0
登录后你可以
  • 下载海量资料
  • 学习在线课程
  • 观看技术视频
  • 写文章/发帖/加入社区
创作中心
发布
  • 发文章

  • 发资料

  • 发帖

  • 提问

  • 发视频

创作活动
2701165

2701165

  • 厂商:

    PHOENIX(菲尼克斯)

  • 封装:

  • 描述:

    TEMP CONTROL MODULE 4 ANALOG

  • 数据手册
  • 价格&库存
2701165 数据手册
IB IL AI/TEMP 4 RTD-XC-PAC Inline analog input terminal, version for extreme conditions, 4 inputs, 2-wire connection method Data sheet 8360_en_00 1 © PHOENIX CONTACT 2016-01-25 Function description The terminal is designed for use within an Inline station. The terminal has four inputs that may be configured independently of each other and either for measuring voltages or resistances or for RTDs. The sensors are connected using the 2-wire connection method, so that a nominal resistance of at least 1000 Ω is recommended when sensors with a relatively small temperature coefficient (e.g., platinum sensors) are used. Features – – The resistance measurement with conversion into temperature values can be used for the temperature measurement with NTC resistors. The advantage of these resistors is a large temperature coefficient. Thanks to special engineering measures and tests, the terminal can be used under extreme ambient conditions. – – – – – – – Four measuring inputs that can be configured as – Voltage inputs 0 V ... 10 V – Inputs for resistance measurements up to 300 kΩ with output either in ohms or percent (potentiometer measurement) – Input for temperature measurements The terminal supports – Platinum sensors according to DIN EN 60751/ IEC 60751 and the SAMA guideline – Nickel sensors according to DIN 43760 and the SAMA guideline – KTY81-110, KTY81-210, KTY84 sensors – Viessmann Ni 500, Viessmann NTC10 k sensors – Siemens LG-Ni 1000 sensor Connection of sensors in 2-wire technology Communication via process data Channels are configured independently of one another using the bus system. Diagnostic indicators Can be used under extreme ambient conditions Painted PCBs Extended temperature range of -40°C … +70°C (see “Tested successfully: Use under extreme ambient conditions” on page 5) This data sheet is only valid in association with the IL SYS INST UM E user manual. Make sure you always use the latest documentation. It can be downloaded at phoenixcontact.net/products. IB IL AI/TEMP 4 RTD-XC-PAC Table of contents 1 Function description ................................................................................................................... 1 2 Ordering data.............................................................................................................................. 3 3 Technical data ............................................................................................................................ 3 4 Tested successfully: Use under extreme ambient conditions ..................................................... 5 5 Internal circuit diagram................................................................................................................ 6 6 Local diagnostic indicator ........................................................................................................... 7 7 Terminal point assignment .................................................................................................................................. 7 8 Installation instructions ............................................................................................................... 8 9 Connection notes ............................................................................................................................................... 8 10 Connection examples ................................................................................................................. 8 11 Process data............................................................................................................................... 9 11.1 11.2 Process data output words OUT .................................................................................................................... 