https://www.phoenixcontact.com/us/products/2701152
Inline terminal - IB IL 24 DI 4-XC-PAC - 2701152
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Inline digital input terminal, version for extreme conditions, complete with accessories (connector plug and
labeling field), 4 inputs, 24 V DC, 3-conductor connection technology
Product description
The terminal is designed for use within an Inline station.
It is used to acquire digital input signals.
Product Features
4 digital inputs
Connection of sensors in 2 and 3-wire technology
Maximum permissible load current per sensor: 250 mA
Maximum permissible load current from the terminal: 1 A
Diagnostic and status indicators
Can be used under extreme ambient conditions
Coated PCBs
Extended temperature range T2 (-40°C ... +55°C)
Key commercial data
Packing unit
1 pc
Weight per Piece (excluding packing)
100.0 GRM
Custom tariff number
85389091
Country of origin
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
12.2 mm
09/03/2014 Page 1 / 5
https://www.phoenixcontact.com/us/products/2701152
Inline terminal - IB IL 24 DI 4-XC-PAC - 2701152
Technical data
Dimensions
Height
140.5 mm
Depth
71.5 mm
Note on dimensions
Housing dimensions
Ambient conditions
Ambient temperature (operation)
-40 °C ... 55 °C (See also the "Tested successfully: Use under extreme
ambient conditions" section of the data sheet.)
-40 °C ... 60 °C (At US < 24.5 V; see also the "Tested successfully: Use
under extreme ambient conditions" section of the data sheet.)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
GRP_Temperature class
T2 (-40°C ... 55°C, EN 50155)
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection
IP20
General
Weight
66 g
Note on weight specifications
with connector
Mounting type
DIN rail
Operating mode
Process data operation with 4 bits
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Test section
5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz
1 min
5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz
1 min
7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min
24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min
Interfaces
Fieldbus system
Lokalbus
Designation
Inline local bus
Connection method
Inline data jumper
Transmission speed
500 kBit/s
Power supply for module electronics
Supply voltage
24 V DC (via voltage jumper)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Supply current
40 mA
Communications power UL
7.5 V (via voltage jumper)
09/03/2014 Page 2 / 5
https://www.phoenixcontact.com/us/products/2701152
Inline terminal - IB IL 24 DI 4-XC-PAC - 2701152
Technical data
Power supply for module electronics
Current consumption
max. 40 mA (from the local bus)
Power consumption
max. 0.3 W (at UL)
Inline potentials
Communications power UL
7.5 V DC
Current consumption from UL
max. 40 mA
Segment supply voltage US
24 V DC (nominal value)
Current consumption from US
max. 1 A
Power consumption
max. 0.3 W (at UL)
Digital inputs
Input name
Digital inputs
Connection method
Spring-cage connection
2, 3-wire
Number of inputs
4 (EN 61131-2 type 1)
Typical response time
< 1 ms
Input voltage
24 V DC (via voltage jumper)
Input voltage range "0" signal
-3 V DC ... 5 V DC
Input voltage range "1" signal
15 V DC ... 30 V DC
Nominal input current at UIN
min. 3 mA (at nominal voltage)
Classifications
eCl@ss
eCl@ss 4.0
27240404
eCl@ss 4.1
27240404
eCl@ss 5.0
27242204
eCl@ss 5.1
27242604
eCl@ss 6.0
27242604
eCl@ss 7.0
27242604
eCl@ss 8.0
27242604
ETIM
ETIM 2.0
EC001433
ETIM 3.0
EC001599
ETIM 4.0
EC001599
ETIM 5.0
EC001599
09/03/2014 Page 3 / 5
https://www.phoenixcontact.com/us/products/2701152
Inline terminal - IB IL 24 DI 4-XC-PAC - 2701152
Classifications
UNSPSC
UNSPSC 6.01
43172015
UNSPSC 7.0901
43201404
UNSPSC 11
39121311
UNSPSC 12.01
39121311
UNSPSC 13.2
39121311
Approvals
Approvals
Approvals
UL Recognized / cUL Recognized / cULus Recognized
Ex Approvals
Approvals submitted
Approval details
UL Recognized
cUL Recognized
cULus Recognized
Drawings
09/03/2014 Page 4 / 5
https://www.phoenixcontact.com/us/products/2701152
Inline terminal - IB IL 24 DI 4-XC-PAC - 2701152
Connection diagram
Block diagram
1.1
IN 2
IN 1
+24 V
1.2
2.2
1.3
2.3
1.4
2.4
Local bus
+24 V
UL
2
1
OPC
2
IN 3
1.5
2.5
1.6
2.6
2
2
2
IN 4
+24 V
+24 V
3
4
+24 V (US)
+24 V (UM)
Dimensioned drawing
140,5
71,5
119,8
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com
09/03/2014 Page 5 / 5