CANopen bus coupler, 24 V DC, bus interface 2 x 5-pos. TWIN-COMBICON connector, complete with
accessories (plug and labeling field)
Product Description
®
®
The CANopen fieldbus coupler enables the flexible INTERBUS Inline automation kit to be operated in CANopen networks as well. The fieldbus coupler
®
®
allows an INTERBUS Inline station to be inserted at any point in a CANopen network. The fieldbus coupler is a slave in the CANopen network and a
master in the lower-level INTERBUS Inline local bus.
®
®
The address of the CANopen slave can easily be set via DIP switches from outside. The CANopen network is connected via a Twin Combicon plug.
The operating voltage for the fieldbus coupler and the electronics can be fed using a separate power plug.
®
For the CANopen project planning, a regularly updated EDS file (Electronica Data Sheet) is provided in the Product Information Service (see below).
®
®
The CANopen fieldbus coupler supports the proven INTERBUS Inline diagnostics as well as the typical diagnostics objects for CANopen . Local LEDs
enable precise diagnostics.
Please note the following when you configure the system:
®
The total logic current of all terminals connected to a CANopen network must not exceed the maximum permissible total current of 2 A. Therefore,
depending on your configuration, the number of terminal blocks that you can connect may be less than 63.
Product Features
■
■
■
■
■
®
Slave function in CANopen network
Address can be set via DIP switches
®
CANopen connection via TWIN-COMBICON plug
63 terminals can be connected
Diagnostic and status indicators
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
307.4 g
Custom tariff number
85389091
Country of origin
Germany
Technical data
Note
03/07/2016 Page 1 / 6
https://www.phoenixcontact.com/us/products/2718701
Bus coupler - IL CAN BK-TC-PAC - 2718701
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
85 mm
Height
119.8 mm
Depth
71.5 mm
Ambient conditions
Ambient temperature (operation)
-25 °C ... 55 °C
Ambient temperature (storage/transport)
-45 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection
IP20
General
Net weight
299 g
Note on weight specifications
with connectors
Mounting type
DIN rail
Interfaces
Fieldbus system
CANopen
®
Designation
CANopen
®
Connection method
TWIN COMBICON
Transmission speed
1 MBaud, 500 kBaud, 250 kBaud, 125 kBaud, 50 kBaud, 20 kBaud, 10
kBaud (Can be set via DIP switch or programmed)
Address area assignment
0 ... 63, can be set
Number of positions
10
Fieldbus system
Lokalbus
Designation
Inline local bus
Connection method
Inline data jumper
System limits of the bus coupler
Designation
System limits of the bus coupler
Number of supported devices
max. 63 (per station)
Number of local bus devices that can be connected
max. 63
Number of devices with parameter channel
max. 8
Number of supported branch terminals with remote bus branch
0
03/07/2016 Page 2 / 6
https://www.phoenixcontact.com/us/products/2718701
Bus coupler - IL CAN BK-TC-PAC - 2718701
Technical data
Power supply for module electronics
Connection method
Spring-cage connection
Designation
Bus coupler supply UBC; Communications power UL (7.5 V) and the analog
supply UANA (24 V) are generated from the bus coupler supply.
Supply voltage
24 V DC (via Inline connector)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumption
max. 1.25 A (from UBK)
Inline potentials
Communications power UL
7.5 V DC ±5 %
Power supply at UL
max. 2 A DC
Main circuit supply UM
24 V DC -15 % / +20 % (acc. to EN 61131-2)
Power supply at UM
max. 8 A DC (Sum of UM + US)
Segment circuit supply US
24 V DC -15 % / +20 % (acc. to EN 61131-2)
Power supply at US
max. 8 A DC (Sum of UM + US)
I/O supply voltage UANA
24 V DC -15 % / +20 % (acc. to EN 61131-2)
Power supply at UANA
max. 0.5 A DC
Standards and Regulations
Test section
CANopen/local bus 500 V
Connection in acc. with standard
CUL
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Classifications
eCl@ss
eCl@ss 4.0
27250203
eCl@ss 4.1
27250203
eCl@ss 5.0
27250203
eCl@ss 5.1
27242608
eCl@ss 6.0
27242608
eCl@ss 7.0
27242608
eCl@ss 8.0
27242608
ETIM
ETIM 2.0
EC001434
ETIM 3.0
EC001604
ETIM 4.0
EC001604
ETIM 5.0
EC001604
03/07/2016 Page 3 / 6
https://www.phoenixcontact.com/us/products/2718701
Bus coupler - IL CAN BK-TC-PAC - 2718701
Classifications
UNSPSC
UNSPSC 6.01
43172015
UNSPSC 7.0901
43201404
UNSPSC 11
43172015
UNSPSC 12.01
43201404
UNSPSC 13.2
43201404
Approvals
Approvals
Approvals
UL Recognized / cUL Recognized / EAC / cULus Recognized
Ex Approvals
UL Listed / cUL Listed / cULus Listed
Approvals submitted
Approval details
UL Recognized
Nominal current IN
0.06 A
Nominal voltage UN
24 V
cUL Recognized
Nominal current IN
0.06 A
Nominal voltage UN
24 V
EAC
03/07/2016 Page 4 / 6
https://www.phoenixcontact.com/us/products/2718701
Bus coupler - IL CAN BK-TC-PAC - 2718701
Approvals
cULus Recognized
Drawings
Connection diagram
Dimensional drawing
119,8
CAN
24 V DC +
(UBK)
-
2.1
1.2
2.2
1.3
2.3
1.4
2.4
+ 24 V DC
(UM)
-
+ 24 V DC
(US)
-
71,5
1.1
Block diagram
03/07/2016 Page 5 / 6