0
登录后你可以
  • 下载海量资料
  • 学习在线课程
  • 观看技术视频
  • 写文章/发帖/加入社区
创作中心
发布
  • 发文章

  • 发资料

  • 发帖

  • 提问

  • 发视频

创作活动
2701164

2701164

  • 厂商:

    PHOENIX(菲尼克斯)

  • 封装:

  • 描述:

    OUTPUT MODULE 8 ANALOG

  • 数据手册
  • 价格&库存
2701164 数据手册
IB IL AO 4/8/U/BP-XC-PAC Inline analog output terminal, version for extreme conditions, 8 outputs Data sheet 8359_en_00 1 © PHOENIX CONTACT 2012-05-08 Description This terminal is designed for use within an Inline station. This terminal provides an 8-channel output module to output analog standard voltage signals. The output values are represented by 16-bit or 8-bit values. Thanks to special engineering measures and tests, the terminal can be used under extreme ambient conditions. Features – – – – – – – – – Eight analog signal outputs Connection of actuators in 2-wire technology with shield connection Communication via either process data or parameter channel (PCP) Channels are configured independently of one another using the bus system. Measured values can be represented in four different formats Diagnostic indicator Can be used under extreme ambient conditions Painted PCBs Extended temperature range T2 (-40°C … +55°C) This data sheet is only valid in association with the IL SYS INST UM E user manual. Make sure you always use the latest documentation. It can be downloaded at www.phoenixcontact.net/catalog. IB IL AO 4/8/U/BP-XC-PAC Table of contents 1 Description.................................................................................................................................. 1 2 Ordering data.............................................................................................................................. 3 3 Technical data ............................................................................................................................ 4 4 Tolerance and temperature response ........................................................................................ 7 5 Tested successfully: Use under extreme ambient conditions ..................................................... 8 6 Internal basic circuit diagram ...................................................................................................... 9 7 Electrical isolation ................................................................................................................................................ 10 8 Local diagnostic indicators ........................................................................................................10 9 Terminal point assignment for each connector ..........................................................................10 10 Installation instructions ..............................................................................................................11 11 Connection notes.......................................................................................................................11 12 Connection example ........................................................................................................................................... 11 13 Connecting shielded cables using the shield connector ............................................................12 14 Process data..............................................................................................................................12 15 OUT process data......................................................................................................................13 15.1 15.2 15.3 Output word OUT1 (control word) ................................................................................................................ 14 Parameters in output word OUT1 ................................................................................................................. 15 Parameters for configuration ........................................................................................................................ 15 16 IN process data..........................................................................................................................16 16.1 16.2 Input word IN1 (status word)......................................................................................................................... 16 Input words IN2 to IN5 .................................................................................................................................. 