IB IL 24 DO 2-2A-XC-PAC
Inline digital output terminal,
version for extreme conditions,
2 outputs, 24 V DC, 2 A
Data sheet
106145_en_00
1
© PHOENIX CONTACT 2014-07-29
Description
The terminal is designed for use within an Inline station. It is
used to output digital signals.
Thanks to special engineering measures and tests, the terminal can be used under extreme ambient conditions.
Features
–
–
–
–
–
–
–
–
–
Connections for two digital actuators
Connection of actuators in 2, 3, and 4-wire technology
Nominal current of each output: 2 A
Total current of the terminal: 4 A
Short-circuit and overload protected outputs
Diagnostic and status indicators
Can be used under extreme ambient conditions
Painted PCBs
Extended temperature range T2 (-40°C ... +55°C)
This data sheet is only valid in association with the IL SYS INST UM E user manual.
Make sure you always use the latest documentation.
It can be downloaded from the product at phoenixcontact.net/products.
IB IL 24 DO 2-2A-XC-PAC
2
Table of contents
1
Description .............................................................................................................................. 1
2
Table of contents ..................................................................................................................... 2
3
Ordering data .......................................................................................................................... 3
4
Technical data ......................................................................................................................... 3
5
Additional tables ...................................................................................................................... 6
5.1
Output characteristic curve..................................................................................................... 6
5.2
Power dissipation ................................................................................................................ 6
5.3
Limitation of simultaneity, derating ........................................................................................... 6
6
Tested successfully: Use under extreme ambient conditions .................................................. 7
7
Internal circuit diagram ............................................................................................................ 7
8
Local status and diagnostic indicators ..................................................................................... 8
9
Terminal point assignment....................................................................................................... 8
10
Connection notes and examples ............................................................................................. 8
11
Process data............................................................................................................................ 8
106145_en_00
PHOENIX CONTACT
2
IB IL 24 DO 2-2A-XC-PAC
3
Ordering data
Description
Order No.
Pcs. / Pkt.
Inline digital output terminal, version for extreme conditions, complete with IB IL 24 DO 2-2A-XC-PAC
accessories (connector plug and marking field), 2 outputs, 24 V DC, 2 A, 4conductor connection technology
Type
2702133
1
Accessories
Type
Order No.
Pcs. / Pkt.
Labeling field, width: 12.2 mm (Marking)
IB IL FIELD 2
2727501
10
Insert strip, Sheet, white, unlabeled, can be labeled with: Office printing
systems, Plotter: Laser printer, Mounting type: Insert, Lettering field: 62 x
10 mm (Marking)
ESL 62X10
0809492
1
Insert strip, Sheet, white, unlabeled, can be labeled with: Office printing
systems, Plotter: Laser printer, Mounting type: Insert, Lettering field: 62 x
46 mm (Marking)
ESL 62X46
0809502
5
Inline connector, colored (Connector/Adapter)
IB IL SCN-8-CP
2727608
10
Connector, for digital 1, 2 or 8-channel Inline terminals (Connector/
Adapter)
IB IL SCN-8
2726337
10
Documentation
Type
Order No.
Pcs. / Pkt.
User manual, English, Automation terminals of the Inline product range
IL SYS INST UM E
-
-
Data sheet, English, INTERBUS addressing
DB GB IBS SYS ADDRESS
-
-
4
Technical data
Dimensions (nominal sizes in mm)
140,5
71,5
119,8
Width
12.2 mm
Height
119.8 mm
Depth
71.5 mm
Note on dimensions
Housing dimensions
General data
Color
green
Weight
61 g (with connector)
Operating mode
Process data mode with 2 bits
Ambient temperature (operation)
-40 °C ... 55 °C (See also the "Tested successfully: Use under extreme ambient
conditions" section of the data sheet.)
Ambient temperature (operation)
-40 °C ... 60 °C (At US < 24.5 V; see also the "Tested successfully: Use under extreme ambient conditions" section of the data sheet.)
