MINI MCR-SL-U-UI
Configurable 3-way isolating amplifier
Data sheet
101744_en_05
1
© PHOENIX CONTACT 2012-01-05
Description
The 6.2 mm wide MINI MCR-SL-U-UI(-SP)(-NC) configurable Features
3-way isolating amplifier is used to electrically isolate, condi– Configurable 3-way isolating amplifier
tion, amplify, and filter standard signals.
– Input and output signal range configurable via DIP
On the input side, 0 ... 24 V and 0 ... 30 V signals can be proswitches
cessed.
– Approval for Ex-zone 2 (nA)
The standard analog signals 0 ... 20 mA, 4 ... 20 mA, 0 ... 10 V,
– Screw or spring-cage connection can be provided
2 ... 10 V, 0 ... 5 V or 1 ... 5 V are available electrically isolated
– Can be supplied configured or unconfigured
on the output side.
The DIP switches, which can be accessed on the side of the
housing, are used to configure the input and output signal
ranges.
The power supply (19.2..30 V DC) can be supplied either via
connection terminal blocks "3"/"4" or "7"/"8" on the modules
or in conjunction with the DIN rail connector. Please refer to
the section titled "Power supply" for more information.
Attention: Correct usage in potentially explosive areas
The module is a category 3 item of electrical equipment. It is absolutely vital to follow the instructions provided
here during installation and observe the information in the "Safety regulations and installation notes".
Make sure you always use the latest documentation.
It can be downloaded from the product at www.phoenixcontact.net/catalog.
This data sheet is valid for all products listed on the following page:
MINI MCR-SL-U-UI
2
Table of contents
1
Description .............................................................................................................................. 1
2
Table of contents ..................................................................................................................... 2
3
Ordering data .......................................................................................................................... 3
3.1
Order key .......................................................................................................................... 3
4
Technical data ......................................................................................................................... 4
5
Safety regulations and installation notes.................................................................................. 6
5.1
Installation notes ................................................................................................................. 6
5.2
Installation in the Ex area (zone 2)............................................................................................ 6
6
Installation ............................................................................................................................... 7
6.1
Connection notes ................................................................................................................ 7
6.2
Structure ........................................................................................................................... 7
6.3
Block diagram ..................................................................................................................... 7
6.4
Power supply ...................................................................................................................... 7
6.5
Assembly........................................................................................................................... 8
6.6
Connecting the wires ............................................................................................................ 8
7
Configuration ........................................................................................................................... 9
7.1
Configuration table ............................................................................................................... 9
8
Adjustment .............................................................................................................................. 9
9
Connection/application example ........................................................................................... 10
101744_en_05
PHOENIX CONTACT
2
MINI MCR-SL-U-UI
3
Ordering data
Description
Type
Order No.
Pcs. / Pkt.
MCR 3-way isolation amplifier, with configurable input/output, for electrical
isolation and conversion of analog signals up to 30 V, with screw connection, order configuration
MINI MCR-SL-U-UI
2864053
1
MCR 3-way isolation amplifier, with configurable input/output, for electrical MINI MCR-SL-U-UI-SP
isolation and conversion of analog signals up to 30 V, with spring-cage connection, order configuration
2811213
1
MCR 3-way isolation amplifier, with configurable input/output, for electrical
isolation and conversion of analog signals up to 30 V, with screw connection, standard configuration
2865007
1
MCR 3-way isolation amplifier, with configurable input/output, for electrical MINI MCR-SL-U-UI-SP-NC
isolation and conversion of analog signals up to 30 V, with spring-cage connection, standard configuration
2810078
1
Accessories
Type
Order No.
Pcs. / Pkt.
DIN rail connector (TBUS), 5-pos., for bridging the supply voltage, can be
snapped onto NS 35/... DIN rails according to EN 60715
ME 6,2 TBUS-2 1,5/5-ST-3,81 GN
2869728
10
MCR power terminal block for supplying several MINI Analog modules via
the DIN rail connectors, with screw connection, current consumption up to
max. 2 A
MINI MCR-SL-PTB
2864134
1
MCR power terminal block for supplying several MINI-ANALOG modules MINI MCR-SL-PTB-SP
via the DIN rail connectors, with spring-cage connection, current consumption up to max. 2 A
2864147
1
Eight MINI analog signal converters with screw connection method can be
connected to a control system using a system adapter and system cabling
with a minimum of wiring and very low error risk.
