IBS ST (ZF) 24 BK LB-T
Bus Terminal Module With Local Bus Branch
Data Sheet 5049B
4
6
1 5
Terminal Assignment
1 6
7
8
T E R
B
IB S S T 2 4 B K L B -T
U S
U L
R C
B A 1
B A 2
E 1
E 2
L D 1
R D
in
ec
om
po
1
2
R e c o n fig u r a tio n
L D 2
ne
nt
IN
Terminals Assignment
1
Supply voltage of the module
4
Supply voltage of the
reconfiguration input 2 (optional)
6
Supply voltage of the alarm contact
(optional)
8
Supply voltage of the
reconfiguration input 1 (optional)
9
Ground contact of the module
12
Ground contact of the
reconfiguration input 2
14
Ground contact of the alarm contact
16
Ground contact of the
reconfiguration input 1
s.
F
U S
E
1
1 4
m
1 2
5049B000
co
9
09/1999
B u s T e r m in a l, 2 4 V D C
M o d u le Id e n t. 1 : 0 8 , M o d u le Id e n t. 2 : 5 2
R e m o te b u s O U T
on
l
R e m o te b u s IN
Des.
UL
L o c a l b u s b ra n c h
5 0 4 9 B 0 0 1
Figure 1 IBS ST 24 BK LB-T module
This data sheet is intended to be used
in conjunction with the IBS SYS PRO
UM E Manual.
Ground the mounting rail. The module
is grounded by snapping it onto the
mounting rail.
5049B
Local Diagnostic and Status Indicators
Color Meaning
Green Supply voltage for the
electronics module
RC Green Remote bus cable check
BA1/2 Green Remote bus active
E1
Red Error in the ST compact station
(local bus group)
E2
Red Error in the local bus branch
LD1
Red ST compact station (local bus
group) disconnected
LD2
Red Local bus branch disconnected
RD
Red Remote bus disconnected
1
IBS ST (ZF) 24 BK LB-T
Connection Example
Connection of the Supply Voltages and the Bus Cables
U
L
+
U
_
U
R E C 2
_
+
A
+
U
_
R E C 1
+
_
T o b e w ir e d e x te r n a lly
1 3
1 4
1 5
1 6
4
5
6
7
8
F
U S
E
1
1 2
B A 1
B A 2
nt
E 1
E 2
L D 1
L D 2
R D
om
1
2
R e c o n fig u r a tio n
in
ec
F a s te n e le c tr o n ic s m o d u le
w ith s c r e w o n te r m in a l
b lo c k b a s e .
R C
IB S S T 2 4 B K L B -T
U S
po
U L
B
T E R
ne
IN
s.
9
co
m
In te r n a lly c o n n e c te d
B u s T e r m in a l, 2 4 V D C
M o d u le Id e n t. 1 : 0 8 , M o d u le Id e n t. 2 : 5 2
L o c a l b u s
b ra n c h
on
l
R e m o te b u s IN
R e m o te b u s O U T
5 0 4 9 B 0 0 2
Figure 2 Connection of the supply voltage and bus cables
UREC1/2: Voltage supply of the reconfiguration
inputs (optional). These inputs can only be used
together with group definitions. As the terminals
9, 12, and 16 are connected with each other, the
reconfiguration inputs and the power supply are
assigned to the same potential.
2
UL: Power supply for the bus logic
UA: Voltage supply for the alarm input (optional).
5049B
IBS ST (ZF) 24 BK LB-T
Functioning of the Alarm Contact
A la r m
A la r m n o t s e t a n d
IN T E R B U S c o n n e c te d
s e t
1 4
1 4
1 5
1 5
6
5 0 4 9 B 0 0 3
m
6
co
Figure 3 Functioning of the alarm contact
Programming Data
Assignment of the Reconfiguration Inputs
0hex
0 bytes
Output address area
0 bytes
Parameter channel (PCP)
0 bytes
Register length (bus)
0 bytes
Disconnection of the ST
compact station
om
Programmable functions
po
Input address area
Yes
Disconnection of the outgoing
remote bus
Yes
Reset of the outgoing remote
bus
Yes
Monitoring of the incoming
remote bus cable
Yes
Disconnection of local bus
Yes
in
ec
R E C 1
R E C 2
ID :
0 8 (d e c )
ID :
5 2 (d e c )
S T c o m p a c t s ta tio n
L o c a l b u s b ra n c h
Yes
Reset of the ST compact station
on
l
IB S S T 2 4 B K L B -T
ne
Length code
B u s te r m in a l m o d u le
nt
8hex, 8dec
34hex ,52dec
s.
