IB IL AI/TEMP 4 RTD-XC-PAC
Inline analog input terminal,
version for extreme conditions,
4 inputs, 2-wire connection method
Data sheet
8360_en_00
1
© PHOENIX CONTACT 2016-01-25
Function description
The terminal is designed for use within an Inline station. The
terminal has four inputs that may be configured
independently of each other and either for measuring
voltages or resistances or for RTDs.
The sensors are connected using the 2-wire connection
method, so that a nominal resistance of at least 1000 Ω is
recommended when sensors with a relatively small
temperature coefficient (e.g., platinum sensors) are used.
Features
–
–
The resistance measurement with conversion into
temperature values can be used for the temperature
measurement with NTC resistors. The advantage of these
resistors is a large temperature coefficient.
Thanks to special engineering measures and tests, the
terminal can be used under extreme ambient conditions.
–
–
–
–
–
–
–
Four measuring inputs that can be configured as
– Voltage inputs 0 V ... 10 V
– Inputs for resistance measurements up to 300 kΩ
with output either in ohms or percent
(potentiometer measurement)
– Input for temperature measurements
The terminal supports
– Platinum sensors according to DIN EN 60751/
IEC 60751 and the SAMA guideline
– Nickel sensors according to DIN 43760 and the
SAMA guideline
– KTY81-110, KTY81-210, KTY84 sensors
– Viessmann Ni 500, Viessmann NTC10 k sensors
– Siemens LG-Ni 1000 sensor
Connection of sensors in 2-wire technology
Communication via process data
Channels are configured independently of one another
using the bus system.
Diagnostic indicators
Can be used under extreme ambient conditions
Painted PCBs
Extended temperature range of -40°C … +70°C
(see “Tested successfully: Use under extreme ambient
conditions” on page 5)
This data sheet is only valid in association with the IL SYS INST UM E user manual.
Make sure you always use the latest documentation.
It can be downloaded at phoenixcontact.net/products.
IB IL AI/TEMP 4 RTD-XC-PAC
Table of contents
1
Function description ................................................................................................................... 1
2
Ordering data.............................................................................................................................. 3
3
Technical data ............................................................................................................................ 3
4
Tested successfully: Use under extreme ambient conditions ..................................................... 5
5
Internal circuit diagram................................................................................................................ 6
6
Local diagnostic indicator ........................................................................................................... 7
7
Terminal point assignment .................................................................................................................................. 7
8
Installation instructions ............................................................................................................... 8
9
Connection notes ............................................................................................................................................... 8
10 Connection examples ................................................................................................................. 8
11 Process data............................................................................................................................... 9
11.1
11.2
Process data output words OUT .................................................................................................................... 9
Process data input words IN......................................................................................................................... 12
12 Formats for representing measured values................................................................................13
12.1
12.2
12.3
12.4
IB IL format (default setting) ......................................................................................................................... 13
IB ST format ................................................................................................................................................. 14
S7-compatible format ................................................................................................................................... 15
Standardized representation format ............................................................................................................. 16
13 Diagnostic codes in the in formats IB IL and standardized representation .................................16
14 Selecting measuring ranges and sensors ..................................................................................17
14.1
14.2
8360_en_00
Systematic errors ......................................................................................................................................... 17
Tolerance and drift ....................................................................................................................................... 17
PHOENIX CONTACT
2 / 19
IB IL AI/TEMP 4 RTD-XC-PAC
2
Ordering data
Terminal blocks
Description
Type
Order No.
Pcs. / Pkt.
IB IL AI/TEMP 4 RTD-XC-PAC
2701165
1
Accessories
Description
Type
Order No.
Pcs. / Pkt.
Connector as replacement item
IB IL SCN-12-OCP
2727624
10
Documentation
Description
Type
Order No.
Pcs. / Pkt.
“Automation terminals of the Inline product range” user manual
IL SYS INST UM E
2698724
1
Inline analog input terminal, version for extreme conditions,
complete with accessories (connector and labeling field), 4 inputs, 0-10 V,
resistance temperature detector (RTD), 2-wire connection technology
3
Technical data
Dimensions (nominal sizes in mm)
140,5
71,5
119,8
Housing dimensions (width x height x depth)
12.2 x 140.5 x 71.5 mm
General data
Color
Green
Weight
68 g (with connector)
Operating mode
Process data mode with 2 words
Connection method for sensors
2-wire technology
Ambient temperature (operation)
-25°C ... +55°C (Standard)
-40 °C ... +70°C (Extended, see also the “Tested successfully: Use under
extreme ambient conditions” section of the data sheet).