16 17 Formats for representing output values......................................................................................17 17.1 17.2 17.3 17.4 IB IL format (default setting) ......................................................................................................................... 17 IB ST format ................................................................................................................................................. 18 S7-compatible format ................................................................................................................................... 19 “Standardized representation” format........................................................................................................... 20 18 Configuration and analog value transmission ............................................................................21 19 PCP communication ..................................................................................................................22 19.1 19.2 8359_en_00 Object dictionary .......................................................................................................................................... 22 Object descriptions....................................................................................................................................... 23 PHOENIX CONTACT 2 IB IL AO 4/8/U/BP-XC-PAC 2 Ordering data Products Description Type Inline analog input terminal, version for extreme conditions, complete with ac- IB IL AO 4/8/U/BP-XC-PAC cessories (connector and labeling field), 8 outputs, 0 - 10 V, ±10 V, 2-wire connection technology Order No. Pcs. / Pkt. 2701164 1 Pcs. / Pkt. Accessories Description Type Order No. Inline shield connector for analog Inline terminals IB IL SCN 6-SHIELD-TWIN 2740245 5 Shield connection clamp for applying the shield on busbars SK 8 3025163 10 Shield connection clamp for applying the shield on busbars SK 14 3025176 10 Shield connection clamp for applying the shield on busbars SK 20 3025189 10 Shield connection clamp for applying the shield on busbars SK 35 3026463 10 Support for mounting on the NS 35/7,5 DIN rail, for 10 mm x 3 mm busbars AB-SK 3025341 10 Support for direct mounting with contact to the mounting surface AB-SK 65 3026489 10 Support, made of insulation material, with fixing screws, can be used for either 10 mm x 3 mm or 6 mm x 6 mm busbars AB-SK/E 3026476 10 Neutral busbar, 3 mm x 10 mm, length: 1000 mm NLS-CU 3/10 SN 1000MM 0402174 10 Power terminal, conductor cross section: 0.5 - 4 mm², width: 7 mm AK 4 0404017 50 Power terminal, conductor cross section: 0.5 - 4 mm², width: 7 mm; color: green-yellow AK 4 GNYE 0421029 50 Power terminal, conductor cross section: 0.5 - 4 mm², width: 7 mm; color: black AKG 4 BK 0421032 50 Documentation Description Type Order No. Pcs. / Pkt. “Automation terminals of the Inline product range” user manual IL SYS INST UM E – – 8359_en_00 PHOENIX CONTACT 3 IB IL AO 4/8/U/BP-XC-PAC 3 Technical data Dimensions (nominal sizes in mm) 136,8 71,5 119,8 Housing dimensions (width x height x depth) 12.2 x 136.8 x 71.5 mm General data Color Green Weight 215 g (with connectors) Operating mode Process data mode with 5 words/1 word PCP Connection method for actuators 2-wire technology with shield connection Ambient temperature (operation) -40 °C ... +55°C (see also the “Tested successfully: Use under extreme ambient conditions” section of the data sheet). Ambient temperature (storage/transport) -40 °C ... +85°C Temperature class T2 (-40°C ... +55°C, IEC 50155) Permissible humidity (operation/storage/transport) 10% to 95%, according to DIN EN 61131-2 Permissible air pressure (operation/storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level) Degree of protection IP20 Protection class III, IEC 61140, EN 61140, VDE 0140-1 Connection data Designation Inline connector Connection method Spring-cage connection Conductor cross section, solid/stranded 0.08 mm2 ... 1.5 mm2 Conductor cross section (AWG) 28 ... 