Universal varistor-based plug-in lightning/surge arrester for 3-phase power supply networks with separate N and
PE (5-conductor system: L1, L2, L3, N, PE), for Lightning Protection Levels III and IV, with remote indication
contact.
Product Features
■
■
■
■
■
■
Plugs can be checked with CHECKMASTER
With or without floating remote indication contact
Secure hold of plugs in the event of high lightning current loads and strong vibrations thanks to new latching
Optical, mechanical status indication for the individual arresters
Thermal disconnect device for each individual plug
Mechanical coding of all slots
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
660.0 g
Custom tariff number
85363030
Country of origin
Germany
Technical data
Dimensions
Height
99 mm
Width
71.2 mm
Depth
77.5 mm
Horizontal pitch
4 Div.
Ambient conditions
03/08/2016 Page 1 / 8
https://www.phoenixcontact.com/us/products/2800183
Lightning/surge arrester type 1/2 - VAL-MS-T1/T2 335/12.5/3+1FM - 2800183
Technical data
Ambient conditions
Degree of protection
IP20 (only when all terminal points are used)
Ambient temperature (operation)
-40 °C ... 80 °C
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Altitude
≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)
5 % ... 95 %
Shock (operation)
30g (half sinus / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)
7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
General
Standards/specifications
IEC 61643-11 2011
EN 61643-11 2012
IEC test classification
I / II
T1 / T2
T1
EN type
T1 / T2
T1
IEC power supply system
TT
TN-S
Number of ports
One
SPD design
Combination type
Mode of protection
L-N
L-PE
N-PE
Mounting type
DIN rail: 35 mm
Color
jet black RAL 9005
Housing material
PA 6.6
PBT
Degree of pollution
2
Flammability rating according to UL 94
V-0
Type
DIN rail module, two-section, divisible
Surge protection fault message
Optical, remote indicator contact
Protective circuit
Nominal voltage UN
240/415 V AC (TN-S)
240/415 V AC (TT)
Nominal frequency fN
50 Hz (60 Hz)
Maximum continuous operating voltage UC (L-N)
335 V AC
03/08/2016 Page 2 / 8
https://www.phoenixcontact.com/us/products/2800183
Lightning/surge arrester type 1/2 - VAL-MS-T1/T2 335/12.5/3+1FM - 2800183
Technical data
Protective circuit
Maximum continuous operating voltage UC (L-PE)
335 V AC
Maximum continuous voltage UC (N-PE)
264 V AC
Rated load current IL
80 A
Residual current IPE
≤ 5 µA
Standby power consumption PC
≤ 810 mVA
Nominal discharge current In (8/20) µs (L-N)
12.5 kA
Nominal discharge current In (8/20) µs (L-PE)
12.5 kA
Nominal discharge current In (8/20) µs (N-PE)
50 kA
Maximum discharge current Imax (8/20) µs
50 kA
Impulse discharge current (10/350) µs (L-N), charge
6.25 As
Impulse discharge current (10/350) µs (L-N), specific energy
39 kJ/Ω
Impulse discharge current (10/350) µs (L-N), peak current value Iimp
12.5 kA
Impulse discharge current (10/350) µs (L-PE), charge
6.25 As
Impulse discharge current (10/350) µs (L-PE), specific energy
39 kJ/Ω
Impulse discharge current (10/350) µs (L-PE), peak current value Iimp
12.5 kA
Impulse discharge current (10/350) µs (N-PE), charge
25 As
Impulse discharge current (10/350) µs (N-PE), specific energy
625 kJ/Ω
Impulse discharge current (10/350) µs (N-PE), peak current value Iimp
50 kA
Total discharge current ITotal (8/20) µs
50 kA
Total discharge current ITotal (10/350) µs
50 kA
Follow current interrupt rating Ifi (N-PE)
100 A (264 V AC)
Short-circuit current rating ISCCR
25 kA
Voltage protection level Up (L-N)
≤ 1.2 kV
≤ 1.6 kV (30 kA - 8/20µs)
Voltage protection level Up (L-PE)
≤ 2 kV
Voltage protection level Up (N-PE)
≤ 1.7 kV
Residual voltage Ures (L-N)
≤ 1.2 kV (at In)
≤ 1.1 kV (at 10 kA)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 3 kA)
Residual voltage Ures (L-PE)
≤ 2 kV (at In)
≤ 1.5 kV (at 10 kA)
≤ 1.2 kV (at 5 kA)
≤ 1.1 kV (at 3 kA)
Residual voltage Ures (N-PE)
≤ 0.6 kV (at In)