Ambient temperature (storage/transport)
-40 °C ... +85°C
Permissible humidity (operation/storage/transport)
10% ... 95%, according to DIN EN 61131-2
Permissible air pressure (operation/storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection
IP20
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
8360_en_00
PHOENIX CONTACT
3 / 19
IB IL AI/TEMP 4 RTD-XC-PAC
Connection data
Designation
Inline connector
Connection method
Spring-cage connection
Conductor cross section, solid/stranded
0.08 mm2 ... 1.5 mm2
Conductor cross section [AWG]
28 ... 16
Inline local bus interface
Connection method
Inline data jumper
Transmission speed
500 kbps
Power consumption
Communications power UL
7.5 V
Current consumption from UL
≤ 60 mA (typical)
≤ 0.45 W (typical)
Total power consumption
Supply of the module electronics and I/O through bus coupler/power terminal
Connection method
Potential routing
Analog inputs
Number
4
Connection of signals
2-wire, shielded sensor cable
Sensor types that can be used
Pt, Ni, KTY, voltage 0 V ... 10 V
Standards for characteristic curves
According to DIN EN 60751: 07/1996/
according to SAMA RC 21-4-1966
Conversion time of the A/D converter
150 ms
Process data update time of all four channels
600 ms
Protective equipment
None
Electrical isolation
The terminal is only supplied with power from the logic circuit (communications power UL = 7.5 V). All four analog inputs refer to one potential that is electrically
isolated from all other circuits (UL, main circuit UM, segment circuit US, analog circuit UANA). FE (functional earth ground) is a separate potential area that is
connected with shield and analog ground via a coupling network consisting of a 1 MΩ resistor and a 1 nF capacitor connected in parallel.
Separate potentials in the IB IL AI/TEMP 4 RTD-XC-PAC terminal
Test distance
Test voltage
Analog inputs / UL, UM, US, UANA
500 V AC, 50 Hz, 1 min
Error messages to the higher-level control or computer system
None
Error messages via process data
Peripheral fault/user error
Yes (see page 16)
Mechanical requirements
Vibration, IEC 60068-2-6; EN 60068-2-6
5g
Shock, IEC 60068-2-27; EN 60068-2-27
30g
8360_en_00
PHOENIX CONTACT
4 / 19
IB IL AI/TEMP 4 RTD-XC-PAC
Programming data
Local bus (INTERBUS)
ID code
5Fhex (95dec)
Length code
02hex
Input address area
2 words
Output address area
2 words
Parameter channel (PCP)
0 bytes
Register length (bus)
2 words
For the programming data/configuration data of other bus systems, please refer to the corresponding electronic device data sheet (e.g., GSD,
EDS).
Approvals
For the latest approvals, please visit www.phoenixcontact.net/catalog.
4
Tested successfully: Use under extreme ambient conditions
XC terminals have been tested successfully over
250 temperature change cycles in accordance with
IEC 61131-2 in the range from -40°C to +70°C.
The following conditions were observed:
– The Inline devices for all connecting cables were
connected with a minimum conductor cross section of
0.5 mm²
– The Inline station was installed on a wall-mounted
horizontal DIN rail
– Fans were used to ensure continuous movement of air
in the control cabinet
– The Inline station was not exposed to vibration or shock
– The Inline station was operated with a maximum of
24.5 V (ensured by using regulated power supply units)
3 h + 30 min
t1
Tmax + 2 K
(3 + 0,6) K/min
Tmin + 3 K
3 h + 30 min
t1
1
Figure 1
Temperature change cycle
Temperature in the control cabinet/ambient
temperature
Cycle
WARNING:
The terminal is not approved for use in potentially
explosive areas.
The terminal is not approved for use in safety
technology.