16 Inline local bus interface Connection method Inline data jumper Transmission speed 500 kbps Power consumption Communications power UL 7.5 V DC Current consumption from UL 80 mA (typical) I/O supply voltage UANA 24 V DC Current consumption at UANA 72 mA (typical) Total power consumption 2.35 W (typical) Supply of the module electronics and I/O through bus coupler/power terminal Connection method 8359_en_00 Potential routing PHOENIX CONTACT 4 IB IL AO 4/8/U/BP-XC-PAC Analog outputs Number Eight analog voltage outputs Connection of signals 2 or 3-wire, shielded twisted pair cable Signals 0 V to 10 V, 0 V to 5 V, ±10 V, ±5 V Output value representation 16 bits (15 bits with sign bit) or 8 bits (7 bits with sign bit) Resolution of the DAC 16 bits Resolution (quantization) Inline format 0 V to 10 V 0 V to 10.837 V 0.333 mV/LSB 0 V to 5 V 0 V to 5.419 V 0.167 mV/LSB ±10 V -10.837 V to +10.837 V 0.333 mV/LSB ±5 V -5.419 V to +5.419 V 0.167 mV/LSB Basic error limit Voltage: ±0.1% (typical) of the output range final value Output load 2 kΩ, minimum, 30 kΩ, typical Process data update including conversion time of the D/A converter 2 ms Slew rate (>99% of the final value) < 1 ms at ohmic load Actuator cable length 250 m, maximum, using shielded cable 10 m, maximum, using unshielded cable Default Output range ±10 V Format IB IL Behavior upon bus reset HOLD (hold last value) Protective equipment Transient protection of analog outputs Yes Short-circuit protection of analog outputs Yes, for at least 1 minute Electrical isolation Common potentials The 24 V main voltage UM, 24 V segment voltage US, and GND have the same potential. FE is a separate potential area. Separate potentials in the terminal Test distance Test voltage 7.5 V supply voltage/ ±15 V 500 V AC, 50 Hz, 1 min. 7.5 V supply voltage (bus logic)/functional earth ground 500 V AC, 50 Hz, 1 min. ±15 V-, +5 V analog supply (analog I/O)/functional earth ground 500 V AC, 50 Hz, 1 min. Error messages to the higher-level control or computer system Failure of the internal I/O voltage supply Yes, I/O error message sent to the bus coupler Failure of or insufficient communications power UL Yes, I/O error message sent to the bus coupler Signal rise times: voltage output 0 V to 10 V (typical values) 10% to 90% 0% to > 99% (including overshoots) No-load operation 9 µs 20 µs Ohmic load RL = 2 kΩ 10 µs 22 µs Ohmic/capacitive load RL = 2 kΩ / CL = 10 nF (parallel) 9 µs 28 µs Ohmic/capacitive load RL = 2 kΩ / CL = 220 nF (parallel) 71 µs 175 µs Ohmic/inductive load RL = 2 kΩ / LL = 3,3 mH (serial) 9 µs 19 µs 8359_en_00 PHOENIX CONTACT 5 IB IL AO 4/8/U/BP-XC-PAC Signal rise times: voltage output 0 V to 5 V (typical values) 10% to 90% 0% to > 99% (including overshoots) No-load operation 8 µs 18 µs Ohmic load RL = 2 kΩ 9 µs 20 µs Ohmic/capacitive load RL = 2 kΩ / CL = 10 nF (parallel) 8 µs 26 µs Ohmic/capacitive load RL = 2 kΩ / CL = 220 nF (parallel) 29 µs 118 µs Ohmic/inductive load RL = 2 kΩ / LL = 3.3 mH (serial) 8 µs 20 µs Signal rise times: voltage output ±5 V (typical values) 10% to 90% 0% to > 99% (including overshoots) No-load operation 9 µs 19 µs Ohmic load RL = 2 kΩ 10 µs 20 µs Ohmic/capacitive load RL = 2 kΩ / CL = 10 nF (parallel) 9 µs 28 µs Ohmic/capacitive load RL = 2 kΩ / CL = 220 nF (parallel) 54 µs 150 µs Ohmic/inductive load RL = 2 kΩ / LL = 3.3 mH (serial) 9 µs 20 µs Signal rise times: voltage output ±10 V (typical values) 10% to 90% 0% to > 99% (including overshoots) No-load operation 12 µs 24 µs Ohmic load RL = 2 kΩ 13 µs 27 µs Ohmic/capacitive load RL = 2 kΩ / CL = 10 nF (parallel) 12 µs 32 µs Ohmic/capacitive load RL = 2 kΩ / CL = 220 nF (parallel) 117 µs 220 µs Ohmic/inductive load RL = 2 kΩ / LL = 3.3 mH (serial) 12 µs 24 µs Programming data Local bus (INTERBUS) ID code DFhex (223dec) Length code 05hex Input address area 5 words Output address area 5 words Parameter channel (PCP) 1 words Register length (bus) 6 words For the programming data/configuration data of other bus systems, please refer to the corresponding electronic device data sheet (e.g., GSD, EDS). Approvals For the latest approvals, please visit www.phoenixcontact.net/catalog. 