106145_en_00
PHOENIX CONTACT
3
IB IL 24 DO 2-2A-XC-PAC
General data
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Temperature class
T2 (-40°C ... 55°C, EN 50155)
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection
IP20
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Connection data
Designation
Inline connector
Connection method
Spring-cage connection
Conductor cross section solid / stranded
0.08 mm² ... 1.5 mm² / 0.08 mm² ... 1.5 mm²
Conductor cross section [AWG]
28 ... 16
Stripping length
8 mm
Connection data for UL approvals
Designation
Inline connector
Connection method
Spring-cage connection
Conductor cross section solid / stranded
0.2 mm² ... 1.5 mm² / 0.2 mm² ... 1.5 mm²
Conductor cross section [AWG]
24 ... 16
Stripping length
8 mm
Interface Inline local bus
Connection method
Inline data jumper
Transmission speed
500 kBit/s
Power consumption
Segment supply voltage US
24 V DC (nominal value)
Current consumption from US
max. 4 A
Communications power UL
7.5 V DC (via voltage jumper)
Current consumption from UL
max. 35 mA
Power consumption
max. 0.27 W (at UL)
Digital outputs
Number of outputs
2
Connection method
Spring-cage connection
Connection method
2, 3, 4-wire
Nominal output voltage
24 V DC
Voltage difference with nominal current
≤1V
Maximum output current per channel
2A
Maximum output current per device
4A
Nominal load, ohmic
48 W (12 Ω)
Nominal load, inductive
48 VA (1.2 H, 12 Ω)
Nominal load, lamp
48 W
Signal delay when switching on an ohmic nominal load
approx. 200 µs
Signal delay when switching on an inductive nominal load
approx. 250 ms (1.2 H, 12 Ω)
Signal delay when switching on a lamp nominal load
typ. 200 ms (for switching frequencies up to 8 Hz; above this frequency, the lamp
load behaves like an ohmic load)
Signal delay when switching off an ohmic nominal load
approx. 200 µs
Signal delay when switching off an inductive nominal load
approx. 250 ms (1.2 H, 12 Ω)
106145_en_00
PHOENIX CONTACT
4
IB IL 24 DO 2-2A-XC-PAC
Digital outputs
Signal delay when switching off a lamp nominal load
approx. 200 µs
Maximum operating frequency with ohmic nominal load
max. 300 Hz (this switching frequency is limited by the data rate selected, the
number of bus devices, the structure of the bus, the software used and the control
or computer system used)
Maximum operating frequency with inductive nominal load
max. 0.5 Hz (1.2 H, 12 Ω)
Maximum operating frequency with lamp nominal load
max. 300 Hz (this switching frequency is limited by the data rate selected, the
number of bus devices, the structure of the bus, the software used and the control
or computer system used)
Behavior at voltage switch-off
The output follows the power supply without delay
Limitation of the voltage induced on circuit interruption
approx. -0.7 V
Behavior with overload
Auto restart
Behavior with inductive overload
Output can be destroyed
Reverse voltage resistance to short pulses
Reverse voltage proof
Resistance to permanent reverse voltage
to 2 A DC
Overload protection, short-circuit protection of outputs
Yes
Type of external protective circuit
Freewheeling diode per channel
Programming Data
ID code (hex)
BD
ID code (dec.)
189
Length code (hex)
C2
Length code (dec.)
194
Process data channel
2 Bit
Input address area
0 Bit
Output address area
2 Bit
Parameter channel (PCP)
0 Bit
Register length (bus)
2 Bit
For the programming data/configuration data of other bus systems, please refer to the corresponding electronic device data sheet (e.g., GSD,
EDS).
Fieldbus data telegram
Fieldbus system
PROFIBUS DP
Required parameter data
3 Byte
Need for configuration data
4 Byte
Error messages to the higher level control or computer system
Short-circuit / overload of the digital outputs
Error message in the diagnostic code (bus) and display (2 Hz) via the LED (D) on
the module
Electrical isolation/isolation of the voltage areas
Test section
Test voltage
5 V supply, incoming remote bus/7.5 V supply (bus logics)
500 V AC, 50 Hz, 1 min
5 V supply, outgoing remote bus/7.5 V supply (bus logics)
500 V AC, 50 Hz, 1 min
7.5 V supply (bus logics)/24 V supply (I/O)
500 V AC, 50 Hz, 1 min
24 V supply (I/O) / functional earth ground
500 V AC, 50 Hz, 1 min
To achieve electrical isolation between the logic level and the I/O area, supply these areas from separate power supply units. Interconnection
of the power supply units in the 24 V area is not permitted (see also user manual).
Approvals
For the latest approvals, please visit phoenixcontact.net/products.