8360_en_00
PHOENIX CONTACT
5 / 19
IB IL AI/TEMP 4 RTD-XC-PAC
5
Internal circuit diagram
OPC
Local bus
OPC
Protocol chip
µC
UL+
UANA
UL-
Microcontroller with multiplexer and analog-digital converter
MUX
UL
3.3V
UL
3.3V
Coupling network
µC
Analog ground
EEPROM
MUX
DC/DC converter with electrical isolation
REF
Optocoupler
REF
EEPROM
+24V US
Voltage reference
Non-volatile memory
+24V UM
Figure 2
Internal circuit diagram
Other symbols used are explained in the
IL SYS INST UM E user manual.
8360_en_00
PHOENIX CONTACT
6 / 19
IB IL AI/TEMP 4 RTD-XC-PAC
6
Local diagnostic indicator
7
Terminal point assignment
D
1.1
Figure 3
Des.
D
Local diagnostic indicator
Color Meaning
Green Diagnostics
Function identification
1.1 2.1
2.1
1.2
1.2 2.2
1.3
1.3 2.3
2.3
1.4
1.4 2.4
2.4
1.5
1.5 2.5
2.5
1.6
1.6 2.6
2.6
2.2
Green
Figure 4
Terminal point assignment
2-wire connection
Terminal
points
1.1
Signal
Assignment
+AI1
1.2
1.3
1.4
AGND*
Shield*
+AI2
1.5
1.6
2.1
AGND*
Shield*
+AI3
2.2
2.3
2.4
AGND*
Shield*
+AI4
2.5
2.6
AGND*
Shield*
Resistance/voltage input of
channel 1
Sensor ground of channel 1
Shield connection of channel 1
Resistance/voltage input of
channel 3
Sensor ground of channel 3
Shield connection of channel 3
Resistance/voltage input of
channel 2
Sensor ground of channel 2
Shield connection of channel 2
Resistance/voltage input of
channel 4
Sensor ground of channel 4
Shield connection of channel 4
*
8360_en_00
AGND and shield are connected internally.
PHOENIX CONTACT
7 / 19
IB IL AI/TEMP 4 RTD-XC-PAC
8
Installation instructions
High current flowing through potential jumpers UM and US
leads to a temperature rise in the potential jumpers and
inside the terminal. To keep the current flowing through the
potential jumpers of the analog terminals as low as possible,
always place the analog terminals after all the other
terminals at the end of the main circuit (for the sequence of
the Inline terminals, see also IL SYS INST UM E user
manual).
9
Connection notes
Always connect the analog sensors using
shielded, twisted pair cables.
A shield may reduce the influence of
electromagnetic interference. Connect the shield
at one end with the shield connection of the
terminal and insulate it at the sensor.
Connect unused sensor inputs with sensor
ground.
Connect the shield externally in areas with strong
EMI, and insulate it at the device and the sensor
10
Connection examples
D
D
AI/TEMP 4
RTD
AI/TEMP 4
RTD
1.1 2.1
1.1 2.1
+AI 2
+AI1
OUT1
+AI 2
+AI1
1.2 2.2
AGND
AGND
AGND
1.3 2.3
Shield
Shield
Shield
OUT3
+AI4
+AI3
1.5 2.5
Figure 5
8360_en_00
OUT4
1.5 2.5
AGND
AGND
Shield
Shield
1.6 2.6
Shield
Shield
1.4 2.4
+AI4
AGND
AGND
1.3 2.3
1.4 2.4
+AI3
OUT2
1.2 2.2
AGND
1.6 2.6
Shield
Examples for connecting RTDs and sensors for voltage measurement
PHOENIX CONTACT
8 / 19
IB IL AI/TEMP 4 RTD-XC-PAC
11
Process data
11.1
Process data output words OUT
Two process data output words are available.
If you change the configuration, the message "Measured
value invalid" appears (diagnostic code 8004hex), until new
measured values are available.
Configure the terminal channels via the process data output
words OUT1 and OUT2. In this context, the output word
OUT1 contains the command and output word OUT2
contains the parameters belonging to this command.
Please note that extended diagnostics is only
possible if the IB IL format or standardized
representation are configured as the format for
representing the measured values. As the IB IL
format is preset on the terminal, it is available
immediately after the voltage has been applied.
The configuration settings are stored in a volatile memory.
