IBS IP CDIO/R 24-12/4/8(-SF)
Input/Output Module With Twelve Digital
Inputs and Four Digital Outputs
Data Sheet 5992B
R C
IB D IA G
05/2004
R D
IN
8
9
6
1 1
6
7
7
5
4
1
2
1
2
3
2
3
3
O U T
0
Product Description
The module is designed for bodyshell
manufacturing systems in the automotive
industry. It can be mounted directly on a flat
mounting surface or on a Kempf terminal box
(particularly suitable for SF versions for potential
routing).
Both module versions are designed for use with
the installation remote bus. The installation
remote bus carries the supply voltage for the
module and I/O electronics, and also two wire
pairs for additional signals.
5
IN
0
0
1 0
IN
4
U S 2
U S 1
E
5 9 9 2 A 0 0 0
These modules can only be operated
when a controller board with firmware
generation G4.x or later is used.
1
5 9 9 2 A 0 0 1
Figure 1
IBS IP CDIO/R 24-12/4/8(-SF)
The IBS IP CDIO/R 24-12/4/8-SF
module is a version of the
IBS IP CDIO/R 24-12/4/8 module.
The differences between the two
modules will be noted, otherwise all of
the details apply for both module
types.
Cover unused M12 sockets with
protective caps to ensure IP65
protection.
5992B
1
IBS IP CDIO/R 24-12/4/8(-SF)
Local Diagnostic and Status Indicators
Des.
Color Meaning
IBDIAG Green ON:
Supply voltage present, bus active,
no I/O error
Flashes (2 Hz):Voltage present, I/O error
Flashes (0.5 Hz):Voltage present, bus not active
OFF:
Supply voltage not present
RC
Green ON:
OFF:
RD
Red
ON:
OFF:
Outgoing remote bus disabled
Outgoing remote bus switched on
E
Red
ON:
Group message: Overload/short circuit of sensor supply
and/or of outputs
No error
OFF:
2
Incoming remote bus connection established
Incoming remote bus connection defective
US1
Green ON:
Flashes:
OFF:
Supply voltage for module electronics and sensors present
Below permissible voltage range
Supply voltage not present
US2
Green ON:
Flashes:
Supply voltage for actuators present
Below permissible voltage range or voltage not present
IN0 to
IN11
Yellow Yellow:
/red OFF:
Red:
Input set, sensor supply present
Input not set, sensor supply present
Short circuit/overload of sensor supply
(all LEDs of the group of four are red)
OUT0
to
OUT3
Yellow Yellow:
/red OFF:
Red:
Output set, no short circuit /overload
Output not set, no short circuit/overload
Short circuit/overload of the relevant output
5992B
IBS IP CDIO/R 24-12/4/8(-SF)
Internal Circuit Diagram
IN T E R B U S
In c o m in g in s ta lla tio n
O P C m ic r o -
O u tg o in g in s ta lla tio n
p ro c e s s o r
re m o te b u s
re m o te b u s
U S 1 / U S 2
S C M a n d C C R
( - S F v e r s io n o f m o d u le o n ly )
2 4 V
5 V D C
5 V
O u tp u t
In p u t
M ic r o p r o c e s s o r b u s
V C C
U S 2
S u p p re s s o r
L o g ic
c ir c u it
IN
S ta tu s in d ic a to r s
O U T
5 9 9 2 A 0 0 8
Figure 2
5992B
Internal circuit diagram
3
IBS IP CDIO/R 24-12/4/8(-SF)
Electrical Isolation of the Individual Function Areas
IN T E R B U S IN
IN T E R B U S O U T