R e m o te b u s IN
ID code
ST compact station
Local bus branch
R e m o te b u s O U T
5 0 4 9 B 0 0 4
Figure 4 Assignment of the reconfiguration
inputs
The bus terminal module and the local
bus branch are programmed like two
individual bus terminal modules.
Therefore, both ID codes must be
entered in the address lists.
5049B
3
IBS ST (ZF) 24 BK LB-T
Technical Data
General
81 mm x 117 mm x 116 mm
(3.189 in. x 4.606 in. x 4.567 in.)
Permissible operating temperature
From 0°C to 55°C (32°F to 131°F)
Permissible storage temperature
From -20°C to 70°C (-4°F to +158°F)
Degree of protection
IP 20, DIN 40050, IEC 60529
Class of protection
Class 3 VDE 0106, IEC 60536
Humidity (operation)
30% to 75%, no condensation
Humidity (storage)
30% to 95%, no condensation
Air pressure (operation)
From 86 to 108 kPa, 1500 m (4921 ft.) above sea
level
Air pressure (storage)
From 66 to 108 kPa, 3500 m (11483 ft.) above
sea level
ne
nt
s.
co
m
Housing dimensions (width x height x depth)
Test voltage
Incoming/outgoing remote bus
Incoming remote bus/local bus branch
Supply voltage/ST local bus
Protective ground
Weight
Interfaces
on
l
INTERBUS
in
ec
Preferred installation position
om
Incoming remote bus/ST local bus
500 V AC, 1 min., 50 Hz
po
Electrical isolation
500 V AC, 1 min., 50 Hz
500 V AC, 1 min., 50 Hz
500 V AC, 1 min., 50 Hz
Panel mounting
Via DIN rail
470 g, typical
Incoming remote bus
9-pos. D-SUB male connector
Outgoing remote bus
9-pos. D-SUB female connector
ST interface
ST cable (supplied with the module)
Local bus
15-pos. D-SUB female connector (supply voltage
is not carried in the local bus branch)
Number of ST modules that can be connected 8 (note the current load)
Maximum distance to the next remote bus
device
400 m (1312 ft.)
Maximum distance to the next local bus device 1.5 m (3.280 ft.)
4
5049B
IBS ST (ZF) 24 BK LB-T
Interfaces
Alarm contact
Terminal points
6, 14, and 15 (see Figure 3)
Maximum voltage
30 V DC/AC
Maximum current
0.5 A
Reconfiguration inputs
Pushbutton 1 (manual operation)
Local bus branch
Pushbutton 2 (manual operation)
Terminal points of the ST compact station
8 (+) and 16 (-)
Terminal points of local bus branch
4 (+) and 12 (-)
Nominal voltage UREC1/2
24 V DC
Permissible voltage range
-30 V to 30 V (DC)
nt
s.
co
m
ST compact station
ne
Set: 13 V to 30 V (DC)
Not set: -30 V to 1 V
Power Consumption
Current consumption of US
om
Communications power
I/O supply voltage Us
2 mA, typical
po
Current consumption (set)
9 V DC
24 V DC
150 mA at 24 V, typical
Maximum
650 mA at 24 V, typical
in
ec
Without ST local bus modules
on
l
Total current consumption of all I/O modules on 800 mA at 9 V, maximum
the ST local bus
I/O Supply Voltage (US)
Nominal value
24 V DC
Permissible ripple
3.6 Vpp within the permissible voltage range
Permissible voltage range (including ripple)
Operation: 20 V DC to 30 V DC
5049B
5
IBS ST (ZF) 24 BK LB-T
I/O Supply Voltage (US)
Current consumption of US
Without ST I/O modules
150 mA at 24 V, typical
Maximum
650 mA at 24 V, typical
Permissible total current consumption of all I/O 800 mA at 9 V, maximum
modules
Fuses in the base element
IBS TR5 1 AT
co
m
Surge voltage protection
s.
Ordering Data
Order Designation
Order No.
BK module (screw-clamp terminals)
IBS ST 24 BK LB-T
27 53 23 2
BK module (spring-clamp terminals)
IBS ST ZF 24 BK LB-T
27 50 77 2
Electronics module
IB STME 24 BK LB-T
27 53 24 5
Replacement terminal block (screw-clamp
terminals)
IB STTB 24 BK LB-T
27 52 69 9
Replacement terminal block (spring-clamp
terminals)
IB STTB ZF 24 BK LB-T
27 50 88 2
on
l
in
ec
om
po
ne
nt
Description
6
5049B
on
l
in
ec
om
po
ne
nt
s.
co
m
IBS ST (ZF) 24 BK LB-T
5049B
7
8
© Phoenix Contact 09/1999 TNR 92 65 66 8
s.
nt
ne
po
om
in
ec
on
l
co
m
IBS ST (ZF) 24 BK LB-T
5049B