MCR-SL-S-...00-U(I)-(LP)
Current Measuring Transducer for Sinusoidal
and Non-Sinusoidal Alternating Currents
INTERFACE
Data Sheet
© PHOENIX CONTACT - 05/2006
Description
The MCR-SL-S-... current measuring transducers provide
the user with the opportunity of retrofitting the current measuring transducer in an existing system without interruption.
This is made possible by an open up coil that functions on
the Rogowski principle. Insulated conductors on the primary
side with a diameter of up to 18.5 mm can be embraced.
The current measuring transducers are electrically isolated
from one another on the input and output side.
The MCR-SL-S-...-I-LP current measuring transducers convert sinusoidal and non-sinusoidal alternating currents up to
400 A into the analog standard signal of 4...20 mA. The
measuring range at the output is set with a switch. On the
output side, the current measuring transducers are operated in a 4...20 mA current loop, which simultaneously provides the power supply for the modules, which is necessary
for signal conversion.
The MCR-SL-S-...-U current measuring transducers convert sinusoidal and non-sinusoidal alternating currents up to
400 A into analog standard signals of 0...5 V or 0...10 V.
The measuring ranges for input and output can be selected
via a switch.
IN
IN
I
U
I
POWER
I
OUT
OUT
POWER
.
Make sure you always use the latest documentation.
It can be downloaded at www.download.phoenixcontact.com.
A conversion table is available on the Internet at
www.download.phoenixcontact.com/general/7000_en_00.pdf.
This data sheet is valid for all products listed on the following page:
102504_04_en
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
Phone: +49-(0) 5235-3-00 • Fax: +49-(0) 5235-3-4 12 00 • www.phoenixcontact.com
www.phoenixcontact.com/salesnetwork
1
MCR-SL-S-...00-U(I)-(LP)
Ordering Data
Description
Order No.
Pcs./Pkt
MCR current measuring transducer, for measuring sinusoidal and non-sinu- MCR-SL-S-100-U
soidal alternating currents, input current 0...100 A, output voltage 0...(5) 10 V
Type
2813457
1
MCR current measuring transducer, for measuring sinusoidal and non-sinu- MCR-SL-S-200-U
soidal alternating currents, input current 0...200 A, output voltage 0...(5) 10 V
2813460
1
MCR current measuring transducer, for measuring sinusoidal and non-sinu- MCR-SL-S-400-U
soidal alternating currents, input current 0...400 A, output voltage 0...(5) 10 V
2813473
1
MCR current measuring transducer, for measuring sinusoidal and nonsinusoidal alternating currents, input current 0...100 A, loop-powered output
with 4...20 mA
MCR-SL-S-100-I-LP
2813486
1
MCR current measuring transducer, for measuring sinusoidal and nonsinusoidal alternating currents, input current 0...200 A, loop-powered output
with 4...20 mA
MCR-SL-S-200-I-LP
2813499
1
MCR current measuring transducer, for measuring sinusoidal and nonsinusoidal alternating currents, input current 0...400 A, loop-powered output
with 4...20 mA
MCR-SL-S-400-I-LP
2813509
1
Technical Data
General Data
MCR-SL-S-...-U
Supply voltage
MCR-SL-S-...-I-LP
20 V DC ... 30 V DC
Current consumption
< 30 mA
–
< ±1% of end value
Transmission error
Cable position error
< 0.63%
Temperature coefficient
< 0.035%/K
< 0.025%/K
Step response (10% ... 90%)
< 340 ms
Degree of protection
IP20
Test voltage
5 kV, 50 Hz, 1 min.
Ambient temperature range
-20°C ... +60°C
Dimensions (W x H x D)
55 mm x 67 mm x 85 mm
0.2 mm 2 ... 2.5 mm2
Conductor cross section
Housing design
Polyamide PA non-reinforced, green
c compliant
Electromagnetic compatibility
Input
MCR-SL-S-100...
MCR-SL-S-200...
Input current
0 A AC ... 100 A AC
0 A AC ... 200 A AC
0 A AC ... 400 A AC
Measuring range
0 A ... 50/75/100 A
0 A ... 100/150/200 A
0 A ... 200/300/400 A
Response threshold
1% of end value
Frequency range
30 Hz ... 6000 Hz
Curve type
MCR-SL-S-400...
Sinusoidal and non-sinusoidal
Overload capacity (continuous)
No limitation
Surge strength (for 1 s)
No limitation
Connection method
Clamp-on cable design for 18.5 mm ∅ (insulated conductor)
Output
MCR-SL-S-...-U
MCR-SL-S-...-I-LP
0 V ... (5)10 V
4 mA ... 20 mA
Output signal
Max. output signal
7 V (0...5 V); 14 V (0...10 V)
25 mA
≥ 10 kΩ
(UB - 12 V) / 20 mA
Load
Approvals
UL/C-UL Listed UL 508
Yes
UL/C-UL Listed UL 1604 Class I, Division 2
In preparation
102504_04_en
PHOENIX CONTACT
2
MCR-SL-S-...00-U(I)-(LP)
Features
–
–
–
–
–
Can be retrofitted with the open up Rogowski coil
Choice of voltage or current output
Measuring range selection with slide switch
True r.m.s. value measurement from 30 Hz ... 6000 Hz
Clamp-on cable design for 18.5 mm ∅ (insulated
conductor)
Block Diagrams
MCR-SL-S-...00-U
MCR-SL-S-...00-I-LP
OUT
OUT
IN
=
=
GND
OUT
+24V
Current Measurement
+
24V
U
IN
I
OUT
+24V
Current Monitoring
383A
-
+
24V
-
4...20mA
UB=24V
MCR-SL-S-...-U
0...5V
0...10V
MCR-SL-S-...-I-LP
L1
L1
L2
L3
Figure 1
L2
L3
Current measurement
Figure 2
Current monitoring
© PHOENIX CONTACT 05/2006
102504_04_en
PHOENIX CONTACT
3