8359_en_00 PHOENIX CONTACT 6 IB IL AO 4/8/U/BP-XC-PAC 4 Tolerance and temperature response All percentage tolerance values refer to the relevant measuring range final value. Unless stated otherwise, nominal operation (nominal voltage, preferred mounting position, default format, identical measuring range setting for channels) is used as the basis. The tolerance values refer to the operating temperature range specified in the tables. The operable range outside this range is not taken into consideration. Please also observe the tolerances under influences of electromagnetic interference. The maximum tolerance values represent the worst case measurement inaccuracy. They contain the theoretical maximum possible tolerances in the output range sections measuring ranges as well a the theoretical maximum possible tolerances of the calibration and test equipment. Tolerance and temperature response The tolerance values refer to the measuring range final value at a typical load (30 kΩ). TA = 25°C Output range Absolute (typical) Absolute (maximum) Relative (typical) Relative (maximum) 0 V to 5 V, ±5 V ±18 mV ±25 mV ±0.36% ±0.50% 0 V to 10 V, ±10 V ±19 mV ±25 mV ±0.19% ±0.25% TA = -25°C...+55°C Output range Absolute (typical) Absolute (maximum) Relative (typical) Relative (maximum) 0 V to 5 V, ±5 V ±22 mV ±40 mV ±0.44% ±0.80% 0 V to 10 V, ±10 V ±26 mV ±40 mV ±0.26% ±0.40% Additional tolerances influenced by electromagnetic fields Type of electromagnetic interference Typical deviation of the output range final value (relative) Electromagnetic fields; field strength 10 V/m according to EN 61000-4-3/IEC 61000-4-3 < ±0.5% Conducted interference Class 3 (test voltage 10 V) according to EN 61000-4-6/IEC 61000-4-6 < ±0.5% Fast transients (burst), 4 kV supply, 2 kV input according to EN 61000-4-4/IEC 61000-4-4 < ±0.5% 8359_en_00 PHOENIX CONTACT 7 IB IL AO 4/8/U/BP-XC-PAC 5 Tested successfully: Use under extreme ambient conditions The terminal has been tested successfully over 250 temperature change cycles in accordance with IEC 61131-2 in the range from -40°C to +70°C. The following conditions were observed: – The Inline devices for all connecting cables were connected with a minimum conductor cross section of 0.5 mm² – The Inline station was installed on a wall-mounted horizontal DIN rail – Fans were used to ensure continuous movement of air in the control cabinet – The Inline station was not exposed to vibration or shock – The Inline station was operated with a maximum of 24.5 V (ensured by using regulated power supply units) 3 h + 30 min t1 Tmax + 2 K (3 + 0,6) K/min Tmin + 3 K 3 h + 30 min t1 1 Figure 1 Temperature change cycle Temperature in the control cabinet/ambient temperature Cycle WARNING: The terminal is not approved for use in potentially explosive areas. The terminal is not approved for use in safety technology. 8359_en_00 PHOENIX CONTACT 8 IB IL AO 4/8/U/BP-XC-PAC 6 Internal basic circuit diagram Local bus OPC SRE 1 UL+ UANA UL- Levelshift 3V/5V Supervisor +24 V (US) U1 24 V U2 +5 V ±15 V REF µC U3 U4 Voltage Monitoring U5 U6 U7 U8 +24 V (UM) 1 7082B010 Figure 2 Internal wiring of the terminal points Key: R E F OPC Reference voltage Protocol chip Output level S R E 1 L e v e ls h ift 3 V /5 V Register expansion V o lta g e M o n ito r in g Voltage monitoring Level adaptation x x x S u p e r v is o r X X X 1 µ C DC/DC converter with electrical isolation Hardware monitoring Microcontroller Optocoupler Analog ground, electrically isolated from potential jumper ground Other symbols used are explained in the IL SYS INST UM E user manual. Digital/analog converter 8359_en_00 PHOENIX CONTACT 9 IB IL AO 4/8/U/BP-XC-PAC 7 Electrical isolation L o c a l b u s (IN ) U L B u s c o n n e c tio n O P C a n d m ic r o c o n tr o lle r (7 .5 V D C ) 9 L o c a l b u s (O U T ) U L U U A N A (2 4 V D C ) 2 4 V + 5 V ± 1 5 V I/O in te r fa c e + 5 V ± 1 5 V F E p o te n tia l Figure 3 8 (7 .5 V D C ) A N A (2 4 V D C ) A B E le c tr ic a l is o la tio n b e tw e e n a re a s A a n d B A n a lo g o u tp u ts Electrical isolation of the individual function areas D TR Des. D TR 1.1 1.1 2.1 2.1 1.2 1.2 2.2 2.2 1.3 1.3 2.3 2.3 1.4 2.4 7 0 8 2 A 0 0 5 Local diagnostic indicators Figure 4 Terminal point assignment for each connector Figure 5 Terminal points 1.1 2.1 1.2, 2.2 1.3, 2.3 1.4, 2.4 Terminal point assignment Signal Assignment U1 U2 – AGND Shield Voltage output 1 Voltage output 2 Not used Ground of voltage outputs Shield connection Local diagnostic indicators Color Meaning Green Diagnostics Green PCP active Function identification Yellow 8359_en_00 PHOENIX CONTACT 10 IB IL AO 4/8/U/BP-XC-PAC 10 Installation instructions High current flowing through potential jumpers UM and US leads to a temperature rise in the potential jumpers and inside the terminal. To keep the current flowing through the potential jumpers of the analog terminals as low as possible, always place the analog terminals after all the other terminals at the end of the main circuit (for the sequence of the Inline terminals: see also IL SYS INST UM E user manual). 