AXL F BK S3
Axioline F bus coupler for Sercos
Data sheet
105610_en_02
1
© PHOENIX CONTACT 2015-11-10
Description
Valid from firmware version 1.10.
The bus coupler is intended for use within a third-generation
Sercos network and represents the link to the Axioline F
system.
Up to 63 Axioline F devices can be connected to an existing
Sercos network with the help of the bus coupler.
Features of Sercos
–
–
–
–
–
–
–
–
–
2 Ethernet-Ports
Rotary coding switches for setting the Sercos address
Transmission speed of 100 Mbps with a minimum Sercos cycle time of 31.25 µs
Sercos diagnostic LED
Certified according to Sercos V1.12
Supports Sercos V1.31
FSP-IO (Function Specific Profile-IO) for modular I/O
devices
A maximum of 8 connections are supported (max. 4
consumer and max. 4 producer connections)
Cross communication is possible up to reaching the
maximum number of connections
–
Synchronization
Features of Axioline F
–
–
–
–
–
Up to 63 additional Axioline F devices can be connected
Typical cycle time of the Axioline F local bus is around
10 μs
Runtime in the bus coupler is negligible (goes to 0 µs)
Firmware can be updated
Diagnostic and status indicators
This data sheet is only valid in association with the UM EN AXL F SYS INST user manual.
You can find further information on Sercos in the UM DE SERCOS SYS user manual.
Make sure you always use the latest documentation.
It can be downloaded from the product at phoenixcontact.net/products.
You will always find the current SDDML-files here.
AXL F BK S3
2
Table of contents
1
Description .............................................................................................................................. 1
2
Table of contents ..................................................................................................................... 2
3
Ordering data .......................................................................................................................... 3
4
Technical data ......................................................................................................................... 4
5
Internal circuit diagram ............................................................................................................ 6
6
Connection of Sercos and supply ............................................................................................ 7
7
Connection example................................................................................................................ 7
8
Configuration via rotary encoding switch ................................................................................. 8
9
Local status and diagnostic indicators ..................................................................................... 9
10
Sercos ................................................................................................................................... 12
11
Sercos parameter .................................................................................................................. 16
12
Access to PDI objects............................................................................................................ 20
13
Mapping method.................................................................................................................... 20
14
Tunnel method....................................................................................................................... 21
15
Reset button .......................................................................................................................... 25
16
Service interface.................................................................................................................... 26
17
Startup................................................................................................................................... 26
18
Firmware update.................................................................................................................... 28
105610_en_02
PHOENIX CONTACT
2
AXL F BK S3
3
Ordering data
Description
Order No.
Pcs./Pkt.
Axioline F bus coupler for Sercos (including bus base module and connec- AXL F BK S3
tor)
Type
2701686
1
Accessories
Type
Order No.
Pcs./Pkt.
Axioline F bus base module for housing type BK (Replacement item)
AXL BS BK
2701422
5
