https://www.phoenixcontact.com/us/products/2701232
I/O module - AXL F AI8 XC 1F - 2701232
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Axioline F analog input module, extreme conditions version, 8 inputs: 0 - 10 V, ±10 V, 0 - 20 mA, 4 - 20 mA,
±20 mA, 2-conductor connection technology (including bus base module and connectors)
The figure shows the standard item
Product Description
The module is designed for use within an Axioline F station.
It is used to acquire analog voltage and current signals.
Why buy this product
8 analog, bipolar input channels for the connection of either voltage or current signals
Connection of sensors in 2-wire technology
Voltage ranges: 0 V ... 10 V, ±10 V, 0 V ... 5 V, ±5 V
Current ranges: 0 mA ... 20 mA, 4 mA ... 20 mA, ±20 mA
Device rating plate stored
Diagnostic and status indicators
Can be used under extreme ambient conditions
Extended temperature range of -40°C ... +70°C (see “Tested successfully: use under extreme ambient conditions” in the data sheet)
Partially coated PCBs
Key Commercial Data
Packing unit
1 STK
GTIN
GTIN
4046356730495
Weight per Piece (excluding packing)
260.000 g
Custom tariff number
85389091
Country of origin
Germany
04/13/2017 Page 1 / 8
https://www.phoenixcontact.com/us/products/2701232
I/O module - AXL F AI8 XC 1F - 2701232
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
53.6 mm
Height
126.1 mm
Depth
54 mm
Note on dimensions
The depth is valid when a TH 35-7.5 DIN rail is used (according to
EN 60715).
Ambient conditions
Ambient temperature (operation)
-25 °C ... 60 °C (Standard)
-40 °C ... 70 °C (Extended, see section “Tested successfully: use under
extreme ambient conditions” in the data sheet.)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)
5 % ... 95 % (non-condensing)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection
IP20
General
Mounting type
DIN rail
Net weight
204 g
Note on weight specifications
with connectors and bus base module
Interfaces
Designation
Axioline F local bus
Connection method
Bus base module
Transmission speed
100 Mbps
Power supply for module electronics
Connection method
Push-in connection
Note on connection method
Please observe the information provided on conductor cross sections in
the “Axioline F: system and installation” user manual.
Axioline potentials
Communications power UBus
5 V DC (via bus base module)
Current consumption from UBus
typ. 105 mA
max. 130 mA
Supply for analog modules UA
24 V DC
04/13/2017 Page 2 / 8
https://www.phoenixcontact.com/us/products/2701232
I/O module - AXL F AI8 XC 1F - 2701232
Technical data
Axioline potentials
Current consumption from UA
typ. 35 mA
max. 45 mA (IiS = 0 mA)
Analog inputs
Description of the input
Differential inputs, voltage or current can be chosen separately
Input name
Analog inputs
Number of inputs
8
Connection method
Push-in connection
Connection technology
2-wire
Note regarding the connection technology
Shielded, twisted pair
A/D conversion time
2 µs
Resolution A/D
16 bit
Limit frequency (3 dB)
30 Hz
12 kHz (in fast mode)
Type of protection
Transient protection of inputs
Protective circuit/component
Suppressor diode
Data formats
IB IL, S7-compatible
Measured value representation
16 bits (15 bits + sign bit)
Current input signal
0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
Input resistance current input
104 Ω (typical)
Voltage input signal
0 V ... 5 V
-5 V ... 5 V
0 V ... 10 V
-10 V ... 10 V
Input resistance of voltage input
268 kΩ (typical)
Common mode voltage range signal - ground
-50 V DC ... 50 V DC
Filtering
RFI filtering / passive TP 1st order
Input filter
30 Hz, 12 kHz and mean-value generation (can be parameterized)
Electrical isolation
Test section
5 V communications power (logic), 24 V supply (I/O) 500 V AC 50 Hz 1
min.
5 V supply (logic)/functional earth ground 500 V AC 50 Hz 1 min.
24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min.