03/08/2016 Page 3 / 8
https://www.phoenixcontact.com/us/products/2800183
Lightning/surge arrester type 1/2 - VAL-MS-T1/T2 335/12.5/3+1FM - 2800183
Technical data
Protective circuit
≤ 0.5 kV (at 10 kA)
≤ 0.5 kV (at 5 kA)
≤ 0.4 kV (at 3 kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs (N-PE)
≤ 1.7 kV
TOV behavior at UT (L-N)
415 V AC (5 s / withstand mode)
457 V AC (120 min / safe failure mode)
TOV behavior at UT (N-PE)
1200 V AC (200 ms / withstand mode)
Response time tA (L-N)
≤ 25 ns
Response time tA (L-PE)
≤ 100 ns
Response time tA (N-PE)
≤ 100 ns
Max. backup fuse with branch wiring
160 A (gG)
Max. backup fuse with V-type through wiring
80 A (gG - 16 mm²)
Indicator/remote signaling
Connection name
Remote fault indicator contact
Switching function
PDT contact
Operating voltage
5 V AC ... 250 V AC
30 V DC
Operating current
5 mA AC ... 1.5 A
1A
Connection method
Screw connection
Screw thread
M2
Tightening torque
0.25 Nm
Stripping length
7 mm
Conductor cross section flexible
0.14 mm² ... 1.5 mm²
Conductor cross section solid
0.14 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Connection data
Connection method
Screw connection
Conductor cross section flexible
1.5 mm² ... 25 mm²
Conductor cross section solid
1.5 mm² ... 35 mm²
Conductor cross section AWG
15 ... 2
Screw thread
M5
Tightening torque
4.5 Nm
Stripping length
16 mm
03/08/2016 Page 4 / 8
https://www.phoenixcontact.com/us/products/2800183
Lightning/surge arrester type 1/2 - VAL-MS-T1/T2 335/12.5/3+1FM - 2800183
Technical data
UL specifications
SPD Type
4CA
Maximum continuous operating voltage MCOV (L-L)
670 V AC
Maximum continuous operating voltage MCOV (L-N)
335 V AC
Maximum continuous operating voltage MCOV (L-G)
335 V AC
Maximum continuous operating voltage MCOV (N-G)
264 V AC
Nom. voltage
240/415 V AC
Mode of protection
L-L
L-N
L-G
N-G
Power distribution system
3Y
Nominal frequency
50/60 Hz
Measured limiting voltage MLV (L-L)
3570 V
Measured limiting voltage MLV (L-N)
2630 V
Measured limiting voltage MLV (L-G)
3600 V
Measured limiting voltage MLV (N-G)
2600 V
Nominal discharge current In (L-L)
20 kA
Nominal discharge current In (L-N)
20 kA
Nominal discharge current In (L-G)
20 kA
Nominal discharge current In (N-G)
20 kA
UL indicator/remote signaling
Operating voltage
125 V AC
Operating current
1A
Tightening torque
4 lbf-in.
Conductor cross section AWG
30 ... 14
UL connection data
Conductor cross section AWG
10 ... 2
Tightening torque
30 lbf-in.
Classifications
eCl@ss
eCl@ss 4.0
27140201
eCl@ss 4.1
27130801
eCl@ss 5.0
27130801
03/08/2016 Page 5 / 8
https://www.phoenixcontact.com/us/products/2800183
Lightning/surge arrester type 1/2 - VAL-MS-T1/T2 335/12.5/3+1FM - 2800183
Classifications
eCl@ss
eCl@ss 5.1
27130801
eCl@ss 6.0
27130802
eCl@ss 7.0
27130802
eCl@ss 8.0
27130802
eCl@ss 9.0
27130802
ETIM
ETIM 2.0
EC000941
ETIM 3.0
EC000941
ETIM 4.0
EC000381
ETIM 5.0
EC000381
UNSPSC
UNSPSC 6.01
30212010
UNSPSC 7.0901
39121610
UNSPSC 11
39121610
UNSPSC 12.01
39121610
UNSPSC 13.2
39121620
Approvals
Approvals
Approvals
KEMA-KEUR / ÖVE / CCA / IECEE CB Scheme / GL / UL Recognized / cUL Recognized / EAC / EAC / cULus Recognized
Ex Approvals
Approvals submitted
Approval details
KEMA-KEUR
03/08/2016 Page 6 / 8
https://www.phoenixcontact.com/us/products/2800183
Lightning/surge arrester type 1/2 - VAL-MS-T1/T2 335/12.5/3+1FM - 2800183
Approvals
ÖVE
CCA
IECEE CB Scheme
GL
UL Recognized
cUL Recognized
EAC
EAC
cULus Recognized
Drawings
03/08/2016 Page 7 / 8
https://www.phoenixcontact.com/us/products/2800183
Lightning/surge arrester type 1/2 - VAL-MS-T1/T2 335/12.5/3+1FM - 2800183
Dimensional drawing
Circuit diagram
22,5
11
FM
70
77,5
45
14
12
99
L2
L3
N
51,5
L1
Application drawing
F2*
F2*
F1
L1
L2
L3
N
PE
F2*
F1
L1
L2
L3
N
PE
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
03/08/2016 Page 8 / 8
很抱歉,暂时无法提供与“2800183”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格 香港价格
- 1+7144.382611+890.06421