AXL E IOL TC4/K M12 - Analog module
2702983
https://www.phoenixcontact.com/us/products/2702983
Please be informed that the data shown in this PDF document is generated from our online catalog. Please find the complete data in the user
documentation. Our general terms of use for downloads are valid.
Axioline E IO-Link/analog converter with 4 analog TC inputs (type K/J), 2-conductor connection
technology, 1 IO-Link A port, 24 V DC, IP65 degree of protection
Product description
The Axioline E IO-Link/analog converter is an IO-Link device that transfers analog signals from thermocouples (TCs) via the IO-Link protocol. The
device offers you the option of using an IO-Link master to record the analog signals of conventional Type K thermocouples (TC). It supports
type K/J thermocouples in accordance with DIN EN 60584-1. The measured values are depicted in standardized representation format. The device
is connected to an IO-Link master via an IO-Link A port. Use within different networks is possible via the IO-Link master.
Your advantages
• Connection to an IO-Link master with M12 connector (A-coded, 4-pos.)
• IO-Link A port
• IO-Link specification V1.1.2
• Status indicators
• 4 differential inputs for thermocouples
• Measuring range type K: -270°C ... +1,372°C
• Measuring range type J: -210 °C ... +1200 °C
• Selectable resolution 0.1 K/0.01 K
• Connection of sensors in 2-conductor technology
• M12 cable gland, Push-in Technology
• Diagnostic information in the process data word
• Supply of the module electronics via the IO-Link interface of the master
• Degree of protection IP65
Commercial data
Item number
2702983
Packing unit
1 pc
Minimum order quantity
1 pc
Sales key
DR04
Product key
DRI7Z5
Catalog page
Page 181 (C-6-2019)
GTIN
4055626447261
Weight per piece (including packing)
384.3 g
Weight per piece (excluding packing)
384.3 g
Customs tariff number
85176200
Jan 8, 2024, 8:58 AM
Page 1 (11)
AXL E IOL TC4/K M12 - Analog module
2702983
https://www.phoenixcontact.com/us/products/2702983
Country of origin
DE
Jan 8, 2024, 8:58 AM
Page 2 (11)
AXL E IOL TC4/K M12 - Analog module
2702983
https://www.phoenixcontact.com/us/products/2702983
Technical data
Notes
Utilization restriction
EMC note
EMC: class A product, see manufacturer's declaration in the
download area
Product properties
Type
Stand-Alone
Product type
Interface converter
Product family
Axioline E
Insulation characteristics
Pollution degree
2 (EN 60664-1)
Electrical properties
Supply: IO-Link
Designation
IO-Link port supply (L+)
Nominal voltage for I/O supply
24 V DC (Provided via the IO-Link interface of the IO-Link
master.)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Nominal current per device
typ. 35 mA (±15% (at 24 V DC), max. 70 mA)
Protective circuit
Reverse polarity protection; yes
Short-circuit protection; yes
Overload protection; yes
Electrical isolation/isolation of the voltage ranges
Test voltage: IO-Link bus logic
500 V AC, 50 Hz, 1 min.
Test voltage: Thermocouple I/O devices
500 V AC, 50 Hz, 1 min.
Test voltage: Functional ground
500 V AC, 50 Hz, 1 min.
Input data
IO-Link
Number of ports
1
Connection method
M12 connector (A-coded)
Connection technology
3-conductor
Port type
Class A
Specification
V1.1.2
Reverse polarity protection
yes
Transmission speed
230.4 kbps (COM3)
Process data update
< 310 ms
Amount of process data
64 bit (4x 16-bit input data)
Analog
Jan 8, 2024, 8:58 AM
Page 3 (11)
AXL E IOL TC4/K M12 - Analog module
2702983
https://www.phoenixcontact.com/us/products/2702983
Input name
Analog TC inputs
Description of the input
Differential inputs
Number of inputs
4
Connection method
Push-in technology
Connection technology
2-conductor
A/D conversion time
typ. 40 ms
A/D converter resolution
24 bit
Sensor types that can be used (TC)
K/J
Measuring principle
Sigma/Delta process
Measured value representation
16 bits
Protective circuit
Transient protection of inputs
Overload protection
Wire-break detection
Connection data
Thermocouples
Connection method
Push-in technology
Conductor cross section, rigid
0.2 mm² ... 1.5 mm²
Conductor cross section, flexible
0.2 mm² ... 1.5 mm²
Conductor cross section AWG
24 ... 16
Stripping length
8 mm
Dimensions
Dimensional drawing
Width
150 mm
Height
54 mm
Depth
118 mm
Note on dimensions
When installing, note the length of the M12 connector for the IOLink cable and the bending radii of the TC cables.
