Extract from the online
catalog
IB IL TEMP 2 RTD
Order No.: 2726308
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2726308
Inline analog input terminal block; without accessories; 2 inputs; RTD
(resistance temperature detector); 2, 3, 4-wire connection method
Product notes
WEEE/RoHS-compliant since:
01/04/2008
Commercial data
GTIN (EAN)
4
017918
168148
sales group
K412
Pack
1 pcs.
Customs tariff
85389091
Catalog page information
Page 77 (AX-2007)
http://
www.download.phoenixcontact.com
Please note that the data given
here has been taken from the
online catalog. For comprehensive
information and data, please refer
to the user documentation. The
General Terms and Conditions of
Use apply to Internet downloads.
Product description
Using these analog input terminals, it is possible to measure signals from conventional thermocouples and resistance
thermometers.
The terminals are configured for connection to various types of sensors. The user can configure the different sensor
characteristic curves himself via process data. It is thus possible to attain the best possible adaptations in very different
applications.
The Inline terminals can be labeled using hinged labeling fields. The fields have insert cards that can be labeled
individually to suit the application. Additionally, there is the proven ZBFM-6... Zack strip for labeling the terminal points.
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 1 / 5
Feb 7, 2011
IB IL TEMP 2 RTD Order No.: 2726308
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2726308
Technical data
General data
Width
12.2 mm
Height
119.8 mm
Depth
71.5 mm
Weight
46 g
Mounting type
DIN rail
Ambient temperature (operation)
-25 °C ... 55 °C
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection
IP20
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Test section
7.5 V supply (bus logics)/24 V analog supply (analog I/O) 500 V
AC 50 Hz 1 min
7.5 V supply (bus logics) / functional earth ground 500 V AC 50
Hz 1 min
24 V analog supply (analog I/O) / functional earth ground 500 V
AC 50 Hz 1 min
Interface
Name
Inline local bus
Type of connection
Inline data jumper
Transmission speed
500 kbps
500 kBit/s
Transmission physics
Copper
Inline potential routing
Communications power UL
7.5 V DC (via voltage jumper)
Current consumption from UL
max. 60 mA
Typ. 43 mA
I/O supply voltage UANA
24 V DC
Current consumption from UANA
max. 18 mA
Typ. 11 mA
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 2 / 5
Feb 7, 2011
IB IL TEMP 2 RTD Order No.: 2726308
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2726308
Power consumption
Typ. 587 mW
max. 882 mW
Analog inputs
Number of inputs
2 Typ. ± 0.26°C
Input name
Analog RTD inputs
Type of connection
Spring-cage connection
Connection method
2, 3-conductor
Sensor types (RTD) that can be used
Pt, Ni, Cu, KTY, linear resistors
Linear resistance measuring range
0 Ω ... 400 Ω
0 Ω ... 4 kΩ
Measuring principle
Successive approximation
Measured value representation
16 bits two's complement and other
A/D conversion time
Typ. 120 µs (per channel)
Resolution A/D
16 bit (15 bit + sign bit)
Process data update
30 ms
Certificates / Approvals
Certification
ABS, BV, CUL, DNV, GL, GOST, LR, UL
Certification Ex:
CUL-EX LIS, PxC-EX, UL-EX LIS
Accessories
Item
Designation
Description
0809492
ESL 62X10
Insert strip for laser printer, lettering field: 62 x 10 mm
2727501
IB IL FIELD 2
Labeling field, width: 12.2 mm
2740245
IB IL SCN 6-SHIELD-TWIN
Inline shield connector
2726353
IB IL SCN-6 SHIELD
Inline shield connector
Marking
Plug/Adapter
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 3 / 5
Feb 7, 2011
IB IL TEMP 2 RTD Order No.: 2726308
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2726308
Diagrams/Drawings
Connection diagram
Dimensioned drawing
FAQs
•
Malfunctioning in the potentiometer input range
If module IB IL TEMP 2 RTD is operated in the areas of linear resistance (400 Ohm or 4 kOhm), or in the
potentiometer area (these are the sensor configurations 13, 14 and 15, see page 11 data sheet), and if the 4-wire
connection method has been chosen for the first channel, the wire break fault warning message (8002 hex) cannot
be guaranteed (e.g. when the Inline connector is unplugged). Instead, messages 8080 hex (measuring underrange)
or measured values close to 0 Ohm can occur.
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 4 / 5
Feb 7, 2011
IB IL TEMP 2 RTD Order No.: 2726308
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2726308
Address
PHOENIX CONTACT Inc., USA
586 Fulling Mill Road
Middletown, PA 17057,USA
Phone (800) 888-7388
Fax (717) 944-1625
http://www.phoenixcon.com
© 2011 Phoenix Contact
Technical modifications reserved;
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 5 / 5
Feb 7, 2011
很抱歉,暂时无法提供与“2726308”相匹配的价格&库存,您可以联系我们找货
免费人工找货