IB IL 24 DI8/HD-XC-PAC
Inline digital input terminal,
version for extreme conditions,
8 inputs, 24 V DC
Data sheet
8461_en_00
1
© PHOENIX CONTACT 2012-05-29
Description
The terminal block has been developed for use in an Inline
station. It is used to acquire digital signals.
Thanks to special engineering measures and tests, the terminal can be used under extreme ambient conditions.
Features
–
–
–
–
–
–
Connections for eight digital sensors
Connection of sensors in 1-wire technology
Diagnostic and status indicators
Can be used under extreme ambient conditions
Painted PCBs
Extended temperature range T2 (-40°C +55°C)
This data sheet is only valid in association with the IL SYS INST UM E user manual.
Make sure you always use the latest documentation.
It can be downloaded from the product at www.phoenixcontact.net/catalog.
IB IL 24 DI8/HD-XC-PAC
2
Table of contents
1
Description .............................................................................................................................. 1
2
Table of contents ..................................................................................................................... 2
3
Ordering data .......................................................................................................................... 3
4
Technical data ......................................................................................................................... 3
5
Additional tables ...................................................................................................................... 5
6
Tested successfully: Use under extreme ambient conditions .................................................. 6
7
Internal circuit diagram ............................................................................................................ 6
8
Local status and diagnostic indicators ..................................................................................... 7
9
Terminal point assignment....................................................................................................... 7
10
Connection notes and examples ............................................................................................. 7
11
Process data............................................................................................................................ 7
8461_en_00
PHOENIX CONTACT
2
IB IL 24 DI8/HD-XC-PAC
3
Ordering data
Description
Type
Order No.
Pcs. / Pkt.
Inline digital input terminal, version for extreme conditions, complete with
accessories (connector plug and labeling field), 8 inputs, 24 V DC, 1-wire
connection technology
IB IL 24 DI8/HD-XC-PAC
2701212
1
Accessories
Type
Order No.
Pcs. / Pkt.
Connector, for digital 1, 2 or 8-channel Inline terminals ( Plug/Adapter )
IB IL SCN-8
2726337
10
Labeling field, width: 12.2 mm ( Marking )
IB IL FIELD 2
2727501
10
Documentation
Type
Order No.
Pcs. / Pkt.
User manual, English, Automation terminals of the Inline product range
IL SYS INST UM E
-
-
Data sheet, English,
INTERBUS addressing
DB GB IBS SYS ADDRESS
-
-
4
Technical data
Dimensions (nominal sizes in mm)
140,5
71,5
119,8
Width
12.2 mm
Height
119.8 mm
Depth
71.5 mm
Note on dimensions
Housing dimensions
General data
Color
green
Weight
60 g ( With connector )
Operating mode
Process data mode with one byte
Ambient temperature (operation)
-40 °C ... 55 °C (See also the "Tested successfully: Use under extreme ambient
conditions" section of the data sheet.)
Ambient temperature (operation)
-40 °C ... 60 °C (At US < 24.5 V; see also the "Tested successfully: Use under extreme ambient conditions" section of the data sheet.)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Temperature class
T2 (-40°C ... 55°C, EN 50155)
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
8461_en_00
PHOENIX CONTACT
3
IB IL 24 DI8/HD-XC-PAC
General data
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection
IP20
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Connection data
Name
Inline connectors
Connection method
Spring-cage connection
Conductor cross section solid / stranded
0.08 mm² ... 1.5 mm²
Conductor cross section [AWG]
28 ... 16
Interface Inline local bus
Connection method
Inline data jumper
Transmission speed
500 kBit/s
Power consumption
Segment supply voltage US
24 V DC (nominal value)
Current consumption from US
max. 5.5 mA DC
Communications power UL
7.5 V DC
Current consumption from UL
max. 30 mA DC
Power loss
max. 0.72 W
Digital inputs
Number of inputs
8
Connection method
Spring-cage connection
Connection method
1-wire
Description of the input
EN 61131-2 types 1 and 3
Nominal input voltage
24 V DC
Nominal input current
Typ. 2.4 mA
Input voltage range "0" signal
-3 V DC ... 5 V DC
Input voltage range "1" signal
11 V DC ... 30 V DC
Delay at signal change from 0 to 1
1 ms
Delay at signal change from 1 to 0
1 ms
Permissible conductor length to the sensor
30 m
Programming Data
ID code (hex)
BE
ID code (dec.)
190
Length code (hex)
81
Length code (dec.)
129
Process data channel
8 Bit
Input address area
1 Byte
Output address area
0 Byte
Parameter channel (PCP)
0 Byte
Register length (bus)
8 Bit
For the programming data/configuration data of other bus systems, please refer to the corresponding electronic device data sheet (e.g., GSD,
EDS).
