity. Optional Operator Panel provides user interface. Programming is via nanoNavigator. Why buy this product  An operator panel can be integrated in the basic unit or installed remotely on a panel as an option  Intuitive programming language with options for flowcharts and ladder diagrams  Basic unit has integrated digital inputs, relay outputs, and analog inputs, including high-speed counters Key commercial data Packing unit 1 Minimum order quantity 270 Catalog page Page 11 (AX-2011) GTIN Custom tariff number 85371099 Country of origin INDIA Technical data Interfaces Interface Operator Panel Connection method RJ45 / Combicon Interface V.24 (RS-232) Connection method Slot 1 Interface USB Connection method Slot 1 Interface Realtime Clock Connection method Slot 2 Supply Power supply connection Screw connection Supply voltage 100 V AC Supply voltage range 100 V AC ... 240 V AC Typical current consumption 55 mA (@ 230 V AC) Software interfaces 26.09.2012   Page 1 / 4 https://www.phoenixcontact.com/us/produkte/2701069 base unit - nLC-050-100A-08I-04QRA-05A - 2701069 Technical data Software interfaces Programming tool nanoNavigator 1 or 2 Digital inputs Input name Digital inputs Description of the input EN 61131-2 type 1 NPN/PNP Connection method Screw connection Number of inputs 8 Typical response time 20 ms Input voltage range "0" signal 0 V AC ... 25 V AC Input voltage range "1" signal 80 V AC ... 250 V AC Nominal input current at UIN 0.17 mA AC (On) Digital outputs Output name Relay output Output description Relay output Connection method Screw connection Number of outputs 4 Protective circuit Short-circuit and overload protection Maximum output current per channel 5A Maximum output current per module / terminal block 20 A Maximum output current per module 5A Nominal load, ohmic 600 W (@ 24 ohms) General data Width 80.5 mm Height 103.5 mm Depth 60 mm Mounting type DIN rail Degree of protection IP20 Ambient temperature (operation) -25 °C ... 60 °C Ambient temperature (storage/transport) -25 °C ... 85 °C Permissible humidity (operation) 90 % Classifications eclass eCl@ss 4.0 27240101 eCl@ss 4.1 27240101 eCl@ss 5.0 27242216 eCl@ss 5.1 27242216 eCl@ss 6.0 27242216 eCl@ss 7.0 27242216 26.09.2012   Page 2 / 4 https://www.phoenixcontact.com/us/produkte/2701069 base unit - nLC-050-100A-08I-04QRA-05A - 2701069 Classifications etim ETIM 2.0 EC001417 ETIM 3.0 EC001417 ETIM 4.0 EC001417 unspsc UNSPSC 6.01 43172015 UNSPSC 7.0901 43201404 UNSPSC 11 43172015 UNSPSC 12.01 43201404 UNSPSC 13.2 43201404 Approvals Approvals Approvals UL Recognized / cUL Recognized / UL Listed / cUL Listed / cUL Listed Ex Approvals Approvals submitted Approval details UL Recognized  cUL Recognized  UL Listed  cUL Listed  26.09.2012   Page 3 / 4 https://www.phoenixcontact.com/us/produkte/2701069 base unit - nLC-050-100A-08I-04QRA-05A - 2701069 Approvals cUL Listed  Accessories Accessories Covering hood - NLC-MOD-CAP-PXC - 2701292 Replacement cover for slot 2 in base unit.     Covering hood - NLC-MOD-CAP - 2701289 Replacement cover for slot 1 in base unit.     EMC core - NLC-EMC-PWR-01 - 2701070 EMC choke to reduce conducted emissions     Drawings Connection diagram Dimensioned drawing 80,5 60 PWR nanoLine RUN Q0 Q1 Q2 Q3 1 2 103,5 + © Phoenix Contact 2012 - all rights reserved http://www.phoenixcontact.com 26.09.2012   Page 4 / 4
2701069
物料型号:nLC-050-100A-08I-04QRA-05A - 2701069

器件简介:100-240 V AC Nanoline基础单元,配备8个数字输入和4个继电器输出通道。可以通过最多三个I/O扩展模块添加额外的I/O通道。可选通信模块提供网络或串行连接。可选操作面板提供用户界面。通过nanoNavigator进行编程。

引脚分配:数字输入和继电器输出通过螺钉连接。

参数特性: - 电源电压:100 V AC至240 V AC - 典型电流消耗:55mA(@230V AC) - 数字输入响应时间:20毫秒 - 继电器输出电流:每通道5A,模块/端子块20A

功能详解:基础单元集成了数字输入、继电器输出和模拟输入,包括高速计数器。可选的操作面板可以集成在基础单元中或作为选项远程安装在面板上。

应用信息:适用于需要数字输入和继电器输出的应用场景。

封装信息:DIN导轨安装,尺寸为80.5mm宽、103.5mm高、60mm深,保护等级IP20。
2701069 价格&库存

很抱歉,暂时无法提供与“2701069”相匹配的价格&库存,您可以联系我们找货

免费人工找货
2701069
  •  国内价格 香港价格
  • 1+1364.046601+175.02260

库存:5