IBS RBC SWITCH
INTERBUS
Data Sheet
Remote Bus Switch
Data Sheet Revision A
02/1997
Product Description
The remote bus switch IBS RBC
SWITCH permits to connect a
remote bus topology for reasons
of device availability with a
second, redundant PLC.
Features
- D-SUB 9 remote bus
connectors for two incoming
remote buses and one
outgoing remote bus
- 24 V nominal input voltage
- Pick-up time max. 4 ms
- DIN-rail mounting
Application
- Operation of a bus topology
with two controller boards
that can be used alternatively
Figure 1: IBS RBC SWITCH
5088A
Phoenix Contact GmbH & Co. Postfach 1341 32819 Blomberg Germany
1
Example of an Electrical Installation
Figure 2:Electrical installation example for the IBS RBC SWITCH within an IB ST compact
station.
The length of the remote bus cable must not exceed 400 m for every remote bus segment. The remote bus switch does not start a new remote bus segment.
The switching relays are supplied with a positive coil voltage via terminal A1 and with a
negative coil voltage via terminal A2 (see Figure 3). When the coil voltage is applied the remote
bus switch switches to the first input (IN 1). In the normal state the remote bus input IN 2 is
connected with the remote bus output (OUT).
The connector pin assignments on the input and output side are identical, which means that
pin 1 on the input side is connected to pin 1 on the output side etc. (see Table 1).
In order to reduce the installation times of an INTERBUS system as much as possible, Phoenix Contact offers pre-assembled bus cables (see Phoenix Contact
Catalog Part 11: INTERBUS). Please refer to the INTERBUS Installation Manual
IBS SYS INST UM E (Order No.27 54 80 4) for detailed information on all INTERBUS cable types.
5088A
Phoenix Contact GmbH & Co. Postfach 1341 32819 Blomberg Germany
2
Connection
If the connector is properly installed, the remote bus shielding is continued via the internal
electrical connection of the connector housing.
Figure 3: Connector designations of the IBS RBC SWITCH
Table 1: Pin assignment (remote bus cable with D-SUB, 9-pos.)
Signal
Pin (male)
Pin (female)
DO
1
1
DI
2
2
COM
3
3
nc
4
4
nc
5
5
DO
6
6
DI
7
7
nc
8
8
nc
9
9
Shield
Housing
Housing
Table 2: Ordering data for the IBS RBC SWITCH
Description
Type
Order No.
Remote bus switch (2*IN, 1*OUT)
IBS RBC SWITCH
27 50 02 8
Mounting rail DIN EN 50022, 2 meters
NS 35/7,5 gelocht (perforated)
NS 35/7,5 ungelocht (unperforated)
08 01 68 1
08 01 73 3
5088A
Phoenix Contact GmbH & Co. Postfach 1341 32819 Blomberg Germany
3
Technical Data
General
Type
Air and creepage distances
Permissible operating temperature
Permissible storage temperature
Housing dimensions (w*h*d)
IBS RBC SWITCH
VDE 0110 part1, 01/89
From -20°C to 55°C
From -40°C to 85°C
56 mm * 78 mm * 56 mm (see Figure 1)
Interfaces
- Two incoming remote buses
- Outgoing remote bus
D-SUB male connector, 9-pos.
D-SUB-female connector, 9-pos.
Switching relay
Type
Nominal input voltageUN
Permissible range
Pick-up voltage at 20 °C
Drop-out voltage at 20 °C
Coil resistance
Typical current intake
Pick-up time (with nominal voltage)
Drop-out time (with nominal voltage)
Rebounce time (with nominal voltage)
Test voltage coil/contact
Mechanical life (ohmic load, Tu=20-30 °C)
DS2E-S
24 V
0.8 to 1.1 * UN
16.8 V
2.4 V
2880 Ω ±10%
18 mA
4 ms
4 ms
2 ms
0.5 kV (60 s; 50 Hz)
108 switching operations with 0.1 A and 1 W
High external magnetic fields influence the relay’s characteristics.
Local Diagnostic Indicators
Input voltage
On:
Off:
Input voltage present. Connection to IN 1 established.
In a dead condition the relay switches to the remote
bus input IN 2.
TNR 992 65 87 5
DNR 2540
Yellow LED
5088A
Phoenix Contact GmbH & Co. Postfach 1341 32819 Blomberg Germany
4