Axioline F short power connector (for e.g., AXL F BK ...) (Replacement
item)
AXL CN S/UL
2701421
5
RJ45 connector, shielded, with bend protection sleeve, 2 pieces, gray for
straight cables, for assembly on site. For connections that are not crossed,
it is recommended that you use the connector set with gray bend protection
sleeve. (Connector/Adapter)
FL PLUG RJ45 GR/2
2744856
1
RJ45 connector, shielded, with bend protection sleeve, 2 pieces, green for
crossed cables, for assembly on site. For connections that are crossed, it
is recommended that the connector set with green bend protection sleeves
is used. (Connector/Adapter)
FL PLUG RJ45 GN/2
2744571
1
CAT5-SF/UTP cable (J-02YS(ST)C HP 2 x 2 x 24 AWG), heavy-duty instal- FL CAT5 HEAVY
lation cable, 2 x 2 x 0.22 mm², solid conductor, shielded, outer sheath: 7.8
mm diameter, inner sheath: 5.75 mm ± 0.15 mm diameter (Cable/conductor)
2744814
1
CAT5-SF/UTP cable (J-LI02YS(ST)C H 2 x 2 x 26 AWG), light-duty, flexible installation cable 2 x 2 x 0.14 mm², stranded, shielded, outer sheath:
5.75 mm ± 0.15 mm diameter (Cable/conductor)
FL CAT5 FLEX
2744830
1
Crimping pliers, for assembling the RJ45 plugs FL PLUG RJ45..., for assembly on site (Tools)
FL CRIMPTOOL
2744869
1
Zack marker strip for Axioline F (device labeling), in 2 x 20.3 mm pitch, un- ZB 20,3 AXL UNPRINTED
printed, 25-section, for individual labeling with B-STIFT 0.8, X-PEN, or
CMS-P1-PLOTTER (Marking)
0829579
25
Zack marker strip, flat, in 10 mm pitch, unprinted, 10-section, for individual
labeling with M-PEN 0,8, X-PEN, or CMS-P1-PLOTTER (Marking)
ZBF 10/5,8 AXL UNPRINTED
0829580
50
Insert label, Roll, white, unlabeled, can be labeled with: THERMOMARK
ROLL, THERMOMARK ROLL X1, THERMOMARK X, THERMOMARK
S1.1, Mounting type: snapped into marker carrier, Lettering field: 35 x 18.7
mm (Marking)
EMT (35X18,7)R
0801831
1
Connecting cable, for connecting the controller to a PC for PC Worx and
LOGIC+, USB A to micro USB B, 2 m in length. (Cable/conductor)
CAB-USB A/MICRO USB B/2,0M
2701626
1
Documentation
Type
Order No.
Pcs./Pkt.
User manual, English, Axioline F: System and installation
UM EN AXL F SYS INST
-
-
User manual, English, Axioline F: Diagnostic registers, and error messages UM EN AXL F SYS DIAG
-
-
User manual, English, Sercos system manual for I/O devices
UM EN SERCOS SYS
-
-
Application note, English,
Updating the firmware of an Axioline F bus coupler
AH EN TFTP FIRMWARE UPDATE
AXL F BK
-
-
105610_en_02
PHOENIX CONTACT
3
AXL F BK S3
4
Technical data
Dimensions (nominal sizes in mm)
122,4
Width
125,9
74
45
45 mm
Height
125.9 mm
Depth
74 mm
Note on dimensions
The depth is valid when a TH 35-7.5 DIN rail is used (according to EN 60715).
General data
Color
traffic grey A RAL 7042
Weight
177 g (with connector and bus base module)
Ambient temperature (operation)
-25 °C ... 60 °C (Mounting position: wall mounting on horizontal DIN rail)
-25 °C ... 55 °C (Mounting position: any)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)
5 % ... 95 % (non-condensing)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection
IP20
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Mounting position
Any (observe temperature derating)
Connection data
Designation
Axioline F connector
Connection method
Push-in connection
Conductor cross section solid / stranded
0.2 mm² ... 1.5 mm² / 0.2 mm² ... 1.5 mm²
Conductor cross section [AWG]
24 ... 16
Stripping length
8 mm
Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
105610_en_02
PHOENIX CONTACT
4
AXL F BK S3
Interface Sercos
Number
2
Connection method
RJ45 socket, auto negotiation and auto crossing
Transmission speed
100 MBit/s (Full duplex)
Cycle Time
31.25 µs
Transmission physics
Ethernet in RJ45 twisted pair
Transmission length
max. 100 m
Interface Axioline F local bus
Connection method
Bus base module
Transmission speed
100 MBit/s
Interface Service
Number
1
Connection method
Micro USB type B
System limits
Number of supported devices
max. 63 (per station)
NOTE: Electronics may be damaged when overloaded
Observe the logic current consumption of each device when configuring an Axioline F station. It is specified in every module-specific data
sheet. The current consumption can differ depending on the individual module. The permissible number of devices that can be connected
therefore depends on the specific station structure.
