IB IL AO 2/UI-XC-PAC
Inline analog output terminal, version for extreme
conditions, 2 outputs for connection of current and
voltage signals
Data sheet
8500_en_02
1
© PHOENIX CONTACT 2015-11-04
Description
The terminal is designed for use within an Inline station.
It is used to output analog current or voltage signals.
Thanks to special engineering measures and tests, the terminal can be used under extreme ambient conditions.
Features
–
–
–
–
–
–
–
–
2 analog output channels
Connection of actuators in 2-wire technology
Current ranges: 0 mA ... 20 mA, 4 mA ... 20 mA,
±20 mA
Voltage ranges: 0 V ... 10 V, -10 V ... +10 V
Diagnostic and status indicators
Can be used under extreme ambient conditions
Extended temperature range of -40°C ... +70°C
(see “Tested successfully: use under extreme ambient
conditions”)
Painted PCBs
This data sheet is only valid in association with the IL SYS INST UM E user manual.
Make sure you always use the latest documentation.
It can be downloaded from the product at phoenixcontact.net/products.
IB IL AO 2/UI-XC-PAC
2
Table of contents
1
Description .............................................................................................................................. 1
2
Table of contents ..................................................................................................................... 2
3
Ordering data .......................................................................................................................... 3
4
Technical data ......................................................................................................................... 4
5
Additional technical data.......................................................................................................... 7
5.1
Tolerance specifications ........................................................................................................ 7
5.2
Step response (signal rise time) .............................................................................................. 7
5.3
Tolerances influenced by electromagnetic interference ................................................................. 7
6
Tested successfully: Use under extreme ambient conditions .................................................. 8
7
Internal circuit diagram ............................................................................................................ 9
8
Electrical isolation.................................................................................................................... 9
9
Terminal point assignment..................................................................................................... 10
10
Connection example.............................................................................................................. 10
11
Connection notes .................................................................................................................. 10
12
Installation instructions .......................................................................................................... 10
13
Local status and diagnostic indicators ................................................................................... 10
14
Process data.......................................................................................................................... 11
14.1 OUT process data.............................................................................................................. 11
14.2 IN process data ................................................................................................................. 12
14.3 Read firmware version ........................................................................................................ 12
15
Representation of the output values in the different formats .................................................. 13
15.1 IB IL format ...................................................................................................................... 13
15.2 Format S7 compatible ......................................................................................................... 14
8500_en_02
PHOENIX CONTACT
2
IB IL AO 2/UI-XC-PAC
3
Ordering data
Description
Type
Order No.
Pcs./Pkt.
Inline analog output terminal, version for extreme conditions, complete with
accessories (connector connector and labeling field), 2 outputs, 0 - 20 mA,
4 - 20 mA, ±20 mA, 0 - 10 V, ±10 V, 2-conductor connection technology
IB IL AO 2/UI-XC-PAC
2701389
1
Accessories
Type
Order No.
Pcs./Pkt.
Shield connection clamp, for shield on busbars, contact resistance < 1 mΩ
(Assembly)
SK 8
3025163
10
Shield connection clamp, for shield on busbars, contact resistance < 1 mΩ
(Assembly)
SK 14
3025176
10
Shield connection clamp, for shield on busbars, contact resistance < 1 mΩ
(Assembly)
SK 20
3025189
10
Shield connection clamp, for shield on busbars, contact resistance < 1 mΩ
(Assembly)
SK 35
3026463
10
Support bracket for busbars (Assembly)
AB-SK
3025341
10
Support bracket, Bracket for busbars, set every 20 cm, Length: 95.5 mm,
Width: 6.2 mm, Color: gray (Assembly)
AB-SK 65
3026489
10
Support bracket, Bracket for busbars, set every 20 cm, Length: 10 mm,
Width: 56 mm, Height: 20 mm, Color: silver (Assembly)
AB-SK/E
3026476
10
PEN conductor busbar, 3mm x 10 mm, length: 1000 mm (Assembly)
NLS-CU 3/10 SN 1000MM
0402174
10
Connection terminal block, Connection method Screw connection, Cross
section: 0.5 mm² - 6 mm², Width: 7 mm, Color: silver
AK 4
0404017
50
Connection terminal block, Connection method Screw connection, Cross
section: 0.5 mm² - 6 mm², Width: 7 mm, Color: green-yellow
AKG 4 GNYE
0421029
50
Connection terminal block, Connection method Screw connection, Cross
section: 0.5 mm² - 6 mm², Width: 7 mm, Color: black
AKG 4 BK
0421032
50
Documentation
Type
Order No.
