IL PN BK DI8 DO4 2TX-PAC
Order No.: 2703994
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2703994
PROFINET bus coupler, 8 inputs, 24 V DC, 4 outputs, 24 V DC, 500
mA, complete with I/O connectors
Product notes
WEEE/RoHS-compliant since:
03/27/2008
Commercial data
GTIN (EAN)
4
046356
041164
Note
Made-to-order
sales group
K410
Pack
1 pcs.
Customs tariff
85176200
Catalog page information
Page 242 (AX-2009)
http://
www.download.phoenixcontact.com
Please note that the data given
here has been taken from the
online catalog. For comprehensive
information and data, please refer
to the user documentation. The
General Terms and Conditions of
Use apply to Internet downloads.
Product description
The bus coupler for the PROFINET protocol has 4 digital outputs and 8 digital inputs. This package contains all the
necessary Inline connectors for connecting the supply and the I/Os.
The Inline terminals can be labeled using pull-out labeling fields. The fields have insert cards that can be labeled
individually to suit the application. Additionally, there is the ZBFM-6... Zack marker strip for labeling the terminal points.
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 1 / 7
Feb 7, 2011
IL PN BK DI8 DO4 2TX-PAC Order No.: 2703994
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2703994
Technical data
Interface
Fieldbus system
Lokalbus
Name
Inline local bus
Type of connection
Inline data jumper
Transmission speed
500 Kbit / 2 MBaud
500 kBit/s, 2 MBit/s (Automatic detection, no combined system)
Fieldbus system
PROFINET
Name
PROFINET
Type of connection
RJ45 female connector, auto negotiation
Transmission speed
100 MBit/s (acc. to PROFINET standard)
Transmission physics
Ethernet in RJ45 twisted pair
Digital inputs
Input name
Digital inputs
Description of the input
EN 61131-2 type 1
Type of connection
Inline connectors
Connection method
2, 3-wire
Number of inputs
8
Typical response time
Approx. 500 µs
Protective circuit
Protection against polarity reversal Polarity protection diode
Input voltage
24 V DC
Input voltage range "0" signal
-30 V DC ... 5 V DC
Input voltage range "1" signal
15 V DC ... 30 V DC
Nominal input current at UIN
Typ. 3 mA
Typical input current per channel
Typ. 3 mA
Delay at signal change from 0 to 1
5 ms
Delay at signal change from 1 to 0
5 ms
Digital outputs
Output name
Digital outputs
Type of connection
Inline connectors
Connection method
2, 3-wire
Number of outputs
4
Protective circuit
Short-circuit and overload protection Free running circuit
Output voltage
24 V DC -1 V (At nominal current)
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 2 / 7
Feb 7, 2011
IL PN BK DI8 DO4 2TX-PAC Order No.: 2703994
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2703994
Nominal output voltage
24 V DC
Maximum output current per channel
500 mA
Maximum output current per module / terminal
block
2A
Nominal load, inductive
12 VA (1.2 H; 48 Ω)
Nominal load, lamp
12 W
Nominal load, ohmic
12 W
Power supply for module electronics
Type of connection
Spring-cage connection
Name
Bus coupler supply UBC; Communications power UL (7.5 V) and
the analog supply UANA (24 V) are generated from the bus coupler
supply.
Supply voltage
24 V DC (via Inline connector)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumption
max. 0.91 A (from UBK)
General data
Width
80 mm
Height
119.8 mm
Depth
71.5 mm
Note on dimensions
Specfications with male connectors
Weight
375 g
Note on weight specifications
with male connectors
Mounting type
DIN rail
Ambient temperature (operation)
-25 °C ... 55 °C (observe derating)
Ambient temperature (storage/transport)
-45 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection
IP20
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 3 / 7
Feb 7, 2011
IL PN BK DI8 DO4 2TX-PAC Order No.: 2703994
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2703994
Conformance with EMC directives
Noise immunity test in accordance with EN 61000-6-2
Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2
Criterion B; 6 kV contact discharge, 8 kV air discharge
Noise immunity test in accordance with EN 61000-6-2
Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A;
Field intensity: 10 V/m
Noise immunity test in accordance with EN 61000-6-2 Fast
transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion A; all
interfaces 1 kVCriterion B; all interfaces 2 kV
Noise immunity test in accordance with EN 61000-6-2 Transient
surge voltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion
B; supply lines DC: 0.5 kV/0.5 kV (symmetrical/asymmetrical);
fieldbus cable shield 1 kV
Noise immunity test in accordance with EN 61000-6-2 Conducted
interference EN 61000-4-6/IEC 61000-4-6 Criterion A; Test
voltage 10 V
Noise emission test as per EN 61000-6-4 EN 55011 Class A
Mechanical tests
Vibration resistance in acc. with IEC 60068-2-6 5 g
Shock test in acc. with IEC 60068-2-27 Operation: 25 g, 11 ms
duration, semi-sinusoidal shock impulse
Diagnostics messages
Short-circuit / overload of the digital outputs Yes
Sensor supply failure Yes
Failure of the actuator supply Yes
Inline potential routing
Communications power UL
7.5 V DC ±5%
Power supply at UL
max. 0.8 A DC
Main circuit supply UM
24 V DC
Supply voltage range UM
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at UM
max. 8 A DC (Sum of UM + US; 4 A, maximum, when used in
potentially explosive areas.)