PROFIBUS telegram data
Required parameter data
1 Byte
Need for configuration data
4 Byte
8461_en_00
PHOENIX CONTACT
4
IB IL 24 DI8/HD-XC-PAC
Error messages to the higher level control or computer system
None
Electrical isolation/isolation of the voltage areas
5 V supply, incoming remote bus/7.5 V supply (bus logics)
500 V AC , 50 Hz , 1 min
5 V supply, outgoing remote bus/7.5 V supply (bus logics)
500 V AC , 50 Hz , 1 min
7.5 V supply (bus logics)/24 V supply (I/O)
500 V AC , 50 Hz , 1 min
24 V supply (I/O) / functional earth ground
500 V AC , 50 Hz , 1 min
To achieve electrical isolation between the logic level and the I/O area, supply these areas from separate power supply units. Interconnection
of the power supply units in the 24 V area is not permitted (see also user manual).
Approvals
For the latest approvals, please visit www.phoenixcontact.net/catalog.
5
Additional tables
Input characteristic curve
Input voltage U [V]
Typical input current
I [mA]
-30 < U ≤ 0.7
0
3
0.12
6
1.32
9
2.32
12
2.36
15
2.36
18
2.36
21
2.36
24
2.40
27
2.40
30
2.40
8461_en_00
PHOENIX CONTACT
5
IB IL 24 DI8/HD-XC-PAC
6
Tested successfully: Use under extreme ambient conditions
7
Internal circuit diagram
The terminal has been tested successfully over 250 temperature change cycles in accordance with IEC 61131-2 in the
range from -40°C to +70°C.
Local bus
The following conditions were observed:
– The Inline devices for all connecting cables were connected with a minimum conductor cross section of
0.5 mm²
– The Inline station was assembled on a wall-mounted horizontal DIN rail
– Fans were used to ensure continuous movement of air in
the control cabinet
– The Inline station was not exposed to vibration or shock
– The Inline station was operated with a maximum of
24.5 V (ensured by using regulated power supply units)
OPC
UL
8
4x
16 8
4x
3 h + 30 min
t1
Tmax + 2 K
+24 V (US)
+24 V (UM)
(3 + 0,6) K/min
Tmin + 3 K
3 h + 30 min
t1
1
Figure 1
Figure 2
Internal wiring of the terminal points
Temperature change cycle
Temperature in the control cabinet/ambient
temperature
OPC
Protocol chip
(Bus logic including voltage conditioning)
LED (status indicator)
Cycle
Optocoupler
WARNING:
Digital input
The terminal is not approved for use in potentially explosive areas.
The terminal is not approved for use in safety
technology.
8461_en_00
Explanation for other used symbols has been
provided in the IL SYS INST UM E user manual.
PHOENIX CONTACT
6
IB IL 24 DI8/HD-XC-PAC
8
Local status and diagnostic indicators
10
Connection notes and examples
NOTE: Malfunction
Make sure that the supply voltage US is available, as it is used internally as the auxiliary voltage.
D
1
3
5
7
2
4
6
8
Figure 3
When connecting the sensors observe the assignment of the terminal points to the process
data.
Local status and diagnostic indicators
NOTE: Malfunction
Designation
D
1 to 8
Color
Meaning
The sensors and US must be supplied from the
same voltage supply.
Green
Yellow
Diagnostics (bus and logic voltage)
Status of the inputs
If you connect the sensors via external busbars, make sure
that the sensors and US are supplied by the same power supply.
Function identification
Light blue
9
Terminal point assignment
1.1
2.1
1.2
2.2
1.3
2.3
1.4
2.4
IN2
IN1
+24 V
1.1
1.1 2.1
2.1
1.2
1.2 2.2
2.2
1.3
1.3 2.3
2.3
1.4
1.4 2.4
2.4
+24 V
IN7
+24 V
IN8
+24 V
+24 V
Figure 5
11
Example of a connection of sensors when using
external busbars
Process data
Assignment of the terminal points to IN process data
Figure 4
Terminal point assignment
Terminal point
1.1 / 2.1
1.2 / 2.2
1.3 / 2.3
1.4 / 2.4
Assignment
Signal input (IN 1 / IN 2)
Signal input (IN 3 / IN 4)
Signal input (IN 5 / IN 6)
Signal input (IN 7 / IN 8)
(Byte.Bit) Byte
view
Bit
AssignTermiment
nal point
(signal)
Status in- LED
dicator
Byte 0
7
6
5
4
3
2
1
0
2.4 1.4 2.3 1.3 2.2 1.2 2.1 1.1
8
7
6
5
4
3
2
1
For the assignment of the illustrated (byte.bit)
view to your INTERBUS control or computer
system, please refer to the
DB GB IBS SYS ADDRESS data sheet.
8461_en_00
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
www.phoenixcontact.com
7
很抱歉,暂时无法提供与“2701212”相匹配的价格&库存,您可以联系我们找货
免费人工找货