11.1.1 Output word OUT1 (control word)
OUT1
Bit
15
14
13
12
11
10
Command code
Assignment
9
8
7
6
5
4
3
2
1
0
0
0
0
0
0
0
0
0
Bit 15 to bit 8 (command code):
0
0
0
0
0
0
0
1
Bit 15 to bit 8
0
0
0
0
0
1
0
0
1
1
1
1
0
0
0
0
C
C
0
C
OUT1
C 0x00hex
C 1x00hex
0 3C00hex
C 4x00hex
0
1
0
1
0
0
C
C 5x00hex
1
0
0
1
0
0
C
C 9x00hex
Command function
Read measured value in IN2 channel-by-channel.
Read configuration in IN2 channel-by-channel.
Read firmware version and module ID in IN2.
Configure channel, configuration in OUT2.
Configure channel and read measured value of the channel,
configuration in OUT2, measured value in IN2.
Read and write R0 value of the channel.
CC = Channel number
Bit 9 and bit 8: Channel number
Code
dec
bin
0
00
1
01
2
10
3
11
8360_en_00
Channel number
Channel 1
Channel 2
Channel 3
Channel 4
PHOENIX CONTACT
9 / 19
IB IL AI/TEMP 4 RTD-XC-PAC
11.1.2 Output word OUT2 (parameter word)
The parameters for the commands 4x00hex, 5x00hex, and
9x00hex must be specified in OUT2. This parameter word is
only evaluated for these commands.
The parameter word is only evaluated when the
control word contains a valid command code.
Reserved parameters may not be used.
Commands 4x00hex, 5x00hex:
OUT2
Bit
15
14
13
R0
Assignment
12
11
Filter
10
9
Resolution
8
7
6
Format
5
4
3
Sensor type
2
1
0
Measurement
mode
Command 9x00hex:
OUT2
Bit
15
14
13
12
11
10
9
Selection of formats for
the representation of
measured values
Sensor type setting
5
4
3
2
1
0
Short
designation
R0
Default
1000 Ω
Resolution
Quantization of the measured value, select between
°Celsius or °Fahrenheit.
Filter
No mean value
Resolution
0.1 Ω/0.01%/0.01
K
IB IL format
Format
Sensor
0 V ... 10 V
type
Setting the measurement MeasureVoltage
mode
ment mode measurement 0 V
... 10 V
R0
Selecting the resistance of the sensor at 0°C;
The configurable nominal resistance R0 is taken for the
temperature calculation based on nickel and platinum
sensors. Should the desired resistance not be found in the
code table, the nominal resistance of 1 Ω to 65535 Ω can be
configured with increments of 1 Ω. To do this, use the
command 9x00hex with the R0 value in the OUT2 process
data word.
Filter
Selection of mean value generation.
After every conversion, the measured value is saved in a
mean value memory via which the mean value is generated.
The memory size can be selected with the filter option. E.g.,
8360_en_00
6
for a 16-sample mean value, the mean value is generated
using the last 16 measured values.
The following configurations are possible:
Value of reference
resistance R0
Selection of mean value
generation (filtering)
Resolution settings
7
R0 value, 1 Ω increments
Assignment
Configuration
8
The resolution for voltage measurements
depends only on the transmission format.
Format
Representation of the measured value in the IN process
data
Sensor type
Sensor type setting;
The configurable sensor type determines the conversion of
the electrical signal present at the input into a physical size.
Sensor type and measurement mode must be set for a
sensor to be connected to receive a measuring result with a
suitable accuracy. If, for instance, a Pt 1000 sensor is to be
connected, a resistance measurement for the range from
0 Ω ... 3 kΩ can be used as a measurement mode. Also, a
resistance measurement would be possible for the range
from 0 Ω ... 300 kΩ, however, this measurement mode
provides a considerably lower accuracy in the resistance
range relevant for Pt 1000.
Measurement mode
Setting the selected measurement mode;
The measuring mode determines the signal conditioning by
the configurable inputs. Every input can be configured for
voltage or resistance measurement as desired. For the
resistance measurement, an auxiliary current that
generates a voltage drop over the resistance to be
measured is generated. The current supply is deactivated
for the voltage measurement.
PHOENIX CONTACT
10 / 19
IB IL AI/TEMP 4 RTD-XC-PAC
11.1.3 Parameters for configuration
The values in bold are default settings.