Current consumption from UM
max. 8 A DC (US-consumer project+)
Segment supply voltage US
24 V DC
Supply voltage range US
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at US
max. 8 A DC (Sum of UM + US; 4 A, maximum, when used in
potentially explosive areas.)
Current consumption from US
max. 8 A DC (US-consumer project+)
I/O supply voltage UANA
24 V DC
Supply voltage range UANA
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at UANA
max. 0.5 A DC
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 4 / 7
Feb 7, 2011
IL PN BK DI8 DO4 2TX-PAC Order No.: 2703994
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2703994
Certificates / Approvals
Certification
ABS, BV, CUL Listed, DNV, GL, LR, UL Listed
Certification Ex:
PxC-EX
Accessories
Item
Designation
Description
3022218
CLIPFIX 35
Snap-on end bracket, for 35 mm NS 35/7.5 or NS 35/15 DIN
rail, can be fitted with Zack strip ZB 8 and ZB 8/27, terminal strip
marker KLM 2 and KLM, width: 9.5 mm, color: gray
1201442
E/UK
End clamp, for assembly on NS 32 or NS 35/7.5 DIN rail
Assembly
Cable/conductor
2744830
FL CAT5 FLEX
CAT5-SF/UTP cable (J-LI02YS(ST)C H 2 x 2 x 26 AWG), lightduty, flexible installation cable 2 x 2 x 0.14 mm², stranded,
shielded, outer sheath: 5.75 mm ± 0.15 mm diameter
2744814
FL CAT5 HEAVY
CAT5-SF/UTP cable (J-02YS(ST)C HP 2 x 2 x 24 AWG), heavyduty installation cable, 2 x 2 x 0.22 mm², solid conductor, shielded,
outer sheath: 7.8 mm diameter, inner sheath: 5.75 mm ± 0.15 mm
diameter
0809492
ESL 62X10
Insert strip for laser printer, lettering field: 62 x 10 mm
0809502
ESL 62X46
Insert strip for laser printer, lettering field: 62 x 46 mm
2727501
IB IL FIELD 2
Labeling field, width: 12.2 mm
2727515
IB IL FIELD 8
Labeling field, width: 48.8 mm
FL PLUG RJ45 GN/2
RJ45 connector, shielded, with bend protection sleeve, 2 pieces,
green for crossed cables, for assembly on site. For connections
that are crossed, it is recommended that the connector set with
green bend protection sleeves is used.
Marking
Plug/Adapter
2744571
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 5 / 7
Feb 7, 2011
IL PN BK DI8 DO4 2TX-PAC Order No.: 2703994
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2703994
2744856
FL PLUG RJ45 GR/2
RJ45 connector, shielded, with bend protection sleeve, 2 pieces,
gray for straight cables, for assembly on site. For connections that
are not crossed, it is recommended that you use the connector set
with gray bend protection sleeve.
2878599
IL BKDIO-PLSET
Connector set, for Inline bus coupler with I/Os mounted in rows
FL CRIMPTOOL
Crimping pliers, for assembling the RJ45 connectors FL PLUG
RJ45..., for assembly on site
Tools
2744869
Diagrams/Drawings
Connection diagram
Diagram
Dimensioned drawing
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 6 / 7
Feb 7, 2011
IL PN BK DI8 DO4 2TX-PAC Order No.: 2703994
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2703994
Address
PHOENIX CONTACT Inc., USA
586 Fulling Mill Road
Middletown, PA 17057,USA
Phone (800) 888-7388
Fax (717) 944-1625
http://www.phoenixcon.com
© 2011 Phoenix Contact
Technical modifications reserved;
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 7 / 7
Feb 7, 2011