B u s in te r fa c e
(O P C a n d m ic r o p r o c e s s o r )
A
B
E le c tr ic a l is o la tio n
b e tw e e n A a n d B
2 4 V D C s u p p ly
(U S 1 )
2 4 V D C s u p p ly
(U S 2 )
1 2 d ig ita l in p u ts
in th r e e g r o u p s
Figure 3
G r o u n d p o te n tia l
4 d ig ita l o u tp u ts
5 9 9 2 A 0 0 2
Electrical isolation of the individual function areas
Installation Remote Bus
P r o te c tiv e c a p fo r
s e n s o r/a c tu a to r c o n n e c to rs
O u tg o in g in s ta lla tio n
re m o te b u s
In c o m in g in s ta lla tio n
re m o te b u s
5 9 9 2 A 0 0 3
Figure 4
4
Connection of the installation remote bus cables
5992B
IBS IP CDIO/R 24-12/4/8(-SF)
Installation Remote Bus Cable Assembly
In c o m in g in s ta lla tio n
re m o te b u s
O u tg o in g in s ta lla tio n
re m o te b u s
1
1 1
1 2
1 3
2
1 1
M a le
c o n n e c to r
( b la c k )
1 0
1 6
1 7
9
1 5
3
1 4
4
5
C
re s
+ 2 4 V
0 V
+ 2 4 V
0 V
C
C
S
S
R
8
6
7
D O
D O
D I
D I
O M
e rv
(+
(-U
(+
(-U
C R
C R
C M
C M
F E
B S
U L
7
8
9
e d
U S
S 1
U S
S 2
1
2
1
2
1 )
)
2 )
)
T
1 0
1 1
6
4
1
3
2
1 2
1 7
1 3
1 4
5
1 5
1 6
A s s e m b ly
s id e
y e llo w
g re e n
g ra y
p in k
b ro w n
w h ite
re d
b lu e
b ro w n
b la c k
b lu e
re d
b la c k
p u r p le
y e llo w /g r e e n
P la c e s h ie ld in g
in c o n n e c to r
Figure 5
1 0
3
1 4
9
1 5
8
5
9
1 0
C
re s
+ 2 4 V
0 V
+ 2 4 V
0 V
C
C
S
S
re s
re s
4
6
7
8
5 9 9 2 A 0 0 4
2
1 3
1 7
7
1 1
6
4
1
3
2
1 2
1 7
1 3
1 4
5
1 5
1 6
1
1 2
1 6
D O
D O
D I
D I
O M
e rv
(+
(-U
(+
(-U
C R
C R
C M
C M
F E
e rv
e rv
e d
U S
S 1
U S
S 2
1
2
1
2
1 )
)
2 )
)
e d
e d
P la c e s h ie ld in g
in c o n n e c to r
Pin assignment for the installation remote bus cables
Please avoid wiring errors, otherwise
the module electronics may be
damaged.
5992B
F e m a le
c o n n e c to r
( w h ite )
Signals CCR and SCM are only
required in the special application on
welding robots. These two signals are
carried in the hybrid cable of the
installation remote bus. These signals
are only supplied for the SF version
through an opening in the module
base plate.
5
IBS IP CDIO/R 24-12/4/8(-SF)
I/O Devices
Position of the Connectors and Status Indicators on the Module
R C
IB D IA G
E
R D
U S 2
U S 1
In p u t 1 0
In p u t 9
In p u t 8
IN
8
9
1 0
6
7
In p u t 6
In p u t 5
IN
4
5
C o n n e c to r 4
6
5
In p u t 2
In p u t 1
In p u t 0
IN
1
1
C o n n e c to r 0
3
C o n n e c to r 3
3
O u tp u t 2
O u tp u t 1
0
In p u t 3
2
2
C o n n e c to r 2
O u tp u t 0
In p u t 7
7
C o n n e c to r 5
4
0
*
C o n n e c to r 7
C o n n e c to r 6
In p u t 4
In p u t 1 1
1 1
O U T
0
2
O u tp u t 3
3
C o n n e c to r 1
1
In c o m in g in s ta lla tio n
re m o te b u s
O u tg o in g in s ta lla tio n
re m o te b u s
5 9 9 2 A 0 0 5
Figure 6
Position of the connectors and status indicators on the module
* Only in the SF version input 11 is permanently
connected in the module to the thermostatic
switch input on the bottom of the housing and
has no connection to connector 7.
