Differential current converter for type A differential current monitor.
Product Features
Residual current detection characteristics type A (50/60 Hz)
Detects pulsating DC and AC residual currents
Adjustable residual response current of 30 mA to 3 A
Adjustable pre-alarm threshold and delay time
Actual residual current can be read via LED display
Remote signaling for main and pre-alarm
Residual current monitoring devices act as a form of fire prevention
Key commercial data
Packing unit
1 pc
Custom tariff number
85043180
Country of origin
Germany
Technical data
Dimensions
Height
220 mm
Width
33 mm
Depth
196 mm
Diameter converter
140.00 mm
Outside diameter of cables max.
93.00 mm
Ambient conditions
Degree of protection
IP20 (terminal blocks)
IP45 (housing)
Ambient temperature (operation)
-20 °C ... 65 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
10/17/2014 Page 1 / 4
https://www.phoenixcontact.com/us/products/2806090
Differential current monitoring - RCM-A-SCT-140 - 2806090
Technical data
General
Housing material
Polycarbonate
Mounting type
Screw mounting
Common characteristics
Rated current In
350 A
Rated response differential current Idyn
3A
Differential current acquisition characteristic
Type A (50 / 60 Hz)
Response differential current IΔn
0.03 A ... 3 A
Thermal permanent differential current Icth
1.5 x In
Thermal rated short-time differential current Ith
10 x In (for 1 s)
Rated surge voltage resistance Uimp
8 kV
Surge voltage category
IV
Rated voltage Un
690 V
Pollution degree
2
Max. overcurrent as regards the non-resolution
6 x In
Rated differential short-circuit current IΔc
10 kA
Rated surge differential current Idyn
25 x In
Connections
Connection method
Screw terminal blocks
Number of connections
2
Stripping length
8 mm
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
4 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
12
Cable/line name
Converter supply line
Maximum cable length
10 m
Cross section
0.5 mm²
Cable type
LiY
Standards and Regulations
Standards/specifications
DIN EN 62020
VDE 0663
DIN EN 60044-1
VDE 0414
10/17/2014 Page 2 / 4
https://www.phoenixcontact.com/us/products/2806090
Differential current monitoring - RCM-A-SCT-140 - 2806090
Classifications
eCl@ss
eCl@ss 4.0
27210902
eCl@ss 4.1
27210902
eCl@ss 5.0
27210902
eCl@ss 5.1
27210902
eCl@ss 6.0
27210902
eCl@ss 7.0
27210902
eCl@ss 8.0
27210902
ETIM
ETIM 2.0
EC001505
ETIM 3.0
EC001505
ETIM 4.0
EC002048
ETIM 5.0
EC002048
UNSPSC
UNSPSC 6.01
30211501
UNSPSC 7.0901
39121019
UNSPSC 11
39121006
UNSPSC 12.01
39121006
UNSPSC 13.2
39121006
Approvals
Approvals
Approvals
VDE Zeichengenehmigung
Ex Approvals
Approvals submitted
Approval details
10/17/2014 Page 3 / 4
https://www.phoenixcontact.com/us/products/2806090
Differential current monitoring - RCM-A-SCT-140 - 2806090
Approvals
VDE Zeichengenehmigung
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com
10/17/2014 Page 4 / 4
很抱歉,暂时无法提供与“2806090”相匹配的价格&库存,您可以联系我们找货
免费人工找货