Standards and Regulations
Mechanical tests
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
04/13/2017 Page 3 / 8
https://www.phoenixcontact.com/us/products/2701232
I/O module - AXL F AI8 XC 1F - 2701232
Technical data
Standards and Regulations
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g
Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Environmental Product Compliance
China RoHS
Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values
Drawings
Connection diagram
Dimensional drawing
53,6
02
03
04
05
06
07
10
11
12
13
14
15
16
17
20
21
22
23
24
25
26
27
30
31
32
33
34
35
36
37
54
I
I
126,1
U
01
122,4
U
00
Connection for voltage and current measurement
Connection diagram
U1+ U2+
Connection diagram
U1+ U2+
U1– U2–
U1– U2–
U
+24 V
I1+
I2+
I1–
I2–
+24 V
P
I1+
I2+
I1–
I2–
GND
I
P
GND
Passive pressure sensor at a differential current input
Differential voltage input with active 3-wire transmitter
04/13/2017 Page 4 / 8
https://www.phoenixcontact.com/us/products/2701232
I/O module - AXL F AI8 XC 1F - 2701232
Block diagram
Supervisor
UBus
8x
!C
Local bus
FE
D
UA
E1
E2
#
U
REF
M
U
X
8:1
UA
24 V
U/I
AI 1...8
Internal wiring of the terminal points
Classifications
eCl@ss
eCl@ss 4.0
27240405
eCl@ss 4.1
27240405
eCl@ss 5.0
27242201
eCl@ss 5.1
27242601
eCl@ss 6.0
27242601
eCl@ss 7.0
27242601
eCl@ss 8.0
27242601
eCl@ss 9.0
27242601
ETIM
ETIM 3.0
EC001599
ETIM 4.0
EC001435
ETIM 5.0
EC001596
ETIM 6.0
EC001596
UNSPSC
UNSPSC 6.01
43172015
UNSPSC 7.0901
43201404
UNSPSC 11
39121311
UNSPSC 12.01
39121311
UNSPSC 13.2
32151602
04/13/2017 Page 5 / 8
https://www.phoenixcontact.com/us/products/2701232
I/O module - AXL F AI8 XC 1F - 2701232
Approvals
Approvals
Approvals
UL Listed / cUL Listed / BSH / LR / NK / BV / DNV GL / PRS / cULus Listed
Ex Approvals
Approval details
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
http://www.bsh.de/de/index.jsp
840
BSH
LR
http://www.lr.org/en
14-20019
NK
http://www.classnk.or.jp/hp/en/
TA16207M
BV
http://www.veristar.com/portal/veristarinfo/generalinfo/
approved/approvedProducts/equipmentAndMaterials
36433/A2 BV
http://exchange.dnv.com/tari/
TAA00000DF
http://www.prs.pl/
TE/2106/880590/16
DNV GL
PRS
04/13/2017 Page 6 / 8
https://www.phoenixcontact.com/us/products/2701232
I/O module - AXL F AI8 XC 1F - 2701232
Approvals
cULus Listed
Accessories
Accessories
Connector set
Connector set - AXL CNS 4L-O/D/UA/E1/E2 - 2700984
Axioline F connector set (for e.g., AXL F AI8 1F, AXL F AO8 1F)
Device marking
Insert label - EMT (35X46)R - 0801604
Insert label, for the Axioline F series from Phoenix Contact, Roll, white, unlabeled, can be labeled with: THERMOMARK
ROLL, THERMOMARK ROLL X1, THERMOMARK ROLLMASTER 300/600, THERMOMARK X1.2, THERMOMARK
S1.1, Mounting type: snapped into marker carrier, Lettering field: 35 x 46 mm
DIN rail connector
Bus connector - AXL F BS F - 2688129
Axioline F bus base module for housing type F
Mounting material
04/13/2017 Page 7 / 8
https://www.phoenixcontact.com/us/products/2701232
I/O module - AXL F AI8 XC 1F - 2701232
Accessories
Shield connection - AXL SHIELD SET - 2700518
Axioline shield connection set (contains 2 busbar holders and 2 SK 5 shield connection clamps)
Terminal marking
Zack marker strip - ZB 20,3 AXL UNPRINTED - 0829579
Zack marker strip for Axioline F (device labeling), in 2 x 20.3 mm pitch, unprinted, 25-section, for individual labeling with
B-STIFT 0.8, X-PEN, or CMS-P1-PLOTTER
Zack Marker strip, flat - ZBF 10/5,8 AXL UNPRINTED - 0829580
Zack marker strip, flat, in 10 mm pitch, unprinted, 10-section, for individual labeling with M-PEN 0,8, X-PEN, or CMS-P1PLOTTER
Phoenix Contact 2017 © - all rights reserved
http://www.phoenixcontact.com
04/13/2017 Page 8 / 8