MINI MCR-SL-V8-FLK 16-A
2811268
1
DIN rail power supply unit, primary-switched mode, slim design, output: 24
V DC / 1.5 A
MINI-SYS-PS-100-240AC/24DC/1.5
2866983
1
DIN rail power supply unit, primary-switched mode, slim design, output: 24
V DC / 1.5 A, ATEX approval
MINI-PS-100-240AC/24DC/1.5/EX
2866653
1
Label for extended marking of MINI MCR modules in connection with the
MINI MCR-DKL
MINI MCR-DKL-LABEL
2810272
10
Fold up transparent cover for MINI MCR modules with additional labeling
option using insert strips and flat Zack marker strip 6.2 mm
MINI MCR DKL
2308111
10
3.1
MINI MCR-SL-U-UI-NC
Order key
(standard configuration entered as example)
Input
Order No.
2864053
2864053 =
...-U-UI
/
Output
IN39
IN38
IN39
2811213 =
...-U-UI-SP
101744_en_05
= 0 ... 24 V
= 0 ... 30 V
/
Factory calibration certificate
OUT01
OUT01
OUT02
OUT03
OUT04
OUT05
OUT06
=
=
=
=
=
=
0 ... 20 mA
4 ... 20 mA
0 ... 10 V
2 ... 10 V
0 ... 5 V
1 ... 5 V
/
NONE
NONE
= Without factory
PHOENIX CONTACT
3
MINI MCR-SL-U-UI
4
Technical data
Input
Configurable/programmable
Yes, preconfigured
Voltage input signal
0 V ... 24 V
0 V ... 30 V
Max. voltage input signal
50 V DC
Input resistance of voltage input
Approx. 125 kΩ (0 ... 24 V)
Approx. 155 kΩ (0 ... 30 V)
Output
Voltage output signal
0 V ... 10 V
0 V ... 5 V
1 V ... 5 V
2 V ... 10 V
Max. voltage output signal
≤ 12.5 V
Non-load voltage
≤ 12.5 V
Current output signal
0 mA ... 20 mA
4 mA ... 20 mA
Max. current output signal
28 mA
Configurable/programmable
Yes, preconfigured
Short-circuit current
≤ 22 mA
Load/output load voltage output
> 10 kΩ
Ripple
< 20 mVPP (at 500 Ω)
Load/output load current output
< 500 Ω (at 20 mA)
Supply
Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (to bridge the supply voltage, the DIN rail connector (ME
6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used. It can be
snapped onto a 35 mm DIN rail according to EN 60715)
Max. current consumption
< 19 mA (at 24 V DC incl. load)
Power consumption
< 450 mW
General data
Limit frequency (3 dB)
Approx. 100 Hz
Measuring principle
Signal isolator
Maximum transmission error
< 0.1 % (of final value)
< 0.4 % (Without adjustment)
Temperature coefficient, typical
< 0.002 %/K
Maximum temperature coefficient
< 0.01 %/K
Step response (10-90%)
Approx. 3.5 ms
Electrical isolation
Basic insulation according to EN 61010
Surge voltage category
II
Mounting position
Any
Degree of protection
IP20
Pollution degree
2
Rated insulation voltage
50 V AC/DC
Test voltage, input/output/supply
1.5 kV (50 Hz, 1 min.)
Dimensions W / H / D
6.2 mm / 93.1 mm / 102.5 mm
Type of housing
PBT green
101744_en_05
PHOENIX CONTACT
4
MINI MCR-SL-U-UI
Connection data
Screw connection
Spring-cage conn.
Conductor cross section, solid
0.2 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm²
Conductor cross section, stranded
0.2 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm²
Stripping length
12 mm
8 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 65 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Conformance with EMC Directive 2004/108/EC
Noise immunity according to EN 61000-6-2
Noise emission according to EN 61000-6-4
Conformance / approvals
Conformance
CE-compliant
ATEX
II 3 G Ex nA IIC T4 Gc X
UL, USA / Canada
UL 508 Recognized
UL, USA / Canada
Class I, Div. 2, Groups A, B, C, D T5
Shipbuilding
GL EMC 2 D
101744_en_05
PHOENIX CONTACT
5
MINI MCR-SL-U-UI
5
Safety regulations and installation notes
5.1
Installation notes
–
–
–
–
–
The category 3 device is suitable for installation in the
zone 2 potentially explosive area. It fulfills the requirements of EN 60079-0:2009 and EN 60079-15:2010.