9 Process data input words IN......................................................................................................................... 12 12 Formats for representing measured values................................................................................13 12.1 12.2 12.3 12.4 IB IL format (default setting) ......................................................................................................................... 13 IB ST format ................................................................................................................................................. 14 S7-compatible format ................................................................................................................................... 15 Standardized representation format ............................................................................................................. 16 13 Diagnostic codes in the in formats IB IL and standardized representation .................................16 14 Selecting measuring ranges and sensors ..................................................................................17 14.1 14.2 8360_en_00 Systematic errors ......................................................................................................................................... 17 Tolerance and drift ....................................................................................................................................... 17 PHOENIX CONTACT 2 / 19 IB IL AI/TEMP 4 RTD-XC-PAC 2 Ordering data Terminal blocks Description Type Order No. Pcs. / Pkt. IB IL AI/TEMP 4 RTD-XC-PAC 2701165 1 Accessories Description Type Order No. Pcs. / Pkt. Connector as replacement item IB IL SCN-12-OCP 2727624 10 Documentation Description Type Order No. Pcs. / Pkt. “Automation terminals of the Inline product range” user manual IL SYS INST UM E 2698724 1 Inline analog input terminal, version for extreme conditions, complete with accessories (connector and labeling field), 4 inputs, 0-10 V, resistance temperature detector (RTD), 2-wire connection technology 3 Technical data Dimensions (nominal sizes in mm) 140,5 71,5 119,8 Housing dimensions (width x height x depth) 12.2 x 140.5 x 71.5 mm General data Color Green Weight 68 g (with connector) Operating mode Process data mode with 2 words Connection method for sensors 2-wire technology Ambient temperature (operation) -25°C ... +55°C (Standard) -40 °C ... +70°C (Extended, see also the “Tested successfully: Use under extreme ambient conditions” section of the data sheet). Ambient temperature (storage/transport) -40 °C ... +85°C Permissible humidity (operation/storage/transport) 10% ... 95%, according to DIN EN 61131-2 Permissible air pressure (operation/storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level) Degree of protection IP20 Protection class III, IEC 61140, EN 61140, VDE 0140-1 8360_en_00 PHOENIX CONTACT 3 / 19 IB IL AI/TEMP 4 RTD-XC-PAC Connection data Designation Inline connector Connection method Spring-cage connection Conductor cross section, solid/stranded 0.08 mm2 ... 1.5 mm2 Conductor cross section [AWG] 28 ... 16 Inline local bus interface Connection method Inline data jumper Transmission speed 500 kbps Power consumption Communications power UL 7.5 V Current consumption from UL ≤ 60 mA (typical) ≤ 0.45 W (typical) Total power consumption Supply of the module electronics and I/O through bus coupler/power terminal Connection method Potential routing Analog inputs Number 4 Connection of signals 2-wire, shielded sensor cable Sensor types that can be used Pt, Ni, KTY, voltage 0 V ... 