Material specifications
Color
light grey RAL 7035
Housing material
Polycarbonate
Environmental and real-life conditions
Ambient conditions
Ambient temperature (operation)
-25 °C ... 60 °C
Degree of protection
IP65 (not UL-tested)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Jan 8, 2024, 8:58 AM
Page 4 (11)
AXL E IOL TC4/K M12 - Analog module
2702983
https://www.phoenixcontact.com/us/products/2702983
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
5 % ... 95 %
Permissible humidity (storage/transport)
5 % ... 95 %
Standards and regulations
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Jan 8, 2024, 8:58 AM
Page 5 (11)
AXL E IOL TC4/K M12 - Analog module
2702983
https://www.phoenixcontact.com/us/products/2702983
Drawings
Dimensional drawing
150
135
54
14
5
80
≈118
120
Dimensions (in mm)
Connection diagram
TC
+24 V DC (L+)
GND (L-)
C/Q
1_IN+
1_IN2_IN+
2_IN3_IN+
3_IN4_IN+
4_IN-
Connection example
Jan 8, 2024, 8:58 AM
Page 6 (11)
AXL E IOL TC4/K M12 - Analog module
2702983
https://www.phoenixcontact.com/us/products/2702983
Approvals
To download certificates, visit the product detail page: https://www.phoenixcontact.com/us/products/2702983
cULus Listed
Approval ID: E238705
Jan 8, 2024, 8:58 AM
Page 7 (11)
AXL E IOL TC4/K M12 - Analog module
2702983
https://www.phoenixcontact.com/us/products/2702983
Classifications
ECLASS
ECLASS-11.0
27242601
ECLASS-12.0
27242601
ECLASS-13.0
27242601
ETIM
ETIM 8.0
EC001596
UNSPSC
UNSPSC 21.0
32151600
Jan 8, 2024, 8:58 AM
Page 8 (11)
AXL E IOL TC4/K M12 - Analog module
2702983
https://www.phoenixcontact.com/us/products/2702983
Environmental product compliance
REACh SVHC
Lead 7439-92-1
Jan 8, 2024, 8:58 AM
Page 9 (11)
AXL E IOL TC4/K M12 - Analog module
2702983
https://www.phoenixcontact.com/us/products/2702983
Accessories
SEALING PLUG 5X12 RD - Closing cap
1400253
https://www.phoenixcontact.com/us/products/1400253
Closing cap, color: red
AXL E TC4 SHIELD SET - Shield connection
1065793
https://www.phoenixcontact.com/us/products/1065793
Axioline E shield connection set (includes 5 shield braid clips for receiving
shielded TC compensating lines)
Jan 8, 2024, 8:58 AM
Page 10 (11)
AXL E IOL TC4/K M12 - Analog module
2702983
https://www.phoenixcontact.com/us/products/2702983
IOL-CONF - Network management software
1083065
https://www.phoenixcontact.com/us/products/1083065
IOL-CONF is a browser-based configuration software tool for the easy startup of
IO-Link masters and IO-Link devices
Phoenix Contact 2024 © - all rights reserved
https://www.phoenixcontact.com
Phoenix Contact USA
586 Fulling Mill Road
Middletown, PA 17057, United States
(+717) 944-1300
info@phoenixcon.com
Jan 8, 2024, 8:58 AM
Page 11 (11)