Repeater, for potential isolation and increasing the range in RS-485 2-wire LON bus systems, 3-way isolation,
rail-mountable
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
200.0 g
Custom tariff number
85176200
Country of origin
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
22.5 mm
Height
99 mm
Depth
114.5 mm
Ambient conditions
Ambient temperature (operation)
-40 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (non-condensing)
Altitude
5000 m (For restrictions see manufacturer's declaration)
Degree of protection
IP20
Noise immunity
EN 61000-6-2:2005
General
12/10/2015 Page 1 / 8
https://www.phoenixcontact.com/us/products/2708041
Interface converter - PSM-ME-REP LON485-P - 2708041
Technical data
General
Transmission channels
2 (1/1), RxD, TxD, full duplex
Bit distortion
< 1.5 % (applies to device: Distortions caused by system-specific cables
are not accounted for)
Electrical isolation
VCC // RS-485 (A) // RS-485 (B)
Test voltage data interfaces
2 kV AC
Test voltage data interface/power supply
2 kV AC
2 kV
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Noise emission
EN 50 081-1
Net weight
188.8 g
Housing material
PA
Color
green
MTTF
1808 Years (SN 29500 standard, temperature 25°C, operating cycle 21 %
(5 days a week, 8 hours a day))
796 Years (SN 29500 standard, temperature 40 °C, operating cycle 34.25
% (5 days a week, 12 hours a day))
334 Years (SN 29500 standard, temperature 40°C, operating cycle 100 %
(7 days a week, 24 hours a day))
Conformance
CE-compliant
UL, USA / Canada
508 recognized
Class I, Div. 2, Groups A, B, C, D
Class I, Zone 2, AEx nA IIC T4
Class I, Zone 2, Ex nA IIC T4 Gc X
Power supply
Nominal supply voltage
24 V AC/DC ±20 %
Typical current consumption
90 mA (24 V DC)
Serial interface
Interface 1
RS-485 interface in acc. with EIA/TIA-485, DIN 66259-4
Operating mode
Semi-duplex
Connection method
Pluggable screw connection
File format/coding
Manchester, slip-tolerant
Data direction switching
Automatic control
Transmission medium
2-wire twisted pair, shielded
Transmission length
≤ 1200 m (depends on transmission speed, bus system and cable type)
Termination resistor
120 Ω
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
12/10/2015 Page 2 / 8
https://www.phoenixcontact.com/us/products/2708041
Interface converter - PSM-ME-REP LON485-P - 2708041
Technical data
Serial interface
Conductor cross section AWG max.
14
Serial transmission speed
39.1/ 78.1/ 500/ 625/ 1000/ 1250/ 2000 kbps
Interface 2
RS-485 interface in acc. with EIA/TIA-485, DIN 66259-4
Operating mode
Semi-duplex
Connection method
Pluggable screw connection
File format/coding
Manchester, slip-tolerant
Data direction switching
Automatic control
Transmission medium
2-wire twisted pair, shielded
Transmission length
≤ 1200 m (depends on transmission speed, bus system and cable type)
Termination resistor
120 Ω
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Serial transmission speed
39.1/ 78.1/ 500/ 625/ 1000/ 1250/ 2000 kbps
Standards and Regulations
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Noise emission
EN 50 081-1
Noise immunity
EN 61000-6-2:2005
Connection in acc. with standard
CUL
Standards/regulations
EN 61000-4-3
EN 61000-4-4
EN 61000-4-6
Conformance
CE-compliant
UL, USA / Canada
508 recognized
Class I, Div. 2, Groups A, B, C, D
Class I, Zone 2, AEx nA IIC T4
Class I, Zone 2, Ex nA IIC T4 Gc X
Classifications
eCl@ss
eCl@ss 4.0
27250312
eCl@ss 4.1
27250312
eCl@ss 5.0
27242208
eCl@ss 5.1
27242208
eCl@ss 6.0
27242208
12/10/2015 Page 3 / 8
https://www.phoenixcontact.com/us/products/2708041
Interface converter - PSM-ME-REP LON485-P - 2708041
Classifications
eCl@ss
eCl@ss 7.0
27242208
eCl@ss 8.0
19179290
ETIM
ETIM 2.0
EC000698
ETIM 3.0
EC000698
ETIM 4.0
EC000698
ETIM 5.0
EC000310
UNSPSC
UNSPSC 6.01
30211506
UNSPSC 7.0901
39121008
UNSPSC 11
39121008
UNSPSC 12.01
39121008
UNSPSC 13.2
43201553
Approvals
Approvals
Approvals
UL Recognized / cUL Recognized / EAC / UL Recognized / cUL Recognized / EAC / cULus Recognized
Ex Approvals
UL Listed / cUL Listed / cUL Recognized / cUL Recognized / UL Listed / cUL Listed / cULus Listed
Approvals submitted
Approval details
UL Recognized
12/10/2015 Page 4 / 8
https://www.phoenixcontact.com/us/products/2708041
Interface converter - PSM-ME-REP LON485-P - 2708041
Approvals
cUL Recognized
EAC
UL Recognized
cUL Recognized
EAC
cULus Recognized
Drawings
Schematic
diagram
Application drawing
≤ 1200m
DIP
switches
≤ 5m
Cable lengths according to the RS-485 standard
12/10/2015 Page 5 / 8
https://www.phoenixcontact.com/us/products/2708041
Interface converter - PSM-ME-REP LON485-P - 2708041
Dimensional drawing
Schematic diagram
118,6
112
22,5
A
D
T
D
R
C
C
V
85
s4
R
5
48
S
R
PSM-ME-RS232/RS485-P
Ord.-No.: 2744416
99
B
D(A
)D
(B
)T
(A
)T
(B
)
RS232
D(A
RS485
)D
(B
D(A) D(B) T(A) T(B)
GND
)T
(A
) T(B
)
5
Application drawing
Linear structure
Max. of 30 devices
Max. of 30 devices
= Switch on bus terminating resistor
Line structure
12/10/2015 Page 6 / 8
https://www.phoenixcontact.com/us/products/2708041
Interface converter - PSM-ME-REP LON485-P - 2708041
Application drawing
2m
60 m
2m
5m
1000 m
1000 m
2m
5m
30 m
60 m
Cable lengths