12 Connection example Use a connector with shield connection when installing the actuators. Figure 6 shows the connection schematically (without shield connector). Connecting actuators S lo t 1 C h a n n e l 11 2 1 2 3 4 3 4 5 6 7 8 Connection notes Analog actuators with a cable length of < 10 m can be connected using unshielded twisted-pair cables. T R A O 1 Connect analog actuators with a cable length of > 10 m using shielded twisted-pair cables. 8359_en_00 2 1 2 1 2 1 2 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 O U T 8 Ensure that the braided shield is 15 mm longer than the strain relief when connecting a shielded actuator cable to the I/O connector. Connect the actuator cables as described in “Connecting shielded cables using the shield connector” on page 12. 4 /8 /U /B P O U T 1 At the terminal, connect one end of the shielding to PE. Fold the outer cable sheath back and connect the shield to the terminal via the shield connector clamp (with strain relief). The clamp connects the shield directly to FE on the terminal side. D 7 0 8 2 A 0 0 7 Figure 6 Connecting two actuators PHOENIX CONTACT 11 IB IL AO 4/8/U/BP-XC-PAC 13 Connecting shielded cables using the shield connector A 2 0 m m (0 .7 8 7 ") B a C 8 m m (0 .3 1 5 ") D E F 6 7 0 8 A 0 0 2 Figure 7 Connecting the shield using the shield connector The diameter of the actuator cable is usually too large to allow the cables to be inserted into the strain relief of the shield connector with sheathed and folded shield. The connection procedure for this cable therefore differs from the connection procedure described in the user manual. The differences from the user manual are marked in bold text. When connecting the cables, proceed as shown in Figure 7: Stripping cables • • • • • Strip the outer cable sheaths to the desired length (a). (A) The desired length (a) depends on the connection position of the wires and whether the wires should have a large or small amount of space between the connection point and the shield connection. Shorten the braided shield to 20 mm (A). Do not fold the braided shield back over the outer sheath. (B) Remove the protective foil. Strip 8 mm off the wires. (B) Inline wiring is normally without ferrules. However, it is possible to use ferrules. If you are using ferrules, make sure they are properly crimped. 8359_en_00 PHOENIX CONTACT 12 IB IL AO 4/8/U/BP-XC-PAC Wiring connectors (according to the user manual) • • • Push a screwdriver into the actuation shaft of the appropriate terminal point, so that you can insert the wire into the spring opening. Phoenix Contact recommends the screwdriver SZF 10,6X3,5 (Order. No. 1204517). Insert the wire. Remove the screwdriver from the opening. This clamps the wire. • The connector pin assignment can be found in the table on page 10. • • Insert the shield connection clamp in the shield connection according to the cable width (see user manual). Place the cables in the shield connection. (D) Push the outer cable sheaths up to the shield connection clamp. The wires with the braided shield must be underneath the shield connection clamp. The braided shield must project approximately 15 mm over the shield connection clamp. Close the shield connection. (E) Tighten the screws on the shield connection with a screwdriver. (F) Connecting the shield • Open the shield connection (see user manual). (C) 14 Process data The device has five process data words and one PCP word. O U T 1 C o n tro l w o rd O U T 2 O U T 3 O U T 4 O U T 5 O U T IN 2 IN 3 IN 4 IN 5 IN IN 1 S ta tu s w o rd Figure 8 15 7 0 6 3 A 0 0 8 Order of the process data words OUT process data Five process data output words are available. Configure the terminal channels via the OUT1 process data word. If you change the configuration the corresponding channel is re-initialized. If the configuration is invalid, a corresponding error message is output in the status word. The configuration settings are stored in a volatile memory only. 8359_en_00 PHOENIX CONTACT 13 IB IL AO 4/8/U/BP-XC-PAC 15.1 Output word OUT1 (control word) OUT1 Bit 15 14 13 12 11 Command code Assignment 10 9 8 Channel/output 7 6 5 4 3 2 1 0 0 0 0 0 0 0 0 0 Bit 15 to bit 8 (command code and channel/output): Bit 15 to bit 12 