Sercos
Equipment type
Sercos slave
Device profile
FSP_IO
Update rate
31.25 µs
Sercos protocols
Sercos
Specification
Sercos specification 1.31
Supply of the bus coupler
Supply of communications power UL
24 V DC
Maximum permissible voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current supply at UBus
2A
Current consumption from UL
typ. 105 mA (without I/Os and UL = 24 V)
max. 570 mA (with 2 A at UBus for the I/Os and UL = 24 V)
Power consumption at UL
typ. 2.5 W (without I/Os)
max. 13.7 W (with 2 A load at UBus for the I/Os)
NOTE: Electronics may be damaged when overloaded
Provide external fuses for the 24 V UL area. The power supply unit must be able to supply four times the nominal current of the external fuse
to ensure that it blows in the event of an error.
Error messages to the higher level control or computer system
None
Mechanical tests
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6
5g
Shock in acc. with EN 60068-2-27/IEC 60068-2-27
30g
Continuous shock according to EN 60068-2-27/IEC 60068-2-27
10g
105610_en_02
PHOENIX CONTACT
5
AXL F BK S3
Conformance with EMC Directive 2004/108/EC
Noise immunity test in accordance with EN 61000-6-2
Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2
Criterion B; 6 kV contact discharge, 8 kV air discharge
Electromagnetic fields EN 61000-4-3/IEC 61000-4-3
Criterion A; Field intensity: 10 V/m
Fast transients (burst) EN 61000-4-4/IEC 61000-4-4
Criterion B, 2 kV
Transient surge voltage (surge) EN 61000-4-5/IEC 61000-4-5
Criterion B; DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical); fieldbus cable shield: ±1 kV
Conducted interference EN 61000-4-6/IEC 61000-4-6
Criterion A; Test voltage 10 V
Noise emission test according to EN 61000-6-3
Radio interference properties EN 55022
Class B
Approvals
For the latest approvals, please visit phoenixcontact.net/products.
5
Internal circuit diagram
Key:
S
FE
Sercos
RDY
FE
Service
Reset
Local bus
SD
RJ45
D
5V
E
RJ45
3.3V
Functional earth ground
Service interface
Reset button
Axioline F local bus
(hereinafter referred to as local bus)
RJ45 interface
RJ45
FE
Service
C
Reset
Power supply unit with electrical isolation
Local bus
UBus
µC
Microcontroller
Power supply unit
XXX
UL
3.3 V
UBus
XXX
LED
24 V
Electrically isolated areas
UL
24 V
Figure 1
105610_en_02
Internal wiring of the terminal points
PHOENIX CONTACT
6
AXL F BK S3
6
Connection of Sercos and supply
6.1
Connecting Sercos
6.2
Connecting the supply voltage - terminal point
assignment
Connecting Sercos to the bus coupler via an 8-pos. RJ45
connector.
a1
a2
The Sercos connections are set to autocrossing (auto crossover).
Install Sercos in accordance with the specifications in the current "Planning and Installation Guide" (see www.sercos.com).
Also observe the information in the "Sercos
system manual for I/O devices" user manual.
Shielding
The shielding ground of the connected twisted pair cables is electrically connected with
the socket. When connecting network segments, avoid ground loops, potential transfers, and voltage equalization currents via the
braided shield.
Figure 2
a1
b1
a2
b2
b1
b2
Terminal point assignment
Terminal Color
Assignment
point
Supply voltage input
a1, a2
Red
24 V DC Supply of the logic voltage (internally jumpered)
(UL)
b1, b2
Blue
GND
Reference potential of the
supply voltage (internally
jumpered)
7
Connection example
Observe bending radii
The housing dimensions specified under "Dimensions" refer to the bus coupler with I/O
connectors without Ethernet connection.
When installing the bus coupler in a control
box, observe the bending radii of the cables
and the connectors used.
Sercos
S
SD
RDY
If required, use angled RJ45 connectors to
maintain these bending radii.
D
E
12 14
0 2
4 6
8 10
S1
X10
UL
105610_en_02
CD
AB
0 2
89
Figure 3
S2
4 6
24 V DC +
(UL)
EF
X1
Connection of the cables
PHOENIX CONTACT
7
AXL F BK S3
8
Configuration via rotary encoding
switch
You can configure the address assignment and other functions using rotary encoding switches.
8.3
Switch position 12C
All settings are reset to the delivery state.