10 V Standards for characteristic curves According to DIN EN 60751: 07/1996/ according to SAMA RC 21-4-1966 Conversion time of the A/D converter 150 ms Process data update time of all four channels 600 ms Protective equipment None Electrical isolation The terminal is only supplied with power from the logic circuit (communications power UL = 7.5 V). All four analog inputs refer to one potential that is electrically isolated from all other circuits (UL, main circuit UM, segment circuit US, analog circuit UANA). FE (functional earth ground) is a separate potential area that is connected with shield and analog ground via a coupling network consisting of a 1 MΩ resistor and a 1 nF capacitor connected in parallel. Separate potentials in the IB IL AI/TEMP 4 RTD-XC-PAC terminal Test distance Test voltage Analog inputs / UL, UM, US, UANA 500 V AC, 50 Hz, 1 min Error messages to the higher-level control or computer system None Error messages via process data Peripheral fault/user error Yes (see page 16) Mechanical requirements Vibration, IEC 60068-2-6; EN 60068-2-6 5g Shock, IEC 60068-2-27; EN 60068-2-27 30g 8360_en_00 PHOENIX CONTACT 4 / 19 IB IL AI/TEMP 4 RTD-XC-PAC Programming data Local bus (INTERBUS) ID code 5Fhex (95dec) Length code 02hex Input address area 2 words Output address area 2 words Parameter channel (PCP) 0 bytes Register length (bus) 2 words For the programming data/configuration data of other bus systems, please refer to the corresponding electronic device data sheet (e.g., GSD, EDS). Approvals For the latest approvals, please visit www.phoenixcontact.net/catalog. 4 Tested successfully: Use under extreme ambient conditions XC terminals have been tested successfully over 250 temperature change cycles in accordance with IEC 61131-2 in the range from -40°C to +70°C. The following conditions were observed: – The Inline devices for all connecting cables were connected with a minimum conductor cross section of 0.5 mm² – The Inline station was installed on a wall-mounted horizontal DIN rail – Fans were used to ensure continuous movement of air in the control cabinet – The Inline station was not exposed to vibration or shock – The Inline station was operated with a maximum of 24.5 V (ensured by using regulated power supply units) 3 h + 30 min t1 Tmax + 2 K (3 + 0,6) K/min Tmin + 3 K 3 h + 30 min t1 1 Figure 1 Temperature change cycle Temperature in the control cabinet/ambient temperature Cycle WARNING: The terminal is not approved for use in potentially explosive areas. The terminal is not approved for use in safety technology. 8360_en_00 PHOENIX CONTACT 5 / 19 IB IL AI/TEMP 4 RTD-XC-PAC 5 Internal circuit diagram OPC Local bus OPC Protocol chip µC UL+ UANA UL- Microcontroller with multiplexer and analog-digital converter MUX UL 3.3V UL 3.3V Coupling network µC Analog ground EEPROM MUX DC/DC converter with electrical isolation REF Optocoupler REF EEPROM +24V US Voltage reference Non-volatile memory +24V UM Figure 2 Internal circuit diagram Other symbols used are explained in the IL SYS INST UM E user manual. 8360_en_00 PHOENIX CONTACT 6 / 19 IB IL AI/TEMP 4 RTD-XC-PAC 6 Local diagnostic indicator 7 Terminal point assignment D 1.1 Figure 3 Des. D Local diagnostic indicator Color Meaning Green Diagnostics Function identification 1.1 2.1 2.1 1.2 1.2 2.2 1.3 1.3 2.3 2.3 1.4 1.4 2.4 2.4 1.5 1.5 2.5 2.5 1.6 1.6 2.6 2.6 2.2 Green Figure 4 Terminal point assignment 2-wire connection Terminal points 1.1 Signal Assignment +AI1 1.2 1.3 1.4 AGND* Shield* +AI2 1.5 1.6 2.1 AGND* Shield* +AI3 2.2 2.3 2.4 AGND* Shield* +AI4 2.5 2.6 AGND* Shield* Resistance/voltage input of channel 1 Sensor ground of channel 1 Shield connection of channel 1 Resistance/voltage input of channel 3 Sensor ground of channel 3 Shield connection of channel 3 Resistance/voltage input of channel 2 Sensor ground of channel 2 Shield connection of channel 2 Resistance/voltage input of channel 4 Sensor ground of channel 4 Shield connection of channel 4 * 8360_en_00 AGND and shield are connected internally. PHOENIX CONTACT 7 / 19 IB IL AI/TEMP 4 RTD-XC-PAC 8 Installation instructions High current flowing through potential jumpers UM and US leads to a temperature rise in the potential jumpers and inside the terminal. To keep the current flowing through the potential jumpers of the analog terminals as low as possible, always place the analog terminals after all the other terminals at the end of the main circuit (for the sequence of the Inline terminals, see also IL SYS INST UM E user manual). 