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 1 1 0 1 0 0 0 1 0 1 0 1 1 0 Bit 11 to bit 8 0 0 0 0 0 0 1 0 0 0 C C 1 1 0 0 C C 0 0 0 0 0 0 0 1 1 C 0 C 1 0 OUT1 0000hex 0100hex 0900hex 1x00hex 3C00hex 4xyyhex 5100hex 60yyhex Command function All outputs are disabled Output at channels 1 to 4 Output at channels 5 to 8 Read configuration in IN2 channel-by-channel. Read firmware version and module ID in IN2. Configure channel Output at channels 1 to 8 in 8-bit resolution Configure entire terminal (all channels) CCC = Channel number; CCC = 000: Channel 1; CCC = 111: Channel 8; yy = Parameter for configuration Control word assignment with command code 0hex OUT1 Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Assignment 0 0 0 0 Gr 0 Z FAO 0 0 0 0 0 0 0 0 0 All outputs disabled 1 Outputs are set to the value specified last 0 Output value directly; the buffered values for the channels that are not addressed are also output 1 Buffer value only 0 Channels 1 to 4 1 Channels 5 to 8 Gr Z FAO Group Buffering action Enabling the analog output channels Output word assignment with command “Output at channels 1 to 8 in 8-bit resolution” Word Byte OUT 1 1 2 5100hex 8359_en_00 OUT 2 3 4 ChanChannel 1 nel 2 OUT 3 5 6 ChanChannel 3 nel 4 OUT 4 7 8 ChanChannel 5 nel 6 OUT 5 9 10 ChanChannel 7 nel 8 PHOENIX CONTACT 14 IB IL AO 4/8/U/BP-XC-PAC 15.2 Parameters in output word OUT1 For command 4xyyhex and 60yyhex the parameters must be specified in OUT1 in addition to the command code. The parameters are only evaluated for these commands. OUT1 Bit 15 14 13 12 11 10 9 8 7 6 4xyy assignment 0 1 0 0 0 K K K 0 AV Format Output range 60yy assignment 0 1 1 0 0 0 0 0 0 AV Format Output range AV Format Output range 5 4 3 2 1 0 Output behavior during bus reset Representation of the output value in the OUT process data Output range settings If invalid parameters are specified in the parameter word, the command will not be executed. The command is confirmed in the input words with the set error bit. 15.3 Parameters for configuration The values displayed in bold are default settings. Bit 6: Code Dec 0 1 Output behavior during bus reset Bin 0 1 Hold Reset Bit 5 and bit 4 Code Dec 0 1 2 3 Format Bin 00 01 10 11 IB IL format (15 bits + sign bit with extended diagnostics) IB ST format (12 bits + sign bit + 3 diagnostic bits) S7-compatible format (15 bits + sign bit) Standardized representation format Bit 3 to bit 0: Code Dec Output range Bin 0 0000 0 V to 10 V 1 0001 ±10 V 2 0010 0 V to 5 V 3 0011 ±5 V 4 0100 ... ... 15 1111 8359_en_00 Reserved PHOENIX CONTACT 15 IB IL AO 4/8/U/BP-XC-PAC 16 IN process data 16.1 Input word IN1 (status word) Five IN process data words are available. The input word IN1 serves as status word. IN1 Bit 15 Assignment EB 14 13 12 11 10 9 8 Bits 14 to 8 of the control word are mirrored 7 6 5 4 3 2 1 0 0 0 0 0 0 0 0 0 EB: Error bit EB = 0 EB = 1 No error has occurred. An error has occurred. Mirroring of the command code: A command code mirrored from the control word. Here, the MSB is suppressed. 16.2 Input words IN2 to IN5 The mirrored output words, the configuration or the firmware version are transmitted to the controller board or the PC via the process data input words IN2 up to IN5 in accordance with the configuration. For control word 3C00hex, IN2 provides the firmware version and the module ID. Example: firmware version 1.23: IN2 Bit Assignment (hex) Meaning 8359_en_00 15 14 13 1 12 11 10 9 8 2 Firmware version 1.23 7 6 5 3 4 3 2 1 0 4hex Module ID PHOENIX CONTACT 16 IB IL AO 4/8/U/BP-XC-PAC 17 Formats for representing output values 17.1 IB IL format (default setting) The output value is represented in bits 14 to 0. An additional bit (bit 15) is available as a sign bit. Output value representation in IB IL format; 15 bits MSB 15 SB 14 SB 13 12 11 10 9 8 7 6 Analog value 5 4 3 2 1 LSB 0 Sign bit Typical analog values depending on the output range INTERBUS output word [hex] [dec] ≤7FFF ≤32767 7F00 32512 7530 30000 0001 1 0000 0 FFFF -1 8AD0 -30000 8100 -32512 80FF to 8000 -32768...