Pcs./Pkt.
User manual, English, Automation terminals of the Inline product range
IL SYS INST UM E
-
-
Data sheet, English, INTERBUS addressing
DB GB IBS SYS ADDRESS
-
-
8500_en_02
PHOENIX CONTACT
3
IB IL AO 2/UI-XC-PAC
4
Technical data
Dimensions (nominal sizes in mm)
140,5
71,5
119,8
Width
12.2 mm
Height
119.8 mm
Depth
71.5 mm
Note on dimensions
Housing dimensions
General data
Weight
66 g (with connector)
Ambient temperature (operation)
-25 °C ... 55 °C (Standard)
-40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme
ambient conditions” in the data sheet.)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection
IP20
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Connection data
Designation
Inline connector
Connection method
Spring-cage connection
Conductor cross section solid / stranded
0.08 mm² ... 1.5 mm² / 0.08 mm² ... 1.5 mm²
Conductor cross section [AWG]
28 ... 16
Stripping length
8 mm
Connection data for UL approvals
Designation
Inline connector
Connection method
Spring-cage connection
Conductor cross section solid / stranded
0.2 mm² ... 1.5 mm² / 0.2 mm² ... 1.5 mm²
Conductor cross section [AWG]
24 ... 16
Stripping length
8 mm
8500_en_02
PHOENIX CONTACT
4
IB IL AO 2/UI-XC-PAC
Interface Inline local bus
Number
2
Connection method
Inline data jumper
Transmission speed
500 kBit/s
Transmission physics
Copper
Inline potentials / Power consumption
Communications power UL
7.5 V DC (via voltage jumper)
Current consumption from UL
typ. 55 mA
max. 65 mA
I/O supply voltage UANA
24 V DC
Current consumption from UANA
typ. 24 mA (No-load)
max. 30 mA (No-load)
typ. 38 mA (Nominal voltage load (UOUT1/2 = 10 V, RL = 1 kΩ))
max. 45 mA (Nominal voltage load (UOUT1/2 = 10 V, RL = 1 kΩ))
typ. 65 mA (Nominal current load (IOUT1/2 = 20 mA, RL = 0 Ω))
max. 75 mA (Nominal current load (IOUT1/2 = 20 mA, RL = 0 Ω))
Power consumption
typ. 1.32 W (Nominal voltage load (UOUT1/2 = 10 V, RL = 1 kΩ))
typ. 1.97 W (Nominal current load (IOUT1/2 = 20 mA, RL = 0 Ω))
Analog outputs
Number of outputs
2
Connection method
2-wire (shielded, twisted pair)
D/A resolution
12 bit
D/A conversion time
typ. 10 µs
Representation of output values
12 bits (11 bits + sign bit)
Data formats
IB IL, S7-compatible
Process data update
bus-synchronous
Permissible cable length
max. 250 m (The specifications refer to nominal operation after complying with installation instructions.The specifications refer to the following reference cable
type:Shielded power station cable: LiYCY; 2 x 2 x 0,5 mm²; VDE0812)
Short-circuit and overload protection
Electronic
Transient protection
Suppressor diode
Analog outputs, Current
Current output signal
0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA
Load/output load current output
≤ 450 Ω
Precision
typ. 0.1 % (of output range final value)
Analog outputs, Voltage
Voltage output signal
0 V ... 10 V, -10 V ... 10 V
Load/output load voltage output
> 1 kΩ
Precision
typ. 0.1 % (of output range final value)
Programming Data
ID code (hex)
5B
ID code (dec.)
91
Length code (hex)
04
Length code (dec.)
04
Process data channel
64 Bit
Input address area
8 Byte
Output address area
8 Byte
Parameter channel (PCP)
0 Byte
Register length (bus)
64 Bit
8500_en_02
PHOENIX CONTACT
5
IB IL AO 2/UI-XC-PAC
Configuration and parameter data in a PROFIBUS system
Required parameter data
10 Byte
Need for configuration data
5 Byte
Error messages to the higher level control or computer system
Failure of the internal I/O supply
I/O error message sent to the bus coupler
I/O supply failure
Message in the diagnostic code (in the IB IL format)
Short circuit/overload of the outputs
Message in the diagnostic code (in the IB IL format)
Configuration invalid
Message in the diagnostic code (in the IB IL format)
Electrical isolation/isolation of the voltage areas
Test section
Test voltage
7.5 V supply (bus logics)/24 V analog supply (analog I/O)
500 V AC, 50 Hz, 1 min
7.5 V supply (bus logics) / functional earth ground
500 V AC, 50 Hz, 1 min
24 V analog supply (analog I/O) / functional earth ground
500 V AC, 50 Hz, 1 min
To achieve electrical isolation between the logic level and the I/O area, supply these areas from separate power supply units. Interconnection
of the power supply units in the 24 V area is not permitted (see also user manual).
