https://www.phoenixcontact.com/us/products/2801146
Type 1/2 surge protection plug - VAL-MS-T1/T2 75/12.5 ST - 2801146
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Replacement plug for VAL-MS-T1/T2 75/12.5... plug-in lighting/surge arrester.
Key commercial data
Packing unit
1 pc
Weight per Piece (excluding packing)
75.0 GRM
Custom tariff number
85363030
Country of origin
Germany
Technical data
Dimensions
Height
47 mm
Width
17.7 mm
Depth
67.3 mm
Horizontal pitch
1 Div.
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-40 °C ... 80 °C
Altitude
≤ 2000 m (NN)
General
Housing material
PBT / PA
Inflammability class according to UL 94
V0
Color
black
Standards for air and creepage distances
DIN EN 60664-1
EN 61643-11
Mounting type
On base element
Type
Male
Number of positions
1
06/30/2014 Page 1 / 4
https://www.phoenixcontact.com/us/products/2801146
Type 1/2 surge protection plug - VAL-MS-T1/T2 75/12.5 ST - 2801146
Technical data
General
Surge protection fault message
Optical
Direction of action
L-N / L-PEN
Protective circuit
IEC test classification
I / II
T1 / T2
EN type
T1 / T2
Nominal voltage UN
60 V DC
Maximum continuous operating voltage UC
75 V DC
Maximum continuous operating voltage UC (L-N)
75 V DC
UT (TOV-proof)
100 V DC (5 s)
Standby power consumption PC
≤ 140 mVA
Max. discharge current Imax (8/20) µs
50 kA
Nominal discharge current In (8/20) µs
12.5 kA
Impulse discharge current (10/350) µs charge
6.25 As
Impulse discharge current (10/350)˽µs, specific energy
39.00 kJ/Ω
Impulse discharge current (10/350)˽µs, peak value limp
12.5 kA
Voltage protection level Up
≤ 0.7 kV
Residual voltage
≤ 0.7 kV
≤ 0.65 kV (at 10 kA)
≤ 0.6 kV (at 5 kA)
≤ 0.55 kV (at 3 kA)
Response time
≤ 25 ns
Max. required backup fuse with branch wiring
160 A
Short-circuit resistance IP with max. backup fuse (effective)
500 A
Connection, protective circuit
Connection type IN
FLASHTRAB/VALVETRAB plug-in system
Connection type OUT
FLASHTRAB/VALVETRAB plug-in system
Standards and Regulations
Standards/regulations
IEC 61643-1 2005
EN 61643-11/A11 2007
UL 1449 ed. 3
06/30/2014 Page 2 / 4
https://www.phoenixcontact.com/us/products/2801146
Type 1/2 surge protection plug - VAL-MS-T1/T2 75/12.5 ST - 2801146
Classifications
eCl@ss
eCl@ss 4.0
27140201
eCl@ss 4.1
27130801
eCl@ss 5.0
27130801
eCl@ss 5.1
27130801
eCl@ss 6.0
27130802
eCl@ss 7.0
27130802
eCl@ss 8.0
27130802
ETIM
ETIM 3.0
EC000941
ETIM 4.0
EC000381
ETIM 5.0
EC000381
UNSPSC
UNSPSC 6.01
30212010
UNSPSC 7.0901
39121610
UNSPSC 11
39121610
UNSPSC 12.01
39121610
UNSPSC 13.2
39121620
Approvals
Approvals
Approvals
UL Recognized / cUL Recognized / cULus Recognized
Ex Approvals
Approvals submitted
Approval details
UL Recognized
06/30/2014 Page 3 / 4
https://www.phoenixcontact.com/us/products/2801146
Type 1/2 surge protection plug - VAL-MS-T1/T2 75/12.5 ST - 2801146
Approvals
cUL Recognized
cULus Recognized
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com
06/30/2014 Page 4 / 4
很抱歉,暂时无法提供与“2801146”相匹配的价格&库存,您可以联系我们找货
免费人工找货