-32513 (without 8001 and 8080) 8001 -32767 Overrange 8080 -32640 Underrange 8359_en_00 0 V to 10 V UOutput [V] +/-10 V UOutput [V] 0 V to 5 V UOutput [V] +/- 5 V UOutput [V] +10.837 +10.837 +10.0 +333.33 µ ≤0 0 0 0 HOLD +10.837 +10.837 +10.0 +333.33 µ 0 -333.33 µ -10.0 -10.837 HOLD +5.419 +5.419 +5.0 +166.67 µ ≤0 0 0 0 HOLD +5.419 +5.419 +5.0 +166.67 µ 0 -166.67 µ -5.0 -5.419 HOLD +10.837 +10.837 +5.419 +5.419 0 -10.837 0 -5.419 PHOENIX CONTACT 17 IB IL AO 4/8/U/BP-XC-PAC 17.2 IB ST format The output value is represented in bits 14 to 3. The remaining 4 bits are available as sign and error bits. Output value representation in IB ST format; 12 bits MSB 15 SB 14 SB 0 13 12 11 10 9 8 Analog value 7 6 5 4 3 2 0 1 0 LSB 0 0 Sign bit Reserved Typical analog values depending on the output range INTERBUS output word [hex] [dec] ≤7FFF 32767 7FF8 32760 4000 16384 0008 8 0000 0 FFF8 -8 C000 -16384 8008 -32760 ≥8000 -32768 8359_en_00 0 V to 10 V UOutput [V] 9.9976 9.9976 5.00 0.002441 0 0 0 0 0 +/-10 V UOutput [V] 9.9976 9.9976 5.00 0.002441 0 -0.002441 -5.0000 -9.9976 -9.9976 0 V to 5 V UOutput [V] 4.9988 4.9988 2.50 0.001221 0 0 0 0 0 +/- 5 V UOutput [V] 4.9988 4.9988 2.50 0.001221 0 -0.001221 -2.5000 -4.9988 -4.9988 PHOENIX CONTACT 18 IB IL AO 4/8/U/BP-XC-PAC 17.3 S7-compatible format The output value is represented in bits 14 to 0. An additional bit (bit 15) is available as a sign bit. Output value representation in the format compatible with S7 (15 bits) MSB 15 SB 14 SB 13 12 11 10 9 8 7 6 Analog value 5 4 3 2 1 LSB 0 Sign bit Typical analog values depending on the output range INTERBUS output word [hex] [dec] ≤7FFF ≤32767 7F00 32512 7EFF 32511 6C01 27649 6C00 27648 5100 20736 1 1 0 0 FFFF -1 E501 -6911 E500 -6912 AF00 -20736 9400 -27648 93FF -27649 8101 -32511 8000 to 8100 -32768 to -32512 8359_en_00 0 V to 10 V UOutput [V] 0 0 +11.7589 +10.0004 +10.0000 +7.5000 +361.69 µ 0 0 0 0 0 0 0 0 0 +/-10 V UOutput [V] 0 0 +11.7589 +10.0004 +10.0000 +7.5000 +361.69 µ 0 -361.69 µ -2.4996 -2.5000 -7.5000 -10.0000 -10.0004 -11.7589 0 0 V to 5 V UOutput [V] 0 0 +5.88 +5.0002 +5.0000 +3.7500 +180.845 µ 0 0 0 0 0 0 0 0 0 +/- 5 V UOutput [V] 0 0 +5.88 +5.0002 +5.0000 +3.7500 +180.845 µ 0 -180.845 µ -1.2498 -1.2500 -3.7500 -5.0000 -5.0002 -5.8800 0 PHOENIX CONTACT 19 IB IL AO 4/8/U/BP-XC-PAC 17.4 “Standardized representation” format The output value is represented in bits 14 to 0. An additional bit (bit 15) is available as a sign bit. Output value representation in “standardized representation” format (15 bits) MSB 15 SB 14 SB 13 12 11 10 9 8 7 6 Analog value 5 4 3 2 1 LSB 0 Sign bit Typical analog values depending on the output range INTERBUS output word [hex] [dec] 2A56 to 7FFF 10838 to 32767 2A55 10837 2710 10000 152B 5419 1388 5000 0001 1 0000 0 FFFF -1 EC78 -5000 EAD5 -5419 D8F0 -10000 D5AB -10837 D5AA to 8100 -10838 to -32512 80FF to 8000 (with- -32768 to out 8001 and 8080) -32513 8001 -32767 Overrange 8080 -32640 Underrange 8359_en_00 0 V to 10 V UOutput [V] +/-10 V UOutput [V] 0 V to 5 V UOutput [V] +/- 5 V UOutput [V] +10.837 +10.837 +10.0 +5.419 +5.0 +0.001 0 0 0 0 0 0 0 +10.837 +10.837 +10.0 +5.419 +5.0 +0.001 0 -0.001 -5.0 -5.419 -10.0 -10.837 -10.837 +5.419 +5.419 +5.419 +5.419 +5.0 +0.001 0 0 0 0 0 0 0 +5.419 +5.419 +5.419 +5.419 +5.0 +0.001 0 -0.001 -5.0 -5.419 -5.419 -5.419 -5.419 HOLD HOLD HOLD HOLD +10.837 +10.837 +5.419 +5.419 0 -10.837 0 -5.419 PHOENIX CONTACT 20 IB IL AO 4/8/U/BP-XC-PAC 18 Configuration and analog value transmission You can configure the terminal either via process data or via PCP and transmit the analog values accordingly. Example for terminal configuration via process data All channels are to hold their value (HOLD), use the IB IL format and output the values in the range 0 V to 5 V. Therefore the parameter value is 0002hex. Step 1 2 Process data OUT1 = 6002hex Wait until IN1 = 6002hex Analog value OUT2 = Channel 1, ..., OUT5 = Channel 4 OUT1 = 0100hex Wait until IN1 = 0100hex Analog value OUT2 = Channel 5, ..., OUT5 = Channel 8 OUT1 = 0900hex Wait until IN1 = 0900hex 3 4 5 6 Meaning Specify configuration Wait for confirmation Analog value output at channels 1 to 4 In the event that consistency of five words cannot be ensured, an intermediate step is recommended after every output command. The buffer bit in the “Write analog values” command is used for this purpose. As a result, step 3 and step 5 become more complicated: Step 1 2 3a 3b 3c Wait for confirmation Analog value output at channels 5 to 8 Wait for confirmation Secure process data transmission requires process data consistency of five words. 