9 Connection notes Always connect the analog sensors using shielded, twisted pair cables. A shield may reduce the influence of electromagnetic interference. Connect the shield at one end with the shield connection of the terminal and insulate it at the sensor. Connect unused sensor inputs with sensor ground. Connect the shield externally in areas with strong EMI, and insulate it at the device and the sensor 10 Connection examples D D AI/TEMP 4 RTD AI/TEMP 4 RTD 1.1 2.1 1.1 2.1 +AI 2 +AI1 OUT1 +AI 2 +AI1 1.2 2.2 AGND AGND AGND 1.3 2.3 Shield Shield Shield OUT3 +AI4 +AI3 1.5 2.5 Figure 5 8360_en_00 OUT4 1.5 2.5 AGND AGND Shield Shield 1.6 2.6 Shield Shield 1.4 2.4 +AI4 AGND AGND 1.3 2.3 1.4 2.4 +AI3 OUT2 1.2 2.2 AGND 1.6 2.6 Shield Examples for connecting RTDs and sensors for voltage measurement PHOENIX CONTACT 8 / 19 IB IL AI/TEMP 4 RTD-XC-PAC 11 Process data 11.1 Process data output words OUT Two process data output words are available. If you change the configuration, the message "Measured value invalid" appears (diagnostic code 8004hex), until new measured values are available. Configure the terminal channels via the process data output words OUT1 and OUT2. In this context, the output word OUT1 contains the command and output word OUT2 contains the parameters belonging to this command. Please note that extended diagnostics is only possible if the IB IL format or standardized representation are configured as the format for representing the measured values. As the IB IL format is preset on the terminal, it is available immediately after the voltage has been applied. The configuration settings are stored in a volatile memory. 11.1.1 Output word OUT1 (control word) OUT1 Bit 15 14 13 12 11 10 Command code Assignment 9 8 7 6 5 4 3 2 1 0 0 0 0 0 0 0 0 0 Bit 15 to bit 8 (command code): 0 0 0 0 0 0 0 1 Bit 15 to bit 8 0 0 0 0 0 1 0 0 1 1 1 1 0 0 0 0 C C 0 C OUT1 C 0x00hex C 1x00hex 0 3C00hex C 4x00hex 0 1 0 1 0 0 C C 5x00hex 1 0 0 1 0 0 C C 9x00hex Command function Read measured value in IN2 channel-by-channel. Read configuration in IN2 channel-by-channel. Read firmware version and module ID in IN2. Configure channel, configuration in OUT2. Configure channel and read measured value of the channel, configuration in OUT2, measured value in IN2. Read and write R0 value of the channel. CC = Channel number Bit 9 and bit 8: Channel number Code dec bin 0 00 1 01 2 10 3 11 8360_en_00 Channel number Channel 1 Channel 2 Channel 3 Channel 4 PHOENIX CONTACT 9 / 19 IB IL AI/TEMP 4 RTD-XC-PAC 11.1.2 Output word OUT2 (parameter word) The parameters for the commands 4x00hex, 5x00hex, and 9x00hex must be specified in OUT2. This parameter word is only evaluated for these commands. The parameter word is only evaluated when the control word contains a valid command code. Reserved parameters may not be used. Commands 4x00hex, 5x00hex: OUT2 Bit 15 14 13 R0 Assignment 12 11 Filter 10 9 Resolution 8 7 6 Format 5 4 3 Sensor type 2 1 0 Measurement mode Command 9x00hex: OUT2 Bit 15 14 13 12 11 10 9 Selection of formats for the representation of measured values Sensor type setting 5 4 3 2 1 0 Short designation R0 Default 1000 Ω Resolution Quantization of the measured value, select between °Celsius or °Fahrenheit. Filter No mean value Resolution 0.1 Ω/0.01%/0.01 K IB IL format Format Sensor 0 V ... 10 V type Setting the measurement MeasureVoltage mode ment mode measurement 0 V ... 