6
5992B
IBS IP CDIO/R 24-12/4/8(-SF)
Position of the Signals on the Individual Connectors
IN
8 ( B it 0 )
+ 2 4 V (U S 1 )
(U S 1 )
4
5
IN
3
3
IN
1
4
+ 2 4 V (U S 1 )
5
2
9 ( B it 1 )
(U S 1 )
IN
C o n n e c to r 6
IN
4 ( B it 4 )
(U S 1 )
4
2
3
IN
1
4
+ 2 4 V (U S 1 )
1
5
3
2
5 ( B it 5 )
IN
C o n n e c to r 4
(U S 1 )
0 ( B it 0 )
4
2
3
IN
1
4
+ 2 4 V (U S 1 )
1
5
3
(U S 1 )
IN
O U T 0 ( B it 0 )
(U S 2 )
(U S 2 )
4
1
5
3
2
(U S 2 )
C o n n e c to r 0
O u tp u ts 2 A
*
3
1
4
O U T 3 ( B it 3 )
2
5
(U S 2 )
O U T 2 ( B it 2 )
C o n n e c to r 1
O u tp u ts 0 .5 A
5 9 9 2 A 0 0 6
Signal assignment of the connectors
Only in the SF version input 11 is
permanently connected in the module to the
thermostatic switch input on the bottom of
5992B
2 ( B it 2 )
C o n n e c to r 3
C o n n e c to r 2
Figure 7
3 ( B it 3 )
5
2
1 ( B it 1 )
O U T 1 ( B it 1 )
6 ( B it 6 )
C o n n e c to r 5
+ 2 4 V (U S 1 )
IN
7 ( B it 7 )
5
(U S 1 )
IN
1 0 ( B it 2 )
C o n n e c to r 7
+ 2 4 V (U S 1 )
IN
1 1 * ( B it 3 )
2
1
the housing and has no connection to
connector 7.
7
IBS IP CDIO/R 24-12/4/8(-SF)
Connection of Additional Signals for the SF Version
For the SF module version, the following
additional signals can be connected to springcage terminals on the bottom of the module:
CCR to control the welding current, SCM for
secondary circuit monitoring of the welding
transformer and the signal from a thermostatic
switch which monitors the temperature of the
welding transformer. Signals CCR and SCM are
1
3 0 m m
supplied directly in the hybrid cable and
evaluated by the welding controller. The input for
the thermostatic switch is permanently
connected in the module to input 11. This means
that if you are using the thermostatic switch
connector, input 11 cannot be used to connect
sensors.
( 1 .1 8 in .)
1 1 m m
( 0 .4 3 in .)
2
2
1
5 2 2 1 0 0 0 7
Figure 8
Terminal block base on the module bottom (SF version only)
Assignment of the terminal block base
Terminal
8
Signal
1
+24 V DC (US1) sensor supply (thermostatic switch)
2
Input signal for thermostatic switch (permanently connected to input 11)
3
GND US1
4
Constant current regulation 1 (CCR1)
5
Constant current regulation 2 (CCR2)
6
Secondary circuit monitoring 1 (SCM1)
7
Secondary circuit monitoring 2 (SCM2)
5992B
IBS IP CDIO/R 24-12/4/8(-SF)
3 3 m m
( 1 .3 0 in .)
1
2
3
2
3
3
O U T
0
( 0 .8 3 in .)
2 1 m m
( 0 .3 1 in .)
( 3 .4 4 in .)
IN
2
1 5 0 m m
5
1
0
7
7 3 m m
4
6
8 7 .5 m m
5
0
1 1
7
IN
4
O p e n in g o n ly o n m o d u le
IB S IP C D IO /R 2 4 -1 2 /4 /8 -S F
∅8 m m
1 0
6
( 0 .1 8 in .)
9
( 0 .1 9 in .)
1 3 m m
( 0 .5 1 in .)
U S 2
U S 1
IN
8
3 m m
( 1 .8 9 in .)
∅4 .5 m m
R D
E
( 2 .8 7 in .)
R C
IB D IA G
4 8 m m
1 8 .5 m m
( 2 .1 3 in .)
( 5 .9 1 in .)
5 4 m m
( 0 .7 3 in .)
Housing Dimensions
1
G a s k e t o n ly
fo r S F v e r s io n
3 .0 m m
( 0 .1 2 in .)
6 2 m m
( 2 .4 4 in .)
2 0 .5 m m
( 0 .8 1 in .)
