https://www.phoenixcontact.com/us/products/2701216
Inline function terminal - IB IL TEMP 2 UTH-XC-PAC - 2701216
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Inline analog input terminal, extreme conditions version, complete with accessories (connector plug and labeling
field), 2 inputs, TC (thermocouple), 2-conductor connection technology
Product Features
Connection of thermocouples according to DIN EN 60584-1 and DIN 43710
Absolute and differential temperature measurement (configurable)
Measured value acquisition with 16-bit resolution
Internal and external cold junction
-15 mV to +85 mV linear input
Key commercial data
Packing unit
1 pc
Weight per Piece (excluding packing)
100.0 GRM
Custom tariff number
85389091
Country of origin
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
12.2 mm
Height
136.8 mm
Depth
71.5 mm
Ambient conditions
Ambient temperature (operation)
-40 °C ... 55 °C (See also the "Tested successfully: Use under extreme
ambient conditions" section of the data sheet.)
09/03/2014 Page 1 / 4
https://www.phoenixcontact.com/us/products/2701216
Inline function terminal - IB IL TEMP 2 UTH-XC-PAC - 2701216
Technical data
Ambient conditions
Ambient temperature (storage/transport)
-40 °C ... 85 °C
GRP_Temperature class
T2 (-40°C ... 55°C, EN 50155)
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection
IP20
General
Weight
67 g
Note on weight specifications
with connector
Mounting type
DIN rail
Operating mode
Process data operation with 2 words
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Test section
5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz
1 min
5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz
1 min
7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min
7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min
24 V analog supply (analog I/O) / functional earth ground 500 V AC 50 Hz
1 min
24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min
Interfaces
Designation
Inline local bus
Connection method
Inline data jumper
Transmission speed
500 kBit/s
Transmission physics
Copper
Inline potentials
Communications power UL
7.5 V DC (via voltage jumper)
Current consumption from UL
max. 60 mA
typ. 43 mA
I/O supply voltage UANA
24 V DC
Current consumption from UANA
max. 18 mA
typ. 11 mA
Power consumption
typ. 590 mW
Analog inputs
09/03/2014 Page 2 / 4
https://www.phoenixcontact.com/us/products/2701216
Inline function terminal - IB IL TEMP 2 UTH-XC-PAC - 2701216
Technical data
Analog inputs
Number of inputs
2
Input name
Analog UTH inputs
Description of the input
Inputs for thermocouples or linear voltage
Connection method
Spring-cage connection
2-wire (shielded)
Sensor types that can be used (TC)
U, T, L, J, E, K, N, S, R, B, C, W, HK
Measuring principle
Successive approximation
Measured value representation
16 bits two's complement and other
A/D conversion time
< 120 µs (per channel)
Resolution A/D
16 bit
Process data update
30 ms (For both channels)
Classifications
eCl@ss
eCl@ss 4.0
27250303
eCl@ss 4.1
27250303
eCl@ss 5.0
27250303
eCl@ss 5.1
27242601
eCl@ss 6.0
27242601
eCl@ss 7.0
27242601
eCl@ss 8.0
27242601
ETIM
ETIM 3.0
EC001596
ETIM 4.0
EC001599
ETIM 5.0
EC001596
UNSPSC
UNSPSC 6.01
43172015
UNSPSC 7.0901
43201404
UNSPSC 11
43172015
UNSPSC 12.01
43201404
UNSPSC 13.2
43201404
Approvals
Approvals
09/03/2014 Page 3 / 4
https://www.phoenixcontact.com/us/products/2701216
Inline function terminal - IB IL TEMP 2 UTH-XC-PAC - 2701216
Approvals
Approvals
UL Recognized / cUL Recognized / cULus Recognized
Ex Approvals
Approvals submitted
Approval details
UL Recognized
cUL Recognized
cULus Recognized
Drawings
Connection diagram
1.1
Dimensioned drawing
136,8
2.1
119,8
2.2
1.3
2.3
1.4
2.4
71,5
1.2
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com
09/03/2014 Page 4 / 4