10 V R0 Selecting the resistance of the sensor at 0°C; The configurable nominal resistance R0 is taken for the temperature calculation based on nickel and platinum sensors. Should the desired resistance not be found in the code table, the nominal resistance of 1 Ω to 65535 Ω can be configured with increments of 1 Ω. To do this, use the command 9x00hex with the R0 value in the OUT2 process data word. Filter Selection of mean value generation. After every conversion, the measured value is saved in a mean value memory via which the mean value is generated. The memory size can be selected with the filter option. E.g., 8360_en_00 6 for a 16-sample mean value, the mean value is generated using the last 16 measured values. The following configurations are possible: Value of reference resistance R0 Selection of mean value generation (filtering) Resolution settings 7 R0 value, 1 Ω increments Assignment Configuration 8 The resolution for voltage measurements depends only on the transmission format. Format Representation of the measured value in the IN process data Sensor type Sensor type setting; The configurable sensor type determines the conversion of the electrical signal present at the input into a physical size. Sensor type and measurement mode must be set for a sensor to be connected to receive a measuring result with a suitable accuracy. If, for instance, a Pt 1000 sensor is to be connected, a resistance measurement for the range from 0 Ω ... 3 kΩ can be used as a measurement mode. Also, a resistance measurement would be possible for the range from 0 Ω ... 300 kΩ, however, this measurement mode provides a considerably lower accuracy in the resistance range relevant for Pt 1000. Measurement mode Setting the selected measurement mode; The measuring mode determines the signal conditioning by the configurable inputs. Every input can be configured for voltage or resistance measurement as desired. For the resistance measurement, an auxiliary current that generates a voltage drop over the resistance to be measured is generated. The current supply is deactivated for the voltage measurement. PHOENIX CONTACT 10 / 19 IB IL AI/TEMP 4 RTD-XC-PAC 11.1.3 Parameters for configuration The values in bold are default settings. Bit 15 to bit 13 dec 0 1 2 3 4 5 6 7 Code bin 000 001 010 011 100 101 110 111 Bit 6 to bit 3: Nominal resistance R0 [Ω] hex 0 1 2 3 4 5 6 7 1000 100 500 2000 5000 10000 Reserved 20000 (can be set) Bit 12 and bit 11 Code dec bin 0 00 1 01 2 10 3 11 Filter No mean value 8-sample mean value 32-sample mean value Reserved Bit 10 and bit 9 Code dec bin 0 1 2 3 00 01 10 11 Resolution for sensor type 1 2 3 ... 12 (Resistance (Potentio(Tempe[Ω]) meter [%]) rature) 0.1 0.01 0.01°C 1 0.1 0.1°C 10 1 0.01°F Reserved 0.1°F Bit 8 and bit 7 Code dec bin 0 00 1 01 2 3 10 11 8360_en_00 Format Code dec bin 0 0000 1 0001 2 0010 3 0011 4 0100 5 0101 6 0110 7 0111 8 1000 9 1001 10 1010 11 1011 12 1100 13 1101 14 1110 15 1111 Sensor type 0 V ... 10 V Resistor Potentiometer [%] Pt DIN Pt SAMA Ni DIN Ni SAMA KTY 81-110 KTY 81-210 KTY 84 Ni 1000 (Siemens LG) Ni 500 (Viessmann) NTC 10 k (Viessmann) Reserved Reserved Not configured Bit 2 to bit 0: Code dec bin 0 000 1 001 2 010 3 011 4 100 5 101 6 110 7 111 Measurement mode Voltage measurement 0 V ... 10 V Reserved Reserved Resistance measurement 0 Ω ... 3 kΩ Resistance measurement 0 Ω ... 300 kΩ Reserved Reserved Not configured IB IL (15 bits + sign bit with extended diagnostics) IB ST (12 bits + sign bit + 3 diagnostic bits) S7-compatible (15 bits + sign bit) Standardized representation (15 bits + sign bit with extended diagnostics) PHOENIX CONTACT 11 / 19 IB IL AI/TEMP 4 RTD-XC-PAC 11.2 Process data input words IN 11.2.1 Input word IN1 (status word) The IN1 word is a copy of the OUT1 process data word. IN1 Bit 15 14 13 12 11 10 9 8 Mirroring of the command code Assignment 7 6 5 4 3 2 1 0 0 0 0 0 0 0 0 0 Mirroring of the command code: A command code mirrored from the control word. 11.2.2 Input word IN2 The measured values, the configuration or the firmware version are transmitted to the controller board or the PC via the process data input word IN2 according to the configuration. For control word 3C00hex, IN2 provides the firmware version and the module ID. Example: Firmware version 1.23: Bit Assignment (hex) Meaning IN2 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 1 2 3 Ehex Firmware version 1.23 Module ID For control word 9x00hex, IN2 provides the configuration and R0. MSB 15 14 13 12 11 10 9 8 7 6 5 