After modifying the switch position, restart the bus coupler,
as the modification to the switch position does not take effect during operation.
S1
14
0
10
The device is ready for operation after powering up, as soon as the RDY LED lights up
green.
A connection to the device however cannot be
established in this switch position.
As soon as the RDY LED lights up green, a
new switch position can be selected on the rotary encoding switch and the device can be
restarted.
2
12
4
8
6
x10
S2
E
D
C
B
A
F 0
2
4
9 8
Alternatively, the default setting can also be
restored via the reset button (see “Reset button”).
6
x1
Figure 4
Rotary encoding switch
The code results from the sum of S1 x 10 plus S2 x 1. The
image shows code 77 (7 x 10 + 7).
S1
0
0 ... 15
12
8.1
Resetting to the default settings
8.4
Reserved/invalid switch position
The device starts with the previous settings, e.g., with the
settings that were valid before the device was restarted.
S2
Code
Function
0
00
Remote address assignment
0 ... 9 01 ... 159 Manual address assignment
C
12C
Resetting to the default settings
Other
Reserved
Remote address assignment
Switch position 00
The standard Sercos remote access is activated with this
switch position, so that the bus coupler accepts an address
assignment e.g., via the engineering system.
8.2
Manual address assignment
Switch position 01 ... 159
The devices are automatically assigned addresses as standard.
Set the Sercos address manually with this switch position.
Remote address assignment, e.g., via an engineering tool,
is deactivated.
105610_en_02
PHOENIX CONTACT
8
AXL F BK S3
9
Local status and diagnostic indicators
S
SD
ACT
LNK
ACT
RDY
D
E
UL
Figure 5
LNK
Local status and diagnostic indicators
Designation
UL
Color
Green
Meaning
ULogic
S
Red/or- Sercos
ange/
green
State
ON
OFF
OFF
Orange ON
Flashing
orange/
green
Flashing
orange/
green
Flashing
orange/
green
Green ON
Green
flashing
Flashing
red/orange
Flashing
red/green
Red ON
Flashing
orange
(2 Hz)
Flashing
red (2 Hz)
105610_en_02
Description
Communications power supply present.
Communications power supply not present.
NRT mode; no Sercos communication
CP0
CP1:
250 ms green, 2750 ms orange
CP2:
250 ms green, 250 ms orange,
250 ms green, 2250 ms orange
CP3:
250 ms green, 250 ms orange,
250 ms green, 250 ms orange,
250 ms green, 1750 ms orange
CP4
Loop back activated
User error; see chapter on "Diagnostics: bus and user errors"
MST loss
Communication error
Identification (bit 15 in device control); is used for address assignment and configuration errors.
Watchdog error
PHOENIX CONTACT
9
AXL F BK S3
Designation
SD
RDY
D
105610_en_02
Color
Meaning
Red/or- Sub Device
ange/
green
State
Description
Green ON Sub device is on the operation level (OL)
Orange ON Sub device is on the parameterization level (PL)
Red ON
Error in the sub device (C1D)
OFF
Sub device is not active.
Green/ Ready
Green ON Device is ready for operation.
yellow/
Flashing
Communications power undervoltage or surge voltage
red
green/yel- Overtemperature
low
Yellow ON Firmware/bus coupler is booting
Yellow
Firmware update is being performed.
flashing
Flashing
Firmware update has failed.
yellow/red
Flashing
Faulty firmware
red
Red ON
Rotary encoding switches are set to an invalid/reserved position.
OFF
Device is not ready for operation.
Red/yel- Diagnostics of local bus communication
low/
Run
Green ON The station is ready for operation, communication within the station
green
is OK.
All data is valid. There are no faults.
Active
Green
The station is ready for operation, communication within the station
flashing
is OK.
The data is not valid. Valid data from the controller/higher-level network not available.
There is no fault in the module.
Ready
Yellow ON The station is ready for operation, no data exchange taking place.
Yellow
Access from Startup+ in I/O check mode
flashing
Flashing
Local bus error during active I/O check
yellow/red
Flashing
Local bus error on startup
red
Possible causes:
Configuration cannot be generated, information is missing from a
device
Chip version of a device is