1 4 m m
( 0 .5 5 in .)
5 9 9 2 A 0 0 7
Programming Data
ID code
03hex (03dec)
Length code
01hex
Input address area
2 bytes
Output address area
2 bytes
Parameter channel
(PCP)
0 bytes
Register length (bus)
2 bytes
5992B
9
IBS IP CDIO/R 24-12/4/8(-SF)
Assignment of Inputs to the INTERBUS Process Data Input Word
INTERBUS
reference
Word
"Byte-bit"
view
Byte
Bit
7
6
5
4
3
2
1
0
Module
Connector
5
5
4
4
3
3
2
2
Bit
Channel/input
Word 0
15 14 13 12 11 10
9
8
7
6
5
4
Byte 0
7
6
5
4
3
3
2
1
0
3
2
1
0
7
7
6
6
11 10
9
8
3
2
1
0
2
1
0
Byte 1
2
1
7
6
5
4
Not used
0
Assignment of Outputs to the INTERBUS Process Data Output Word
INTERBUS
reference
Bit
"Byte-bit"
view
Byte
Module
Connector
Bit
Channel/output
10
Word 0
Word
15 14 13 12 11 10
9
8
7
6
5
Byte 0
7
6
5
Not used
4
4
Byte 1
3
2
1
0
1
1
0
0
3
2
1
0
7
6
5
4
3
Not used
5992B
IBS IP CDIO/R 24-12/4/8(-SF)
Technical Data
General
Housing dimensions (width x height x depth)
54 mm x 150 mm x 62 mm
(2.126 in. x 5.906 in. x 2.441 in.)
(without connectors)
Operating mode
Process data operation with one word
Type of sensor connection
4-wire technology
Type of actuator connection
3-wire technology
Total power consumption
See "Power Consumption" table on page 12
Permissible operating temperature
0°C to 55°C (32°F to 131°F)
Permissible storage temperature
-25°C to 70°C (-13°F to +158°F)
Degree of protection
IP65, DIN 40050, IEC 60529
Class of protection
Class 3 VDE 0106; IEC 60536
Humidity (operation)
100% not condensing
Humidity (storage)
95% not condensing
Air pressure (operation)
86 kPa to 108 kPa,
1500 m (4921 ft.) above sea level
Air pressure (storage)
66 kPa to 108 kPa,
3500 m (11483 ft.) above sea level
Isolated groups
Test voltage
Supply voltage US1; sensor supply
500 V AC; 50 Hz for 1 minute
Supply Voltage US2
500 V AC; 50 Hz for 1 minute
Bus logic, incoming and outgoing remote bus
500 V AC; 50 Hz for 1 minute
Preferred mounting position (for SF version)
Mounted on Kempf terminal box
Functional earth ground connection
Via 17-pos. installation remote bus connector
Weight
560 g, typical
Interface
INTERBUS installation remote bus
17-pos. circular connector
Connection of Additional Signals for the SF Version
Spring-cage terminal
Connection capacity (solid, stranded)
5992B
0.14 mm2 - 0.5 mm2 (26 AWG - 20 AWG)
11
IBS IP CDIO/R 24-12/4/8(-SF)
Power Consumption
Voltage for the bus interface
24 V DC (US1)
Current consumption of the bus interface
120 mA, maximum
Voltage for the sensor supply
24 V DC (US1)
Current consumption of the sensors
600 mA, maximum
Total consumption from US1
3.5 W, maximum
Actuator supply voltage (US2)
24 V DC
Module power consumption at US2
2.5 W, maximum
Total power consumption
6.0 W, maximum
Supply Voltage (US1)
Nominal value
24 V DC
Permissible voltage range
18.5 V DC to 32 V DC, ripple included
Permissible ripple
3.6 VPP
Total current consumption at US1
720 mA
Diagnostics
Status indicator on the front of the module
The voltage US1 is looped through the modules and can be tapped from the connection of the
outgoing installation remote bus. The maximum continuous current carrying capacity is 7 A.
Sensor Supply Voltage
Nominal value
US1 minus 1 V
Nominal current
600 mA total; 50 mA per input
Derating
No derating
Protective functions
Electronic overload/short circuit protection
The sensors are grouped in groups of four and each group is supplied by a short-circuit protected
supply.
