https://www.phoenixcontact.com/us/products/2800191
Type 1/2 surge protection plug - F-MS-T1/T2 50 ST - 2800191
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
N-PE replacement plug for VAL-MS-T1/T2 335/12.5 plug-in lighting/surge arrester.
Your advantages
Plugs can be checked with CHECKMASTER
Secure hold of plugs in the event of high lightning current loads and strong vibrations thanks to new latching
Thermal disconnect device for each individual plug
Pluggable
Thermal disconnect device for each individual plug
Mechanical coding of all slots
Key Commercial Data
Packing unit
1 pc
GTIN
GTIN
4046356518628
Weight per Piece (excluding packing)
140.000 g
Custom tariff number
85363030
Country of origin
Germany
Technical data
Dimensions
Height
47 mm
Width
17.7 mm
Depth
67.3 mm
Horizontal pitch
1 Div.
05/02/2021 Page 1 / 7
https://www.phoenixcontact.com/us/products/2800191
Type 1/2 surge protection plug - F-MS-T1/T2 50 ST - 2800191
Technical data
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-40 °C ... 80 °C
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Altitude
≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)
5 % ... 95 %
Shock (operation)
30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)
7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
General
IEC test classification
I / II
T1 / T2
T1
EN type
T1 / T2
T1
IEC power supply system
TT
TN-S
Mode of protection
N-PE
Mounting type
on base element
Color
jet black RAL 9005
Housing material
PA 6.6
PBT
Degree of pollution
2
Flammability rating according to UL 94
V-0
Type
DIN rail module, two-section, divisible
Number of positions
1
Surge protection fault message
optical
Protective circuit
Nominal voltage UN
240/415 V AC (TN-S)
240/415 V AC (TT)
Nominal frequency fN
50 Hz (60 Hz)
Maximum continuous voltage UC
264 V AC
Residual current IPE
≤ 5 µA
Standby power consumption PC
≤ 1.3 mVA
Nominal discharge current In (8/20) µs
50 kA
Maximum discharge current Imax (8/20) µs
50 kA
Impulse discharge current (10/350) µs, charge
25 As
Impulse discharge current (10/350) µs, specific energy
625 kJ/Ω
05/02/2021 Page 2 / 7
https://www.phoenixcontact.com/us/products/2800191
Type 1/2 surge protection plug - F-MS-T1/T2 50 ST - 2800191
Technical data
Protective circuit
Impulse discharge current (10/350) µs, peak value limp
50 kA
Follow current interrupt rating Ifi
100 A (264 V AC)
Voltage protection level Up
≤ 1.7 kV
Residual voltage Ures
≤ 0.6 kV (at In)
≤ 0.5 kV (at 10 kA)
≤ 0.5 kV (at 5 kA)
≤ 0.4 kV (at 3 kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs
≤ 1.7 kV
TOV behavior at UT
1200 V AC (200 ms / withstand mode)
Response time tA
≤ 100 ns
Connection data
Connection method
pluggable
UL specifications
SPD Type
4CA
Maximum continuous operating voltage MCOV (N-G)
264 V AC
Mode of protection
N-G
Power distribution system
Single phase
Nominal frequency
50/60 Hz
Measured limiting voltage MLV (N-G)
2600 V
Nominal discharge current In (N-G)
20 kA
Standards and Regulations
Standards/regulations
IEC 61643-11 2011
EN 61643-11 2012
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings
05/02/2021 Page 3 / 7
https://www.phoenixcontact.com/us/products/2800191
Type 1/2 surge protection plug - F-MS-T1/T2 50 ST - 2800191
Dimensional drawing
17,5
55,3
63,9
47,2
Circuit diagram
Classifications
eCl@ss
eCl@ss 10.0.1
27130890
eCl@ss 11.0
27130890
eCl@ss 4.0
27130800
eCl@ss 4.1
27130800
eCl@ss 5.0
27130800
eCl@ss 5.1
27130800
eCl@ss 6.0
27130800
eCl@ss 7.0
27130802
eCl@ss 9.0
27130890
ETIM
ETIM 2.0
EC000941
ETIM 3.0
EC000941
ETIM 4.0
EC000381
ETIM 6.0
EC000381
ETIM 7.0
EC000381
UNSPSC
UNSPSC 6.01
30212010
UNSPSC 7.0901
39121610
UNSPSC 11
39121610
UNSPSC 12.01
39121610
UNSPSC 13.2
39121620
UNSPSC 18.0
39121620
UNSPSC 19.0
39121620
UNSPSC 20.0
39121620
UNSPSC 21.0
39121620
05/02/2021 Page 4 / 7
https://www.phoenixcontact.com/us/products/2800191
Type 1/2 surge protection plug - F-MS-T1/T2 50 ST - 2800191
Approvals
Approvals
Approvals
DNV GL / CCA / UL Recognized / KEMA-KEUR / cUL Recognized / IECEE CB Scheme / ÖVE / EAC / cULus Recognized
Ex Approvals
Approval details
DNV GL
CCA
https://approvalfinder.dnvgl.com/
TAE00001N9
NTR-AT 1906
UL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 330181
KEMA-KEUR
http://www.dekra-certification.com
2162496-01
cUL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 330181
IECEE CB Scheme
http://www.iecee.org/
AT 2584
ÖVE
https://www.ove.at/zertifizierung-pz/zertifizierungsregister/
18583-009-07
05/02/2021 Page 5 / 7
https://www.phoenixcontact.com/us/products/2800191
Type 1/2 surge protection plug - F-MS-T1/T2 50 ST - 2800191
Approvals
EAC
cULus Recognized
RU CDE.*09.B.00169
Accessories
Accessories
Bridge
Wiring bridge end cover - MPB 18/3- D - 2809322
End cover for lateral connection of wiring bridges, 3-phase
Device marking
Zack marker strip - ZBN 18:UNBEDRUCKT - 2809128
Zack marker strip, Strip, white, unlabeled, can be labeled with: CMS-P1-PLOTTER, PLOTMARK, mounting type: snap
into tall marker groove, for terminal block width: 18 mm, lettering field size: 18 x 5 mm, Number of individual labels: 5
Feed-through terminal block
Feed-through terminal block - DK-BIC-35 - 2749880
Feed-through terminal block for VAL and FLT applications
Labeled device marker
05/02/2021 Page 6 / 7
https://www.phoenixcontact.com/us/products/2800191
Type 1/2 surge protection plug - F-MS-T1/T2 50 ST - 2800191
Accessories
Marker for terminal blocks - ZBN 18,LGS:ERDE - 2749589
Marker for terminal blocks, Strip, white, labeled, horizontal: Grounding symbol, mounting type: snap into tall marker
groove, for terminal block width: 18 mm, lettering field size: 18 x 5 mm, Number of individual labels: 5
Marker for terminal blocks - ZBN 18,LGS:L1-N,ERDE - 2749576
Marker for terminal blocks, Strip, white, labeled, horizontal: L1, L2, L3, N, GND, mounting type: snap into tall marker
groove, for terminal block width: 18 mm, lettering field size: 18 x 5 mm, Number of individual labels: 5
Marker pen
Marker pen - B-STIFT - 1051993
Marker pen, for manual labeling of unprinted Zack strips, smear-proof and waterproof, line thickness 0.5 mm
Phoenix Contact 2021 © - all rights reserved
http://www.phoenixcontact.com