106145_en_00
PHOENIX CONTACT
5
IB IL 24 DO 2-2A-XC-PAC
5
Additional tables
5.1
Output characteristic curve
Output characteristic curve when switched on
(typical)
Output current (A)
Differential output voltage (V)
0
0
0.2
0.02
0.4
0.04
0.6
0.06
0.8
0.08
1.0
0.10
1.2
0.12
1.4
0.14
1.6
0,16
1.8
0.18
2.0
0,20
2.2
0.22
5.2
Power dissipation
Formula for calculating the power dissipation of the
electronics
n
PEL = 0,18 W + ∑ (0,20 W + ILi2 x 0,10 Ω)
i=1
Where:
PEL
i
n
ILi
Total power dissipation in the terminal
Continuous index
Number of set outputs (n = 1 ... 2)
Load current of output i
Power dissipation of the housing
PHOU = 2.4 W
-25°C < TA ≤ -5°C
PHOU = 2.4 W - {[TA - (-5 °C)]/37.5 K/W}
-5°C < TA ≤ +55°C
Where:
PHOU Power dissipation of the housing
Ambient temperature
TA
5.3
106145_en_00
Limitation of simultaneity, derating
Ambient temperature Tamb
Maximum load current
100 % simultaneity
≤ 55 °C
1 A
2A
≤ 40°C
2A
2A
50 % simultaneity
PHOENIX CONTACT
6
IB IL 24 DO 2-2A-XC-PAC
6
Tested successfully: Use under
extreme ambient conditions
7
Internal circuit diagram
The terminal has been tested successfully over 250 temperature change cycles in accordance with IEC 61131-2 in the
range from -40°C to +70°C.
Local bus
UL
The following conditions were observed:
– The Inline devices for all connecting cables were connected with a minimum conductor cross section of
0.5 mm²
– The Inline station was assembled on a wall-mounted
horizontal DIN rail
– Fans were used to ensure continuous movement of air
in the control cabinet
– The Inline station was not exposed to vibration or shock
– The Inline station was operated with a maximum of
24.5 V (ensured by using regulated power supply units)
+24 V (US)
+24 V (UM)
3 h + 30 min
t1
Tmax + 2 K
(3 + 0,6) K/min
Tmin + 3 K
3 h + 30 min
Figure 2
Internal wiring of the terminal points
Key:
t1
1
Figure 1
OPC
OPC
Protocol chip
(Bus logic including voltage conditioning)
Temperature change cycle
LED (status indicator)
Temperature in the control cabinet/ambient
temperature
Optocoupler
Cycle
Transistor
Digital output
WARNING:
The terminal is not approved for use in potentially explosive areas.
Electrically isolated area
The terminal is not approved for use in safety
technology.
Explanation for other used symbols has been
provided in the IL SYS INST UM E user manual.
106145_en_00
PHOENIX CONTACT
7
IB IL 24 DO 2-2A-XC-PAC
Local status and diagnostic
indicators
D
2
Local status and diagnostic indicators
Designa- Color
tion
D
Green
1 ... 2
When connecting the actuators, observe the
assignment of the terminal points to the process data.
Yellow
Meaning
Diagnostics (bus and logic voltage)
Status of the outputs
Figure 5
1.1
2.1
1.2
2.2
1.3
2.3
1.4
2.4
+24 V
Figure 3
Connection notes and examples
OUT 2
1
10
OUT 1
8
Typical connection of actuators
Function identification
The connection of actuators in 4 and 3-wire technology is illustrated.
Pink
9
Terminal point assignment
11
Process data
Assignment of the terminal points to the output
process data
Figure 4
1.1
1.1 2.1
2.1
1.2
1.2 2.2
2.2
1.3
1.3 2.3
2.3
1.4
1.4 2.4
2.4
(Byte.Bit) view Byte.Bit
Assignment
Terminal point
(signal)
Terminal point
(24 V)
Terminal point
(GND)
Terminal point
(FE)
Status indicator LED
0.0
1.1
2.2
1.2
2.3
1.3
2.4
1.4
2
1
Terminal point assignment
Terminal point Assignment
1.1 / 2.1
Signal output (OUT 1 / OUT 2)
1.2, 2.2
Segment voltage US for 4-wire connection
Measuring points for segment voltage
US (24 V DC)
1.3, 2.3
Ground connection (GND) for 2, 3 and 4wire connection
1.4, 2.4
FE connection for 3 and 4-wire connection
106145_en_00
0.1
2.1
For the assignment of the illustrated (byte.bit)
view to your INTERBUS control or computer
system, please refer to the
DB GB IBS SYS ADDRESS data sheet.
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com
8