Configuration / R0 8360_en_00 4 3 2 LSB 1 0 Basically four formats are available for the representation of the measured values. For more detailed information on the formats, please refer to “Formats for representing measured values” on page 13. IB IL, S7-compatible, standardized representation formats MSB 15 14 13 12 11 10 9 8 7 6 5 SB Analog value 4 3 2 4 3 2 1 LSB 0 IB ST format MSB 15 14 13 12 11 10 9 SB MSB LSB SB 0 OC OR 8 7 Analog value 6 5 LSB 1 0 O O 0 C R Most significant bit Least significant bit Sign bit Reserved Open circuit Overrange PHOENIX CONTACT 12 / 19 IB IL AI/TEMP 4 RTD-XC-PAC 12 Formats for representing measured values 12.1 IB IL format (default setting) The measured value is represented in bits 14 to 0. An additional bit (bit 15) is available as a sign bit. This format supports extended diagnostics. Values >8000hex and 10.837 > 3251.21 > 3251.2 > 3251.2 7F00 32512 10.837 3251.21 3251.2 3251.2 7530 30000 10.000 3000.0 3000.0 3000.0 0001 1 0.333 mV 0.1 0.1 0.1 0000 0 0 0 0 0 FFFF -1 -0.333 mV – – -0.1 F448 -3000 -1.000 – – – 8080 -32640 < -1.000 – – < -273.2 In the resistance measurement mode 0 Ω 3 kΩ is limited to 3000.0 Ω. 8360_en_00 PHOENIX CONTACT 13 / 19 IB IL AI/TEMP 4 RTD-XC-PAC 12.2 IB ST format The measured value is represented in bits 14 to 3. The remaining 4 bits are sign and error bits. Measured value representation in IB ST format, 12 bits MSB 15 14 13 12 11 10 9 8 7 6 5 4 3 SB Analog value SB 0 OC OR LSB 2 1 0 0 OC OR Sign bit Reserved Open circuit/short circuit Overrange Typical analog values Sensor type Sensor/code Resolution (bits 10 and 9) Process data item (= analog value) hex dec 7FF9 32761 7FF8 32760 4000 16384 2710 10000 0008 8 0002 2 0001 1 0000 0 FFF8 -8 FC18 -1000 F333 -3277 8001 -32767 1 Voltage 0 – [V] 9.999 5.000 3.052 2.441 mV 0.000 -2.441 mV -0.305 -1.000 Resistance 1 00bin [Ω] Potentiometer 2 01bin [%] Value is outside the valid range 3276.0 3276.01 1638.4 1638.4 1000.0 1000.0 0.8 0.8 Open circuit Value is outside the valid range 0.0 0.0 Value is outside the valid range Temperature 3 ... 12 01bin/11bin [°C]/[°F] 3276.0 1638.4 1000.0 0.8 0.0 -0.8 -100.0 - In the resistance measurement mode 0 Ω 3 kΩ is limited to 3000.0 Ω. If the measured value is outside the representation area of the process data, bit 0 is set to 1. In the event of an open/short circuit, bit 1 is set to 1. 8360_en_00 PHOENIX CONTACT 14 / 19 IB IL AI/TEMP 4 RTD-XC-PAC 12.3 S7-compatible format The measured value is represented in bits 14 to 0. An additional bit (bit 15) is available as a sign bit. Measured value representation in S7-compatible format; 15 bits Overrange or underrange are indicated with the values 7FFFhex or 8000hex. MSB 15 14 13 12 11 10 9 8 7 6 5 SB Analog value SB 4 3 2 1 LSB 0 Sign bit Typical analog values Sensor type Sensor/code Resolution (bits 10 and 9) Process data item (= analog value) Hex Dec 7FFF 32767 6C00 27648 2710 10000 03E8 1000 0001 1 0000 0 FFFF -1 FC18 -1000 F535 -2764 8000 32768 8360_en_00 Voltage 0 – [V] Resistance 1 00bin [Ω] 10.000 3.617 0.362 3.617 mV 0.000 -3.617 mV -0.362 -1.000 2764.8 1000.0 100.0 0.1 0.0 - Potentiometer 2 01bin [%] Temperature 3 ... 12 01bin/11bin [°C]/[°F] Overrange 2764.8 1000.0 100.0 0.1 0.0 - 2764.8 1000.0 100.0 0.1 0.0 -0.1 -100.0 - Underrange PHOENIX CONTACT 15 / 19 IB IL AI/TEMP 4 RTD-XC-PAC 12.4 Standardized representation format The measured value is represented in bits 14 to 0. An additional bit (bit 15) is available as a sign bit. codes in the in formats IB IL and standardized representation” on page 16). The data is standardized with regard to measuring range and resolution and does not need to be converted. The setting of the resolution is 1 Ω for resistance measurements and 1°C for temperature measurements. It has no influence on voltage measurements. Measured value representation in S7-compatible format, 15 bits This format supports extended diagnostics. Values >8000hex and 10.837 10.000 0.001 0.000 -1.000
2701165 价格&库存

很抱歉,暂时无法提供与“2701165”相匹配的价格&库存,您可以联系我们找货

免费人工找货