Installation, operation, and maintenance may only be carried out by qualified electricians. Follow the installation instructions described. When installing and operating the
device, the applicable regulations and safety directives
(including national safety directives), as well as general
technical regulations, must be observed. The technical
data is provided in this package slip and on the certificates (conformity assessment, additional approvals
where applicable).
It is not permissible to open or modify the device. Do not
repair the device yourself but replace it with an equivalent
device. Repairs may only be carried out by the manufacturer. The manufacturer is not liable for damage resulting
from violation.
The IP20 degree of protection (IEC 60529/EN 60529) of
the device is intended for use in a clean and dry environment. Do not subject the device to any load that exceeds
the described limits.
The device is not designed for use in atmospheres with a
danger of dust explosions.
101744_en_05
5.2
–
–
–
–
–
–
Installation in the Ex area (zone 2)
Observe the specified conditions for use in potentially explosive areas.
The device must be installed in a housing (control or distributor box) which meets the requirements of EN 6007915 and provides at least IP54 (EN 60529) degree of protection.
During installation and when connecting the supply and
signal circuits, observe the requirements of EN 6007914. Devices may only be connected to circuits in zone 2 if
they are suitable for operation in Ex zone 2 and for the
prevailing conditions at the place of use.
In potentially explosive areas, terminals may only be
snapped onto or off the DIN rail connector and wires may
only be connected or disconnected when the power is
switched off.
The device must be stopped and immediately removed
from the Ex area if it is damaged, has been subjected to
an impermissible load, has been stored incorrectly, or if it
malfunctions.
You can download the latest documents for these devices from www.phoenixcontact.net/catalog.
PHOENIX CONTACT
6
MINI MCR-SL-U-UI
6.3
6
Installation
6.1
Connection notes
Block diagram
Attention: Electrostatic discharge!
OUT U
The device contains components that can be
damaged or destroyed by electrostatic discharge. When handling the device, observe the
necessary safety precautions against electrostatic discharge (ESD) according to EN 613405-1 and EN 61340-5-2.
6.2
US
OUT
IN
Sensor / Field
1
+ 1
IN U
PLC / DCS
OUT U,I
5 +
5
active
4-wire
GND
2
– 2
+ 3
– 4
passive
GND 2
GND 1
6 –
+24V
+24V
GND 3
6
7 +
GND 3
8 –
Structure
+24V
GND 3
2
3
Zone 2
y
an
rm
Ge UI
rg,
be –UI– 3
lom –SL 38
B
4
le
5 CR 6
ab
82
r
r plifie
I Mo.: 28
V
gu
nfi Am )...5
6
N
MIN
Co ting V,0(2
d.–
Or 1
la
10
Iso (2)...
,0
A
ld
m
ON
/ Fie
..20
o
).
sr
(4
S2 FF
2 N
Sen
0V/0
O
O
F
...3
49° 1
,0
1
C
V
.+
4 D
F
OF
...2 0V 4°..
US
T
OU
S1
: 0 ...3 / –
wire
UT 19,2 5°C
1 U,I 46
IN/O
+
°...+
,I 1
–20
IN U
2 GND
b
Tam
1 2
32
5
PLC
S
/ DC
+
5
,I
TU
OU
5 active
D2
GN
- 6
sive
pas
6
www.phoenixcontact.com
+
6
7
- 8
V
+24
1
-
G G
II 3 A II C T4
Ex n
OL
Power supply
ATTENTION:
cX
R
NT
CO
S
S
ES NT OU
OC E D ZN
PR UIPMAZAR 31
EQR HIONS 2, T5
FOCAT iv.
LO I, D ,C,D
src
A,B
r
C l. s.
pw
Grp max 2
s
mA las
16 e C
Us
D3
GN
Block diagram
6
+
+24 3
D3 4
GN
Figure 2
6.4
D
GN
3
V
+24 GND
ial
Ser
Warning – Do n ot seperate
when energized
Div. 2
4
No.
7
10
9
8
Never connect the supply voltage directly to the
DIN rail connector. It is not permitted to draw
power from the DIN rail connector or from individual modules.
Supply via the module
Where the total current consumption of the aligned modules
does not exceed 400 mA, the power can be supplied directly
at the connection terminal blocks of the module.
A 400 mA fuse should be connected upstream.
