https://www.phoenixcontact.com/us/products/2750963
Bus coupler - IBS ST 24 BKM-LK - 2750963
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
INTERBUS-ST bus terminal module, 24 V DC, with optical fiber F-SMA connector, IP20 protection, consisting of:
Terminal part with screw connection and module electronics
Product description
INTERBUS ST standard bus terminal modules
The INTERBUS bus terminal module connects the input/output modules of an ST station with the INTERBUS network.
Depending on the transmission medium used, the bus terminal modules are equipped with different bus connections. For copper conductors, D-SUB
and MINI-COMBICON connectors are available. The fiber optic versions are equipped with F-SMA connectors.
The bus terminal modules are available in two different performance classes. A maximum of 4 or 8 input/output modules can be operated on one bus
terminal module.
The bus terminal module takes on the following functions within a modular INTERBUS-ST station:
- Refreshing the INTERBUS remote bus signals
- Electrical isolation of the remote bus segments
- Decoupling of the outgoing remote bus or of the connected input/ output modules from the INTERBUS network with a software command
- Supply of the connected input/output modules with an electrically isolated voltage supply from an integrated power supply unit
Key commercial data
Packing unit
1 pc
GTIN
Weight per Piece (excluding packing)
256.2 GRM
Custom tariff number
85389091
Country of origin
Germany
Technical data
Dimensions
Width
44 mm
Height
117 mm
Length
116 mm
09/08/2014 Page 1 / 4
https://www.phoenixcontact.com/us/products/2750963
Bus coupler - IBS ST 24 BKM-LK - 2750963
Technical data
Ambient conditions
Degree of protection
IP20
Interfaces
Interface
INTERBUS remote bus (incoming/outgoing)
Connection method
4x F-SMA connector
Transmission speed
500 kBit/s
Interface
ST local bus
Connection method
ST local bus connector
Transmission speed
500 kBit/s
Power supply
Communications supply
9 V DC
Typical current consumption
70 mA (without connected ST I/O modules)
Max. current consumption
300 mA (for max. terminal configuration)
500 mA (of all I/O modules max.)
I/O voltage
24 V DC
I/O voltage range
20 V DC ... 30 V DC
Electrical isolation
Test section
Between supply voltage and ST local bus 500 V AC 50 Hz 1 min
INTERBUS data
Max. number of ST I/O modules
4 (observe total current consumption)
Maximum distance to the next remote bus device
500 m
Programmable functions
Programmable functions
Local bus branch disable
Local bus reset
Remote bus disable (outgoing remote bus)
Remote bus reset
General
Weight
200 g
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
12
09/08/2014 Page 2 / 4
https://www.phoenixcontact.com/us/products/2750963
Bus coupler - IBS ST 24 BKM-LK - 2750963
Classifications
eCl@ss
eCl@ss 4.0
27250203
eCl@ss 4.1
27250203
eCl@ss 5.0
27250203
eCl@ss 5.1
27242608
eCl@ss 6.0
27242608
eCl@ss 7.0
27242608
ETIM
ETIM 2.0
EC001434
ETIM 3.0
EC001604
ETIM 4.0
EC001604
ETIM 5.0
EC001604
UNSPSC
UNSPSC 6.01
43172015
UNSPSC 7.0901
43201404
UNSPSC 11
43172015
UNSPSC 12.01
43201404
UNSPSC 13.2
43201404
Drawings
09/08/2014 Page 3 / 4
https://www.phoenixcontact.com/us/products/2750963
Bus coupler - IBS ST 24 BKM-LK - 2750963
Dimensioned drawing
Connection diagram
117
116
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com
09/08/2014 Page 4 / 4
很抱歉,暂时无法提供与“2750963”相匹配的价格&库存,您可以联系我们找货
免费人工找货