Bit 15 to bit 13
dec
0
1
2
3
4
5
6
7
Code
bin
000
001
010
011
100
101
110
111
Bit 6 to bit 3:
Nominal resistance R0 [Ω]
hex
0
1
2
3
4
5
6
7
1000
100
500
2000
5000
10000
Reserved
20000 (can be set)
Bit 12 and bit 11
Code
dec
bin
0
00
1
01
2
10
3
11
Filter
No mean value
8-sample mean value
32-sample mean value
Reserved
Bit 10 and bit 9
Code
dec
bin
0
1
2
3
00
01
10
11
Resolution for sensor type
1
2
3 ... 12
(Resistance (Potentio(Tempe[Ω])
meter [%]) rature)
0.1
0.01
0.01°C
1
0.1
0.1°C
10
1
0.01°F
Reserved
0.1°F
Bit 8 and bit 7
Code
dec
bin
0
00
1
01
2
3
10
11
8360_en_00
Format
Code
dec
bin
0
0000
1
0001
2
0010
3
0011
4
0100
5
0101
6
0110
7
0111
8
1000
9
1001
10 1010
11 1011
12 1100
13 1101
14 1110
15 1111
Sensor type
0 V ... 10 V
Resistor
Potentiometer [%]
Pt DIN
Pt SAMA
Ni DIN
Ni SAMA
KTY 81-110
KTY 81-210
KTY 84
Ni 1000 (Siemens LG)
Ni 500 (Viessmann)
NTC 10 k (Viessmann)
Reserved
Reserved
Not configured
Bit 2 to bit 0:
Code
dec
bin
0
000
1
001
2
010
3
011
4
100
5
101
6
110
7
111
Measurement mode
Voltage measurement 0 V ... 10 V
Reserved
Reserved
Resistance measurement 0 Ω ... 3 kΩ
Resistance measurement 0 Ω ... 300 kΩ
Reserved
Reserved
Not configured
IB IL (15 bits + sign bit with extended
diagnostics)
IB ST
(12 bits + sign bit + 3 diagnostic bits)
S7-compatible (15 bits + sign bit)
Standardized representation (15 bits + sign
bit with extended diagnostics)
PHOENIX CONTACT
11 / 19
IB IL AI/TEMP 4 RTD-XC-PAC
11.2
Process data input words IN
11.2.1 Input word IN1 (status word)
The IN1 word is a copy of the OUT1 process data word.
IN1
Bit
15
14
13
12
11
10
9
8
Mirroring of the command code
Assignment
7
6
5
4
3
2
1
0
0
0
0
0
0
0
0
0
Mirroring of the command code:
A command code mirrored from the control word.
11.2.2 Input word IN2
The measured values, the configuration or the firmware
version are transmitted to the controller board or the PC via
the process data input word IN2 according to the
configuration.
For control word 3C00hex, IN2 provides the firmware version
and the module ID.
Example: Firmware version 1.23:
Bit
Assignment (hex)
Meaning
IN2
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
1
2
3
Ehex
Firmware version 1.23
Module
ID
For control word 9x00hex, IN2 provides the configuration
and R0.
MSB
15 14 13 12 11 10 9 8 7 6 5
Configuration / R0
8360_en_00
4
3
2
LSB
1 0
Basically four formats are available for the representation of
the measured values. For more detailed information on the
formats, please refer to “Formats for representing measured
values” on page 13.
IB IL, S7-compatible, standardized representation
formats
MSB
15 14 13 12 11 10 9 8 7 6 5
SB
Analog value
4
3
2
4
3
2
1
LSB
0
IB ST format
MSB
15 14 13 12 11 10 9
SB
MSB
LSB
SB
0
OC
OR
8
7
Analog value
6
5
LSB
1 0
O O
0
C R
Most significant bit
Least significant bit
Sign bit
Reserved
Open circuit
Overrange
PHOENIX CONTACT
12 / 19
IB IL AI/TEMP 4 RTD-XC-PAC
12
Formats for representing measured values
12.1
IB IL format (default setting)
The measured value is represented in bits 14 to 0. An
additional bit (bit 15) is available as a sign bit. This format
supports extended diagnostics. Values >8000hex and
10.837
> 3251.21
> 3251.2
> 3251.2
7F00
32512
10.837
3251.21
3251.2
3251.2
7530
30000
10.000
3000.0
3000.0
3000.0
0001
1
0.333 mV
0.1
0.1
0.1
0000
0
0
0
0
0
FFFF
-1
-0.333 mV
–
–
-0.1
F448
-3000
-1.000
–
–
–
8080
-32640
< -1.000
–
–
< -273.2
In the resistance measurement mode 0 Ω 3 kΩ is limited to 3000.0 Ω.
