Safety-related digital output module, IP20 protection, for the SafetyBridge system. The module has four safe
digital outputs with two-channel occupancy or 8 safe digital outputs with single-channel occupancy
Product Description
The safety module is an output module from the Axioline F product range with integrated safety logic designed for use in a
®
SafetyBridge Technology V3 system. The safety module can be used as part of an Axioline F station at any point within an EtherCAT , EtherNet/
IP™, Sercos, Modbus, PROFINET or PROFIBUS system. The module has four safe digital outputs for two-channel assignment or eight safe digital
outputs for single-channel assignment.
Why buy this product
Cost-effective system configuration, as no safety PLC or safe fieldbus system is required
Flexible use, thanks to compatibility with all bus couplers from the Axioline F range
Reduced installation time, thanks to fast wiring and easy handling
Easy configuration using the free SAFECONF software
Up to SIL 3 according to EN 61508
Up to SILCL 3 according to EN 62061
Up to cat. 4/PL e according to EN ISO 13849-1
Key Commercial Data
Packing unit
1 STK
GTIN
GTIN
4055626004983
Weight per Piece (excluding packing)
222.000 g
Custom tariff number
85389091
Country of origin
Germany
Technical data
Dimensions
Width
53.6 mm
05/03/2018 Page 1 / 6
https://www.phoenixcontact.com/in/products/2702171
Safety module - AXL F LPSDO8/3 1F - 2702171
Technical data
Dimensions
Height
126.1 mm
Depth
54 mm
Note on dimensions
Housing dimensions
Ambient conditions
Ambient temperature (operation)
-35 °C ... 60 °C (Mounting position: any)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
10 % ... 75 % (on average, 85% infrequently, non-condensing)
Permissible humidity (storage/transport)
10 % ... 75 % (non-condensing)
Air pressure (operation)
70 kPa ... 108 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
66 kPa ... 108 kPa (up to 3500 m above sea level)
Degree of protection
IP20
Interfaces
Designation
Axioline F local bus (Note: not suitable for use in the Axioline F local bus
of the Phoenix Contact AXC 3050 controller)
No. of channels
1
Connection method
Bus base module
Digital outputs
Output name
Digital outputs
Connection method
Direct plug-in technology
Connection technology
2, 3-wire
Number of outputs
4 (with two-channel assignment)
8
Type of protection
Overload protection, freewheeling circuit for inductive loads,
Discharge circuit for accelerated discharge of capacitive loads
Output voltage
24 V DC
Output current
max. 2 A (per channel)
max. 1.5 A (per channel according to CULUS)
max. 4 A (per group)
max. 3 A (per group according to CULUS)
max. 8 A (Total current of all outputs; Please observe the notes in the
user manual.)
max. 6 A (Total current of all outputs according to CULUS)
Maximum output current per channel
2A
Maximum output current per module / terminal block
8A
General
Mounting type
DIN rail
Net weight
222 g
Note on weight specifications
with connectors and bus base module
Axioline potentials
05/03/2018 Page 2 / 6
https://www.phoenixcontact.com/in/products/2702171
Safety module - AXL F LPSDO8/3 1F - 2702171
Technical data
Axioline potentials
Designation
Axioline F local bus supply (UBus)
Supply voltage
5 V DC (via bus base module)
Current consumption
typ. 260 mA (all outputs set; power supply by UO of 19.2 V DC to
30.2 V DC)
max. 280 mA
Designation
Supply for digital output modules (UO)
Supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30.2 V DC (including all tolerances, including ripple)
Current consumption
typ. 25 mA (all outputs set; power supply by UO with 30.2 V DC; without
power supply to the actuator)
Type of protection
Protection against polarity reversal, EMC protective circuit, undervoltage
detection
SafetyBridge properties
Connection to I/O modules
max. 16 (safe digital I/O modules)
Logic memory
30 kByte
Safety-related characteristic data
Designation
IEC 61508 - High demand
Safety Integrity Level (SIL)
max. 3 (two channel; dependent in parameterization and wiring)
Designation
IEC 61508 - Low demand
Safety Integrity Level (SIL)
max. 3 (two channel; dependent in parameterization and wiring)
Designation
EN ISO 13849
Performance level (PL)
max. e (two channel; dependent in parameterization and wiring)
Category
max. 4 (two channel; dependent in parameterization and wiring)
Designation
EN 62061
Safety Integrity Level Claim Limit (SIL CL)
max. 3 (two channel; dependent in parameterization and wiring)
Standards and Regulations
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Environmental Product Compliance
China RoHS
Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values
Drawings
05/03/2018 Page 3 / 6
https://www.phoenixcontact.com/in/products/2702171
Safety module - AXL F LPSDO8/3 1F - 2702171
Dimensional drawing
126,1
54
122,4
53,6
Classifications
eCl@ss
eCl@ss 5.1
27242694
eCl@ss 6.0
27242694
eCl@ss 8.0
27242604
eCl@ss 9.0
27242604
ETIM
ETIM 3.0
EC001599
ETIM 4.0
EC002498
ETIM 5.0
EC001599
ETIM 6.0
EC001599
UNSPSC
UNSPSC 6.01
43172015
UNSPSC 7.0901
43201404
UNSPSC 11
43172015
UNSPSC 12.01
43201404
UNSPSC 13.2
32151602
Approvals
Approvals
Approvals
UL Listed / cUL Listed / Functional Safety / Functional Safety / cULus Listed
Ex Approvals
Approval details
05/03/2018 Page 4 / 6
https://www.phoenixcontact.com/in/products/2702171
Safety module - AXL F LPSDO8/3 1F - 2702171
Approvals
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
Functional Safety
968/EZ 424.05/17
Functional Safety
968/EZ 424.05/17
cULus Listed
Accessories
Accessories
Device marking
Insert label - EMT (35X28)R - 0801602
Insert label, Roll, white, unlabeled, can be labeled with: THERMOMARK ROLL, THERMOMARK ROLL X1,
THERMOMARK ROLLMASTER 300/600, THERMOMARK X1.2, THERMOMARK S1.1, mounting type: snapped into
marker carrier, lettering field size: 35 x 28 mm
DIN rail connector
Bus connector - AXL F BS F - 2688129
Axioline F bus base module for housing type F
Terminal marking
05/03/2018 Page 5 / 6
https://www.phoenixcontact.com/in/products/2702171
Safety module - AXL F LPSDO8/3 1F - 2702171
Accessories
Zack marker strip - ZB 20,3 AXL UNPRINTED - 0829579
Zack marker strip for Axioline F (device labeling), in 2 x 20.3 mm pitch, unprinted, 25-section, for individual labeling
with B-STIFT 0.8, X-PEN, or CMS-P1-PLOTTER
Zack Marker strip, flat - ZBF 10/5,8 AXL UNPRINTED - 0829580
Zack marker strip, flat, in 10 mm pitch, unprinted, 10-section, for individual labeling with M-PEN 0,8, X-PEN, or CMSP1-PLOTTER
Phoenix Contact 2018 © - all rights reserved