https://www.phoenixcontact.com/us/products/2800106
Lightning arrester type 1 - FLT 25-400 - 2800106
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Type 1 / Class I / B arrester (lightning current arrester) with arc chopping spark gap, 1-channel. Housing width:
17.5 mm (1 Div.)
Product Features
High discharge capacity
Single-channel
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
180.0 g
Custom tariff number
85363010
Country of origin
Germany
Technical data
Dimensions
Height
90 mm
Width
17.7 mm
Depth
65.5 mm
Horizontal pitch
1 Div.
Ambient conditions
Degree of protection
IP20 (only when all terminal points are used)
Ambient temperature (operation)
-40 °C ... 85 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Altitude
≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)
5 % ... 95 %
General
IEC power supply system
TN-S
12/02/2015 Page 1 / 4
https://www.phoenixcontact.com/us/products/2800106
Lightning arrester type 1 - FLT 25-400 - 2800106
Technical data
General
TN-C
TT
Housing material
PA 6.6
Flammability rating according to UL 94
V-0
Color
black
Standards for cearances and creepage distances
EN 60664-1
EN 61643-11
Mounting type
DIN rail: 35 mm
Type
Rail-mountable module, one-piece
Number of positions
1
Surge protection fault message
None
Direction of action
1L-N/PE
Protective circuit
IEC test classification
I
T1
EN type
T1
Nominal voltage UN
230/400 V AC (TN)
Maximum continuous operating voltage UC (L-PEN)
440 V AC
UT (TOV-proof)
440 V (5 sec.)
TOV behavior at UT
Nominal frequency fN
50 Hz (60 Hz)
Rated load current IL
80 A
Residual current IPE
≤ 0.1 mA
Standby power consumption PC
≤ 44 mVA
Nominal discharge current In (8/20) µs (L-PEN)
25 kA
Front of wave sparkover voltage at 6 kV (1.2/50) µs
≤ 5 kV
Voltage protection level Up (L-PEN)
≤ 5 kV
Response time tA (L-PE)
≤ 100 ns
Max. backup fuse with branch wiring
250 A AC (gG)
Max. backup fuse with V-type through wiring
80 A AC (gG)
Short-circuit resistance IP with max. backup fuse (effective)
25 kA
Short-circuit current rating ISCCR
2.5 kA
Follow current quenching capacity Ifi (L-PEN)
2.5 kA
Connection, protective circuit
Connection method
Screw connection
Connection type IN
Biconnect screw terminal block
12/02/2015 Page 2 / 4
https://www.phoenixcontact.com/us/products/2800106
Lightning arrester type 1 - FLT 25-400 - 2800106
Technical data
Connection, protective circuit
Connection type OUT
Biconnect screw terminal block
Connection method
Biconnect terminal block
Screw thread
M5
Tightening torque
4.5 Nm
Stripping length
14.5 mm
Conductor cross section flexible min.
2.5 mm²
Conductor cross section flexible max.
25 mm²
Conductor cross section solid min.
2.5 mm²
Conductor cross section solid max.
35 mm²
AWG conductor cross section
6 ... 2
Standards and Regulations
Standards/regulations
IEC 61643-11 2011
EN 61643-11 2012
Classifications
eCl@ss
eCl@ss 4.0
27140201
eCl@ss 4.1
27140201
eCl@ss 5.0
27140201
eCl@ss 5.1
27140201
eCl@ss 6.0
27140201
eCl@ss 7.0
27140201
eCl@ss 8.0
27130802
ETIM
ETIM 2.0
EC000381
ETIM 3.0
EC000381
ETIM 4.0
EC000381
ETIM 5.0
EC000381
UNSPSC
UNSPSC 6.01
30212010
UNSPSC 7.0901
39121610
UNSPSC 11
39121610
UNSPSC 12.01
39121610
UNSPSC 13.2
39121620
12/02/2015 Page 3 / 4
https://www.phoenixcontact.com/us/products/2800106
Lightning arrester type 1 - FLT 25-400 - 2800106
Approvals
Approvals
Approvals
EAC / EAC
Ex Approvals
Approvals submitted
Approval details
EAC
EAC
Drawings
Dimensional drawing
90
Circuit diagram
17,7
L/N ( )
58
65,5
L/N ( )
Phoenix Contact 2015 © - all rights reserved
http://www.phoenixcontact.com
12/02/2015 Page 4 / 4
很抱歉,暂时无法提供与“2800106”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格 香港价格
- 1+3538.295941+442.78032