8360_en_00
PHOENIX CONTACT
13 / 19
IB IL AI/TEMP 4 RTD-XC-PAC
12.2
IB ST format
The measured value is represented in bits 14 to 3. The
remaining 4 bits are sign and error bits.
Measured value representation in IB ST format, 12 bits
MSB
15 14 13 12 11 10 9 8 7 6 5 4 3
SB
Analog value
SB
0
OC
OR
LSB
2 1 0
0 OC OR
Sign bit
Reserved
Open circuit/short circuit
Overrange
Typical analog values
Sensor type
Sensor/code
Resolution (bits 10 and 9)
Process data item (= analog value)
hex
dec
7FF9
32761
7FF8
32760
4000
16384
2710
10000
0008
8
0002
2
0001
1
0000
0
FFF8
-8
FC18
-1000
F333
-3277
8001
-32767
1
Voltage
0
–
[V]
9.999
5.000
3.052
2.441 mV
0.000
-2.441 mV
-0.305
-1.000
Resistance
1
00bin
[Ω]
Potentiometer
2
01bin
[%]
Value is outside the valid range
3276.0
3276.01
1638.4
1638.4
1000.0
1000.0
0.8
0.8
Open circuit
Value is outside the valid range
0.0
0.0
Value is outside the valid range
Temperature
3 ... 12
01bin/11bin
[°C]/[°F]
3276.0
1638.4
1000.0
0.8
0.0
-0.8
-100.0
-
In the resistance measurement mode 0 Ω 3 kΩ is limited to 3000.0 Ω.
If the measured value is outside the
representation area of the process data, bit 0 is
set to 1.
In the event of an open/short circuit, bit 1 is set to
1.
8360_en_00
PHOENIX CONTACT
14 / 19
IB IL AI/TEMP 4 RTD-XC-PAC
12.3
S7-compatible format
The measured value is represented in bits 14 to 0. An
additional bit (bit 15) is available as a sign bit.
Measured value representation in S7-compatible format;
15 bits
Overrange or underrange are indicated with the values
7FFFhex or 8000hex.
MSB
15 14 13 12 11 10 9 8 7 6 5
SB
Analog value
SB
4
3
2
1
LSB
0
Sign bit
Typical analog values
Sensor type
Sensor/code
Resolution (bits 10 and 9)
Process data item (= analog value)
Hex
Dec
7FFF
32767
6C00
27648
2710
10000
03E8
1000
0001
1
0000
0
FFFF
-1
FC18
-1000
F535
-2764
8000
32768
8360_en_00
Voltage
0
–
[V]
Resistance
1
00bin
[Ω]
10.000
3.617
0.362
3.617 mV
0.000
-3.617 mV
-0.362
-1.000
2764.8
1000.0
100.0
0.1
0.0
-
Potentiometer
2
01bin
[%]
Temperature
3 ... 12
01bin/11bin
[°C]/[°F]
Overrange
2764.8
1000.0
100.0
0.1
0.0
-
2764.8
1000.0
100.0
0.1
0.0
-0.1
-100.0
-
Underrange
PHOENIX CONTACT
15 / 19
IB IL AI/TEMP 4 RTD-XC-PAC
12.4
Standardized representation format
The measured value is represented in bits 14 to 0. An
additional bit (bit 15) is available as a sign bit.
codes in the in formats IB IL and standardized
representation” on page 16).
The data is standardized with regard to measuring range
and resolution and does not need to be converted. The
setting of the resolution is 1 Ω for resistance measurements
and 1°C for temperature measurements. It has no influence
on voltage measurements.
Measured value representation in S7-compatible format,
15 bits
This format supports extended diagnostics. Values
>8000hex and 10.837
10.000
0.001
0.000
-1.000