Figure 1
Structure
Supply via a power terminal block
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
Input
Cover
Potentiometer for adjustment
Groove for ZBF 6 zack marker strip
Output: Standard signals
Supply voltage
Connection option for DIN rail connector
Universal snap-on foot for EN DIN rails
DIP switch S2
DIP switch S1
101744_en_05
The MINI MCR-SL-PTB power terminal block (Order No.
2864134) or the MINI MCR-SL-PTB-SP power terminal block
(Order No. 2864147), which are the same shape, are used to
feed the supply voltage to the DIN rail connector.
A 2 A fuse should be connected upstream.
Supply via a system power supply unit
The system power supply unit with 1.5 A output current connects the DIN rail connector to the supply voltage and can
therefore be used to supply several modules from the mains.
– MINI-SYS-PS-100-240AC/24DC/1.5 (Order No.
2866983)
– Potentially explosive areas:
MINI-PS-100-240AC/24DC/1.5/EX (Order No. 2866653)
PHOENIX CONTACT
7
MINI MCR-SL-U-UI
6.5
Assembly
Screw connection:
B
A
B
A
D
www.interface.phoenixcontact.com
C
E
Figure 4
•
•
Figure 3
–
6.6
Insert the wire into the corresponding connection terminal
block.
Use a screwdriver to tighten the screw in the opening
above the connection terminal block.
Spring-cage connection:
Mount the module on a 35 mm DIN rail according to EN
60715.
When using the DIN rail connector, first place it into the
DIN rail (see A – C). It is used to bridge the power supply.
It is also absolutely vital that you snap the module and the
DIN rail connector into position in the correct direction:
the snap-on foot should be at the bottom and the connector on the left.
A
B
Connecting the wires
The MINI MCR-SL-U-UI... is available with two types of connection:
– Screw terminal blocks (MINI MCR-SL-U-UI)
– Spring-cage terminal blocks (MINI MCR-SL-U-UI-SP)
Figure 5
•
•
101744_en_05
Screw connection
www.interface.phoenixcontact.com
–
Mounting and removing
X
XXX
XXX
o. X
al N
Seri
X
XXX
XXX
o. X
al N
Seri
Spring-cage connection
Insert a screwdriver into the opening above the connection terminal block.
Insert the wire into the corresponding connection terminal
block.
PHOENIX CONTACT
8
MINI MCR-SL-U-UI
7
Configuration
NC version
The MINI MCR-SL-U-UI-NC and MINI MCR-SL-U-UI-SP-NC
modules feature the default configuration:
– Input 0...30 V
– Output 0...20 mA
(All DIP switches are set to the "off" position, transmission
error < 0.1 %.)
DIP switches
DIP switches S1 and S2 are used to specify the combination
of input and output standard signal ranges (see "Configuration table").
7.1
Configuration table
DIP S2
OUT
1
2
3
4
5
6
1
2
0 ... 30 V
0...20 mA
off
off
off
off
off
off
off
off
4...20 mA
off
off
off
off
off
ON
off
off
0...10 V
ON
off
ON
off
off
off
off
off
2...10 V
ON
off
ON
off
off
ON
off
off
0...5 V
ON
ON
off
off
off
off
off
off
1...5 V
ON
ON
off
off
off
ON
off
off
0 ... 24 V
8
DIP S1
IN
0...20 mA
off
off
off
off
off
off
ON
off
4...20 mA
off
off
off
off
off
ON
ON
off
0...10 V
ON
off
ON
off
off
off
ON
off
2...10 V
ON
off
ON
off
off
ON
ON
off
0...5 V
ON
ON
off
off
off
off
ON
off
1...5 V
ON
ON
off
off
off
ON
ON
off
Adjustment
A potentiometer is located underneath the cover; this is used
for fine adjustment of the analog signals once the configuration of the DIP switches has been modified.
Once the configuration of the DIP switches has
been modified, the potentiometer allows the
accuracy to be increased from < 0.4% to <
0.1%.
The module is adjusted via its output final value:
•
•
Connect the calibration source to the input of the isolating
amplifier and specify the final value of the set input signal.
Use the potentiometer to set the exact final value of the
set output signal.
101744_en_05
PHOENIX CONTACT
9
MINI MCR-SL-U-UI
9
Connection/application example
0...24V
0...10V
IN U
OUT
GND1
GND2
1
5
UPS
2
3
4
6
UB +
UB+
GND3
GND3
MINI MCR-SL-U-UI
Control system
7
8
24V
Mains voltage
Figure 6
101744_en_05
Example application
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
www.phoenixcontact.com
10