https://www.phoenixcontact.com/us/products/2701503
Distributed I/O device - AXL E PB IOL8 DI4 M12 6P - 2701503
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Axioline E PROFIBUS device in a plastic housing with 8 IO-Link ports and 4 digital inputs, 24 V DC, M12 fast
connection technology
Product Description
The device enables the operation of up to eight IO-Link sensors/actuators and is also used to acquire digital signals.
Product Features
Connection to PROFIBUS DP using M12connectors (B-coded)
Baud rate of up to 12 Mbaud (automatic baud rate detection)
Connection of four IO-Link devices with additional digital input
Connection of four IO-Link actuators with additional power supply
Connection of IO-Link ports using M12connectors (A-coded, 5-pos.)
Diagnostic and status indicators
Short-circuit and overload protection of the sensor supply
IP65/IP67 degree of protection
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
560.0 g
Custom tariff number
85176200
Country of origin
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
60 mm
Height
185 mm
12/28/2015 Page 1 / 6
https://www.phoenixcontact.com/us/products/2701503
Distributed I/O device - AXL E PB IOL8 DI4 M12 6P - 2701503
Technical data
Dimensions
Depth
30.5 mm
Note on dimensions
The height is 212 mm including fixing clips.
Drill hole spacing
198.5 mm
Ambient conditions
Ambient temperature (operation)
-25 °C ... 60 °C
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
5 % ... 95 %
Permissible humidity (storage/transport)
5 % ... 95 %
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection
IP65/IP67
General
Net weight
552 g
Mounting type
Wall mounting
Interfaces
Fieldbus system
PROFIBUS DP
Designation
PROFIBUS DP
Connection method
2x M12 connectors, B-coded
Designation connection point
Copper cable
Transmission speed
9,6 kBit/s ... 12 MBit/s (Automatic baud rate detection)
Transmission physics
PROFIBUS-DP-compliant copper cable
Address area assignment
1 ... 126, adjustable
Number of positions
5
System limits of the bus coupler
Designation
PROFIBUS DP
Equipment type
PROFIBUS slave
System-specific protocols
PROFIBUS protocols DP V1
Power supply for module electronics
Module electronics and sensors
M12 connector (T-coded) Module electronics and sensors (US) 4
Connection method
M12 connector (T-coded)
Designation
Module electronics and sensors (US)
Number of positions
4
Supply voltage
24 V DC
Nominal supply voltage range
18 V DC ... 31.2 V DC (including all tolerances, including ripple)
Current consumption
max. 12 A
12/28/2015 Page 2 / 6
https://www.phoenixcontact.com/us/products/2701503
Distributed I/O device - AXL E PB IOL8 DI4 M12 6P - 2701503
Technical data
Power supply for module electronics
Typical current consumption
170 mA ±15 % (at 24 V DC)
Actuators
M12 connector (T-coded) Actuators (UA) 4
Connection method
M12 connector (T-coded)
Designation
Actuators (UA)
Number of positions
4
Supply voltage
24 V DC
Nominal supply voltage range
18 V DC ... 31.2 V DC (including all tolerances, including ripple)
Current consumption
max. 12 A
Typical current consumption
30 mA ±15 % (at 24 V DC)
Digital inputs
Input name
Digital inputs
Connection method
M12 connector, double occupancy
2, 3, 4-wire
Number of inputs
4 (EN 61131-2 types 1 and 3)
Protective circuit
Protection against polarity reversal
Input filter time
< 1000 µs
Input voltage
24 V DC
Input voltage range "0" signal
-30 V DC ... 5 V DC
Input voltage range "1" signal
11 V DC ... 30 V DC
Nominal input current at UIN
typ. 3 mA
Standards and Regulations
Conformity with EMC directives
Noise immunity test in accordance with EN 61000-6-2 Electrostatic
discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact
discharge, 8 kV air discharge
Noise immunity test in accordance with EN 61000-6-2 Electromagnetic
fields EN 61000-4-3/IEC 61000-4-3 Criterion A; Field intensity: 10 V/m
Noise immunity test in accordance with EN 61000-6-2 Fast transients
(burst) EN 61000-4-4/IEC 61000-4-4 Criterion B, 2 kV
Noise immunity test in accordance with EN 61000-6-2 Transient
overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion B, DC supply
lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical)
Noise immunity test in accordance with EN 61000-6-2 Conducted
interference EN 61000-4-6/IEC 61000-4-6 Criterion A; Test voltage 10 V
Noise emission test as per EN 61000-6-4 Radio interference properties EN
55022 Class A
Test section
24 V supply (communications power and sensor supply, IO-Link ports)/bus
connection 500 V AC 50 Hz 1 min.
24 V supply (communications power and sensor supply, IO-Link ports)/FE
500 V AC 50 Hz 1 min.
Bus connection / FE 500 V AC 50 Hz 1 min.
12/28/2015 Page 3 / 6
https://www.phoenixcontact.com/us/products/2701503
Distributed I/O device - AXL E PB IOL8 DI4 M12 6P - 2701503
Technical data
Standards and Regulations
24 V supply (actuator supply)/24 V supply (communications power and
sensor supply, IO-Link ports) 500 V AC 50 Hz 1 min.
24 V supply (actuator supply)/bus connection 500 V AC 50 Hz 1 min.
24 V supply (actuator supply)/FE 500 V AC 50 Hz 1 min.
Mechanical tests
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g, 11 ms period, halfsine shock pulse
Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Classifications
eCl@ss
eCl@ss 4.0
27240404
eCl@ss 4.1
27240404
eCl@ss 5.0
27242204
eCl@ss 5.1
27242604
eCl@ss 6.0
27242604
eCl@ss 7.0
27242604
eCl@ss 8.0
27242604
ETIM
ETIM 2.0
EC001433
ETIM 3.0
EC001599
ETIM 4.0
EC001599
ETIM 5.0
EC001599
UNSPSC
UNSPSC 6.01
43172015
UNSPSC 7.0901
43201404
UNSPSC 11
39121311
UNSPSC 12.01
39121311
UNSPSC 13.2
39121311
Approvals
Approvals
12/28/2015 Page 4 / 6
https://www.phoenixcontact.com/us/products/2701503
Distributed I/O device - AXL E PB IOL8 DI4 M12 6P - 2701503
Approvals
Approvals
UL Listed / cUL Listed / PROFIBUS / cULus Listed
Ex Approvals
UL Listed / cUL Listed / cULus Listed
Approvals submitted
Approval details
UL Listed
cUL Listed
PROFIBUS
cULus Listed
Drawings
Connection diagram
Dimensional drawing
212
DI
L+
X03
33
30,5
32
X04
+24 V
L-
198,5
X05
UA
X06
C/Q
L+
60
UA
30
C/Q
L-
185
12/28/2015 Page 5 / 6
https://www.phoenixcontact.com/us/products/2701503
Distributed I/O device - AXL E PB IOL8 DI4 M12 6P - 2701503
L-
C/Q
GND (UA)
L+
UA
Connection diagram
Phoenix Contact 2015 © - all rights reserved
http://www.phoenixcontact.com
12/28/2015 Page 6 / 6
很抱歉,暂时无法提供与“2701503”相匹配的价格&库存,您可以联系我们找货
免费人工找货