3d 4 5a 5b 5c 5d 6 8359_en_00 Process data OUT1 = 6002hex Meaning Specify configuration Wait for confirmaWait until IN1 = 6002hex tion Buffer command OUT1 = 0300hex Wait for confirmaWait until IN1 = 0300hex tion OUT2 = analog value of chan- Buffer the analog nel 1 values for chanOUT3 = analog value of chan- nels 1 to 4 nel 2 OUT4 = analog value of channel 3 OUT5 = analog value of channel 4 Output the analog OUT1 = 0100hex values for channels 1 to 4 Wait for confirmaWait until IN1 = 0100hex tion Buffer command OUT1 = 0B00hex Wait for confirmaWait until IN1 = 0B00hex tion OUT2 = analog value of chan- Buffer the analog nel 5 values for chanOUT3 = analog value of chan- nels 5 to 8 nel 6 OUT4 = analog value of channel 7 OUT5 = analog value of channel 8 Output the analog OUT1 = 0900hex values for channels 5 to 8 Wait for confirmaWait until IN1 = 0900hex tion PHOENIX CONTACT 21 IB IL AO 4/8/U/BP-XC-PAC 19 PCP communication For information on PCP communication, please refer to the IBS SYS PCP G4 UM E (Order No. 2745169) and IBS PCP COMPACT UM E (Order No. 9015349) user manuals. By default upon delivery, the terminal is configured according to the default settings on page 15. The terminal can be configured to suit your application using process data or PCP. In PCP mode, the terminal is configured with the “Config Table” object. The IBS CMD (for standard controller boards) and PC Worx (for Field Controllers (FC) and Remote Field Controllers (RFC)) programs are available for the configuration and parameterization of your INTERBUS system. Please refer to the corresponding documentation for more information. 19.1 Object dictionary Index 0080hex 0085hex Data type Array of Unsigned 16 Array of Unsigned 16 N 10 8 L 2 2 Meaning Object name Terminal configuration Config Table Analog values of the chan- Analog Out Values nels N: Number of elements rd: Read access permitted L: Length of an element in bytes wr: Write access permitted 8359_en_00 Rights rd/wr rd/wr PHOENIX CONTACT 22 IB IL AO 4/8/U/BP-XC-PAC 19.2 Object descriptions Config Table object Configure the terminal using this object. Object description: Object Config Table Access Read, Write Data type Array of Unsigned 16 Index 0080hex 10 x 2 bytes Subindex 00hex 01hex 02hex 03hex 04hex 05hex 06hex 07hex 08hex 09hex 0Ahex Write all elements Configuration of channel 1 Configuration of channel 2 Configuration of channel 3 Configuration of channel 4 Configuration of channel 5 Configuration of channel 6 Configuration of channel 7 Configuration of channel 8 System settings Reserved Length (bytes) 14hex 02hex Subindex 00hex Subindex 01hex to 0Ahex Data Terminal configuration Element value range The “Configuration channel x” elements have the following structure: Bit 15 14 13 12 11 10 9 8 7 6 Assignment 0 0 0 0 0 0 0 0 0 AV 5 4 Format 3 2 1 0 Output range For the value ranges of the individual parameters, please refer to “Parameters for configuration” on page 15. If an invalid configuration is specified, a negative confirmation is generated with error message 08hex, 00hex or xx30hex. The low byte of the additional error code is 30hex (value is out of range), the high byte contains the number of the affected element. Example: Config Table is completely filled with data (subindex 00) and the entry for channel 6 is invalid. In this case, the additional error code equals 0630hex. Additional functions in element 9 (system settings): 0001hex: Configuration via process data not locked 0002hex: Writing of the “Analog Out Values” object is permitted. 8359_en_00 PHOENIX CONTACT 23 IB IL AO 4/8/U/BP-XC-PAC Analog Out Values object The elements of this object contain the analog values of the channels in a format that has been selected for this channel. Writing to this object must be enabled in the Config Table object. Write value 0002hex to subindex 09 in the “Config Table” object for this purpose. Object description: Object Analog Values Access Read/Write Data type Array of Unsigned 16 Index 0085hex Subindex 00hex 01hex 02hex 03hex 04hex 05hex 06hex 07hex 08hex Read/write all elements Analog value of channel 1 Analog value of channel 2 Analog value of channel 3 Analog value of channel 4 Analog value of channel 5 Analog value of channel 6 Analog value of channel 7 Analog value of channel 8 Length (bytes) 10hex 02hex Subindex 00hex Subindex 01hex to 08hex Data Analog values of the channels 8359_en_00 8 x 2 bytes PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany www.phoenixcontact.com 24
2701164 价格&库存

很抱歉,暂时无法提供与“2701164”相匹配的价格&库存,您可以联系我们找货

免费人工找货