Surge protection in the one-piece 6.2 mm DIN rail module for one floating signal circuit in 2-wire technology.
Tested according to the protection types in Ex areas Ex ia IIC/Ex iaD. HART-compatible.
Product Features
Can be used in binary, analog, and intrinsically safe circuits
Protection of up to four signal wires over a design width of 6.2 mm
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
60.0 g
Custom tariff number
85363010
Country of origin
Germany
Technical data
Dimensions
Height
93 mm
Width
6.2 mm
Depth
102.5 mm
Ambient conditions
Ambient temperature (operation)
-40 °C ... 80 °C
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Degree of protection
IP20
General
Housing material
PBT
02/09/2016 Page 1 / 5
https://www.phoenixcontact.com/us/products/2804610
Surge protection device - LIT 1X2-24 - 2804610
Technical data
General
Flammability rating according to UL 94
V-0
Color
black
Standards for cearances and creepage distances
IEC 60664-1
EN 60079-11
Mounting type
DIN rail: 35 mm
Type
Rail-mountable module, one-piece
Direction of action
Line-Line & Line-Earth Ground
Protective circuit
IEC test classification
C1
C2
C3
D1
Nominal voltage UN
24 V DC
Maximum continuous voltage UC
25 V AC
36 V DC
Nominal current IN
350 mA (40°C)
Operating effective current IC at UC
≤ 2 µA
Standby power consumption PC
≤ 970 mVA
Residual current IPE
≤ 2 µA
Nominal discharge current In (8/20) µs (Core-Core)
5 kA
Nominal discharge current In (8/20) µs (Core-Earth)
5 kA
10 kA (Total)
Total surge current (8/20) µs
20 kA
Total surge current (10/350) µs
1 kA
Max. discharge current Imax (8/20) µs maximum (Core-Core)
10 kA
Max. discharge current Imax (8/20) µs maximum (Core-Earth)
10 kA
20 kA (Total)
Nominal pulse current Ian (10/1000) µs (Core-Core)
50 A
Nominal pulse current Ian (10/1000) µs (Core-Earth)
50 A
100 A (Total)
Impulse discharge current (10/350)˽µs, peak value limp
500 A
Output voltage limitation at 1 kV/µs (Core-Core) spike
≤ 60 V
Output voltage limitation at 1 kV/µs (Core-Earth) spike
≤ 650 V
Residual voltage at In (conductor-conductor)
≤ 70 V
Residual voltage with Ian (10/1000)µs (conductor-conductor)
≤ 50 V
Voltage protection level Up (core-core)
≤ 70 V (C2 - 10 kV / 5 kA)
02/09/2016 Page 2 / 5
https://www.phoenixcontact.com/us/products/2804610
Surge protection device - LIT 1X2-24 - 2804610
Technical data
Protective circuit
≤ 50 V (C3 - 10 A)
≤ 80 V (D1 - 500 A)
Voltage protection level Up (core-ground)
≤ 650 V (C1 - 500 V / 250 A)
≤ 700 V (C2 - 10 kV / 5 kA)
≤ 700 V (D1 - 500 A)
Response time tA (Core-Core)
≤ 1 ns
Response time tA (Core-Earth)
≤ 100 ns
Input attenuation aE, sym.
typ. 0.7 dB (1 MHz / 50 Ω)
typ. 0.3 dB (350 kHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 50 Ohm system
typ. 6 MHz
Cut-off frequency fg (3 dB), sym. in 150 Ohm system
typ. 2 MHz
Capacity
≤ 1.3 nF (per channel)
Resistance in series
3.3 Ω 20 %
Max. required back-up fuse
315 mA
Impulse durability (conductor-conductor)
C2 - 10 kV/5 kA
C3 - 25 A
Impulse durability (conductor-ground)
C2 - 10 kV/5 kA
C3 (25 A)
D1 (500 A)
Alternating current carrying capacity (conductor-ground)
5A-1s
Connection data
Connection method
Screw connection
Connection type IN
Screw terminal blocks
Connection type OUT
Screw terminal blocks
Screw thread
M3
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section solid min.
0.14 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section AWG min.
26
Conductor cross section AWG max.
12
Connection, equipotential bonding
Connection method
DIN rail NS35
Standards and Regulations
Standards/regulations
IEC 61643-21
02/09/2016 Page 3 / 5
https://www.phoenixcontact.com/us/products/2804610
Surge protection device - LIT 1X2-24 - 2804610
Technical data
Standards and Regulations
DIN EN 61643-21
Classifications
eCl@ss
eCl@ss 4.0
27140201
eCl@ss 4.1
27130801
eCl@ss 5.0
27130801
eCl@ss 5.1
27130801
eCl@ss 6.0
27130807
eCl@ss 7.0
27130807
eCl@ss 8.0
27130807
ETIM
ETIM 2.0
EC000943
ETIM 3.0
EC000943
ETIM 4.0
EC000943
ETIM 5.0
EC000943
UNSPSC
UNSPSC 6.01
30212010
UNSPSC 7.0901
39121610
UNSPSC 11
39121610
UNSPSC 12.01
39121610
UNSPSC 13.2
39121620
Approvals
Approvals
Approvals
UL Listed / GL / EAC / EAC
Ex Approvals
IECEx / ATEX / INMETRO
02/09/2016 Page 4 / 5
https://www.phoenixcontact.com/us/products/2804610
Surge protection device - LIT 1X2-24 - 2804610
Approvals
Approvals submitted
Approval details
UL Listed
GL
EAC
EAC
Drawings
Application drawing
Field
Application drawing
protected
Non-Ex
area
Ex area
Controller
0-20mA
LIT 1X2...
LINETRAB
IN
OUT
IN
OUT
Galvanic isolator
barrier
Grounding
Dimensional drawing
102,5
93,1
Circuit diagram
6,2
IN
7
OUT
8
5
6
3
4
1
2
Phoenix Contact 2016 © - all rights reserved