Conformance with EMC Directive 2004/108/EC
Noise immunity test in accordance with EN 61000-6-2
Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2
Criterion B; 6 kV contact discharge, 8 kV air discharge
Electromagnetic fields EN 61000-4-3/IEC 61000-4-3
Criterion A; Field intensity: 10 V/m
Fast transients (burst) EN 61000-4-4/IEC 61000-4-4
Criterion B, 2 kV
Transient surge voltage (surge) EN 61000-4-5/IEC 61000-4-5
Criterion B; DC: ±0.5 kV/±1 kV(symmetrical/unsymmetrical) supply cables;
shielded I/O cables: ±1 kV
Conducted interference EN 61000-4-6/IEC 61000-4-6
Criterion A; Test voltage 10 V
Noise emission test according to EN 61000-6-3
Radio interference properties EN 55022
Class A
Approvals
For the latest approvals, please visit phoenixcontact.net/products.
8500_en_02
PHOENIX CONTACT
6
IB IL AO 2/UI-XC-PAC
5
Additional technical data
5.1
Tolerance specifications
5.2
Step response (signal rise time)
Voltage step 0 V ... 10 V (typical values)
Tolerances at TA = +25°C
Output range
Absolute
Typ.
Relative
Max.
Typ.
Max.
0 V ...10 V, ±10 V
±10 mV
±20 mV
±0.1 %
±0.2%
0 mA ... 20 mA,
4 mA ... 20 mA,
±20 mA
±20 μA
±60 µA
±0.1 %
±0.3%
Load
Time for
10 % ... 90 %
Time for
0 % ... 99 %
RL = 2 kΩ
9 μs
15 μs
RL = 2 kΩ II CL = 10 nF
9 μs
15 μs
RL = 2 kΩ II CL = 220 nF
135 μs
180 μs
RL = 2 kΩ + LL = 3 mH
8 μs
15 μs
The typical specifications contain the typical offset, gain and
linearity errors.
All tolerances indicated as a percentage are related to the
positive output range final value.
Current step 0 mA ... 20 mA (typical values)
The data is valid for nominal operation (UANA = 24 V) in the
default configuration.
Load
Default configuration: IB IL format
RL = 500 Ω
3 μs
5 μs
RL = 500 Ω II CL = 10 nF
18 μs
30 μs
Please also observe the values for the temperature drift.
The maximum tolerance values represent the worst case
measurement inaccuracy. Besides maximum offset and
gain drift, they also comprise longtime drift as well as the
maximum tolerances of the test and calibration equipment.
Time for
10 % ... 90 %
Time for
0 % ... 99 %
RL = 500 Ω II CL = 220 nF
300 μs
590 μs
RL = 500 Ω + LL = 3 mH
1.6 μs
3 μs
RL = 50 Ω II CL = 100 μF
11 μs
27 μs
Current step 4 mA ... 20 mA (typical specifications)
Tolerance and temperature response
at TA = -25°C ... +55°C
Output range
Load
Drift
Time for
10 % ... 90 %
Time for
0 % ... 99 %
Typ.
Max.
RL = 500 Ω
2.3 μs
4 μs
0 V ...10 V, ±10 V
±30 ppm/K
±50 ppm/K
RL = 500 Ω II CL = 10 nF
15 μs
26 μs
0 mA ... 20 mA, 4 mA ... 20 mA,
±20 mA
±30 ppm/K
±50 ppm/K
RL = 500 Ω II CL = 220 nF
260 μs
450 μs
RL = 500 Ω + LL = 3 mH
1.5 μs
2.8 μs
The drift values refer to the relevant output range final value.
The values refer to nominal operation with default settings.
5.3
Tolerances influenced by electromagnetic interference
Type of electromagnetic
interference
Typical deviation in %
referencing the output
range final value
Voltage output
Current
output
Electromagnetic fields; field strength
10 V/m according to EN 61000-4-3/
IEC 61000-4-3