12
5992B
IBS IP CDIO/R 24-12/4/8(-SF)
Digital Inputs
Number
12 inputs (only in the SF version input 11 is
permanently connected in the module to the
thermostatic switch input on the bottom of the
housing and has no connection to connector 7).
Signal level (DIN 19240): Logic 0
Logic 1
-30 V to +5 V
13 V to 30 V
Delay when changing signal
3 ms, typical
Nominal current per input
3.0 mA at 24 V, typical
Permissible residual current, "0" signal
1.5 mA, typical
Input groups
The inputs for connectors 2 and 3, 4 and 5, and
6 and 7, respectively, are grouped together.
Diagnostics
Status indicator per input.
The failure of the sensor supply is reported via
the bus, and the error message is reset by an
acknowledgment in the host.
Supply Voltage (US2)
Nominal value
24 V DC
Permissible voltage range
18.5 V DC to 32 V DC, ripple included
Permissible ripple
3.6 VPP
Total current consumption at US2
5A
Diagnostics
Status indicator on the front of the module
The voltage US2 is looped through the modules and can be tapped to the connection for the
outgoing remote bus. The maximum continuous current carrying capacity is 7 A.
Digital Outputs
Number
4 outputs; 2 with a nominal current of 2 A per
channel on connector 0; 2 with a nominal current
of 0.5 A per channel on connector 1
Minimum output voltage at nominal current
US2 minus 1 V
Derating
No derating
Concurrent channel derating
None
5992B
13
IBS IP CDIO/R 24-12/4/8(-SF)
Digital Outputs (Continued)
Limitation of the voltage induced on circuit
interruption
Up to -20 V, approximately
Protection when ground connection interrupted
Yes
Maximum leakage current, "0" signal
≤0.8 mA
Protective functions
Electronic short-circuit protection, free running
circuit
Diagnostics
Yellow status indicator for each output; color
changes to red in the event of an error; shortcircuit/overload message via the bus, and
storage in volatile memory on the module; the
error message is reset by an acknowledgment in
the host.
Electromagnetic Compatibility
Emitted interference according to EN 55011
Class A
Immunity to interference according to
EN 61000-4-2; IEC 61000-4-2 (ESD)
Class 3, Criterion 2
Immunity to interference according to
EN 61000-4-3; IEC 61000-4-3
10 V/m; Criterion 1
Immunity to interference according to
EN 61000-4-4; IEC 61000-4-4 (burst)
Class 4; Criterion 2
Immunity to interference according to
EN 61000-4-5 (surge)
Class 2; Criterion 2
Immunity to interference according to
IEC 61000-4-6 (conducted)
10 V
Voltage dips according to NAMUR NE21
0 ms ↔ 20 ms; repeat rate 1 s; criterion 1
Mechanical Capability
Vibration according to IEC 60068-2-6 (operation) 5g; Criterion 1
Shock according to IEC 60068-2-27
30g
Degree of protection
IP65 when mounted; cover unused connectors
with protective caps
14
5992B
IBS IP CDIO/R 24-12/4/8(-SF)
Ordering Data
Description
Order Designation
Order No.
Digital input/output module
IBS IP CDIO/R 24-12/4/8
27 30 06 4
Digital input/output module with special
functions
IBS IP CDIO/R 24-12/4/8-SF
27 30 07 7
Protective caps for unused sensor/actuator
connections (5 pcs.)
IBS IP PROT IO
27 59 91 9
Crimping pliers
CRIMPFOX RC 2,5
12 05 44 8
Remote bus connector:
Male connector, straight
Female connector, straight
Male connector, angled
Female connector, angled
TGGM/CDIO/17-ST
TGGM/CDIO/17-BU
TWGM/CDIO/17-ST
TWGM/CDIO/17-BU
16 67 89 5
16 67 90 5
16 67 95 0
16 67 96 3
Make sure you always use the latest documentation.
It can be downloaded at www.phoenixcontact.com.
5992B
15
© Phoenix Contact 05/2004 Technical modifications reserved TNR 90 02 54 5