Type 1 / Class I (lightning current arrester) with arc chopping spark gap and ignition electronics with control lamp,
quenching plates for high mains follow-through current quenching capacity, 1-channel. Protection level: 2.5 kV.
Housing width: 35 mm (2 Div.)
The illustration shows version FLTPLUS CTRL-0,9
Product Features
Good follow current quenching capacity with higher rated voltage
High discharge capacity
Direct parallel connection with type 2 arresters supported
Single-channel
Triggered
Key commercial data
Packing unit
1 pc
Weight per Piece (excluding packing)
560.0 GRM
Custom tariff number
85363010
Country of origin
Germany
Technical data
Dimensions
Height
150 mm
Width
35.5 mm
Depth
80.5 mm
Horizontal pitch
2 Div.
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-40 °C ... 85 °C
Permissible humidity (operation)
≤ 95 %
01/13/2015 Page 1 / 6
https://www.phoenixcontact.com/us/products/2800122
Lightning arrester type 1 - FLT-PLUS CTRL-2.5/I - 2800122
Technical data
General
IEC power supply system
TT
TN-C
TN-S
IT
Housing material
PA-GF
Inflammability class according to UL 94
V0
Color
black
Standards for air and creepage distances
EN 60664-1
EN61643-11
Mounting type
DIN rail: 35 mm
Type
Rail-mountable module, one-piece
Number of positions
1
Surge protection fault message
Optical
Direction of action
1L-N/PE
Protective circuit
IEC test classification
I
T1
EN type
T1
Nominal voltage UN
230 V AC (400 V AC)
Maximum continuous operating voltage UC
440 V AC
Maximum continuous operating voltage UC (L-N)
440 V AC
Maximum continuous operating voltage UC (L-PEN)
440 V AC
UT (TOV-proof)
440 V AC (5 sec.)
UT (TOV-safe)
1640 V AC (200 ms)
Nominal frequency fN
50 Hz
60 Hz
Residual current IPE
≤ 3 mA
Standby power consumption PC
≤ 1.32 VA
Max. discharge current Imax (8/20) µs
50 kA
Nominal discharge current In (8/20) µs
50 kA
Nominal discharge current In (8/20) µs (L-N)
50 kA
Nominal discharge current In (8/20) µs (L-PEN)
50 kA
Impulse discharge current (10/350) µs charge
25 As
Impulse discharge current (10/350)˽µs, specific energy
625 kJ/Ω
Impulse discharge current (10/350)˽µs, peak value limp
50 kA
Front of wave sparkover voltage at 6 kV (1.2/50) µs
≤ 2.5 kV
01/13/2015 Page 2 / 6
https://www.phoenixcontact.com/us/products/2800122
Lightning arrester type 1 - FLT-PLUS CTRL-2.5/I - 2800122
Technical data
Protective circuit
Voltage protection level Up
≤ 2.5 kV
Voltage protection level Up (L-N)
≤ 2.5 kV
Voltage protection level Up (L-PEN)
≤ 2.5 kV
Response time
≤ 100 ns
Response time (L-N)
≤ 100 ns
Response time (L-PEN)
≤ 100 ns
Max. backup fuse with branch wiring
500 A (NH-gL)
Short-circuit resistance IP with max. backup fuse (effective)
25 kA (440 V AC)
50 kA (350 V AC)
Follow current quenching capacity If
25 kA (440 V AC)
50 kA (350 V AC)
Connection, protective circuit
Connection method
Screw connection
Connection type IN
Biconnect screw terminal block
Connection type OUT
Biconnect screw terminal block
Connection method
Biconnect terminal block
Screw thread
M6
Tightening torque
8 Nm
Stripping length
19 mm
Conductor cross section stranded min.
16 mm²
Conductor cross section stranded max.
35 mm²
Conductor cross section solid min.
10 mm²
Conductor cross section solid max.
50 mm²
Conductor cross section AWG/kcmil min.
6
Conductor cross section AWG/kcmil max
1
Standards and Regulations
Standards/regulations
IEC 61643-1 2005
DIN EN 61643-11 2002
DIN EN 61643-11/A11 2007
Classifications
eCl@ss
eCl@ss 4.0
27140201
eCl@ss 4.1
27140201
eCl@ss 5.0
27140201
01/13/2015 Page 3 / 6
https://www.phoenixcontact.com/us/products/2800122
Lightning arrester type 1 - FLT-PLUS CTRL-2.5/I - 2800122
Classifications
eCl@ss
eCl@ss 5.1
27140201
eCl@ss 6.0
27140201
eCl@ss 7.0
27140201
ETIM
ETIM 2.0
EC000381
ETIM 3.0
EC000381
ETIM 4.0
EC000381
ETIM 5.0
EC000381
UNSPSC
UNSPSC 6.01
30212010
UNSPSC 7.0901
39121610
UNSPSC 11
39121610
UNSPSC 12.01
39121610
UNSPSC 13.2
39121620
Approvals
Approvals
Approvals
UL Recognized / KEMA-KEUR / cUL Recognized / GOST / GL / CCA / IECEE CB Scheme / cULus Recognized
Ex Approvals
Approvals submitted
Approval details
UL Recognized
01/13/2015 Page 4 / 6
https://www.phoenixcontact.com/us/products/2800122
Lightning arrester type 1 - FLT-PLUS CTRL-2.5/I - 2800122
Approvals
KEMA-KEUR
cUL Recognized
GOST
GL
CCA
IECEE CB Scheme
cULus Recognized
Drawings
Dimensioned drawing
Circuit diagram
150
L/N( )
L/N( )
51,5
29
45
01/13/2015 Page 5 / 6