https://www.phoenixcontact.com/us/products/2813525
Signal conditioner - MINI MCR-SL-U-I-4 - 2813525
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
MCR 3-way isolating amplifier, for electrical isolation of analog signals, with screw connection, input signal: 0 V ...
10 V, output signal: 4 mA ... 20 mA
Product Features
■
■
■
■
■
■
Power supply possible via the foot element (TBUS)
Entry-level alternative to configurable signal conditioners
Low power consumption
Highly-compact isolating amplifier for electrical isolation, conversion, amplification, and filtering of standard analog signals
Fixed signal combinations
3-way isolation
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
71.6 g
Custom tariff number
85437090
Country of origin
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
6.2 mm
Height
93.1 mm
Depth
102.5 mm
05/16/2016 Page 1 / 6
https://www.phoenixcontact.com/us/products/2813525
Signal conditioner - MINI MCR-SL-U-I-4 - 2813525
Technical data
Ambient conditions
Ambient temperature (operation)
-20 °C ... 65 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Maximum altitude
≤ 2000 m
Degree of protection
IP20
Input data
Number of inputs
1
Configurable/programmable
no
Voltage input signal
0 V ... 10 V
Max. input voltage
30 V
Input resistance of voltage input
approx. 100 kΩ
Output data
Number of outputs
1
Configurable/programmable
no
Current output signal
4 mA ... 20 mA
Max. output current
28 mA
Load/output load current output
≤ 500 Ω
Power supply
Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2
1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply
voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Max. current consumption
< 20 mA
Power consumption
< 450 mW
Connection data
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section AWG min.
26
Conductor cross section AWG max.
12
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Stripping length
12 mm
Screw thread
M3
General
No. of channels
1
Maximum transmission error
≤ 0.1 % (of final value)
05/16/2016 Page 2 / 6
https://www.phoenixcontact.com/us/products/2813525
Signal conditioner - MINI MCR-SL-U-I-4 - 2813525
Technical data
General
Maximum temperature coefficient
< 0.01 %/K
Temperature coefficient, typical
< 0.002 %/K
Limit frequency (3 dB)
approx. 100 Hz
Step response (10-90%)
approx. 3.5 ms
Electrical isolation
Basic insulation according to EN 61010
Overvoltage category
II
Degree of pollution
2
Rated insulation voltage
50 V AC/DC
Test voltage, input/output/supply
1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be minimal
deviations.
Color
green
Housing material
PBT
Mounting position
any
Assembly instructions
The T connector can be used to bridge the supply voltage. It can be
snapped onto a 35 mm DIN rail according to EN 60715.
Conformance
CE-compliant
ATEX
II 3 G Ex nA IIC T4 Gc X
UL, USA / Canada
UL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T5 applied for
GL
GL EMC 2 D
EMC data
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Typical deviation from the measuring range final value
5%
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Typical deviation from the measuring range final value
5%
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Typical deviation from the measuring range final value
5%
Standards and Regulations
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Connection in acc. with standard
CUL
05/16/2016 Page 3 / 6
https://www.phoenixcontact.com/us/products/2813525
Signal conditioner - MINI MCR-SL-U-I-4 - 2813525
Technical data
Standards and Regulations
Standards/regulations
EN 61000-4-2
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Electrical isolation
Basic insulation according to EN 61010
Conformance
CE-compliant
ATEX
II 3 G Ex nA IIC T4 Gc X
UL, USA / Canada
UL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T5 applied for
GL
GL EMC 2 D
Classifications
eCl@ss
eCl@ss 4.0
27210120
eCl@ss 4.1
27210120
eCl@ss 5.0
27210120
eCl@ss 5.1
27210120
eCl@ss 6.0
27210120
eCl@ss 7.0
27210120
eCl@ss 8.0
27210120
eCl@ss 9.0
27210120
ETIM
ETIM 2.0
EC001485
ETIM 3.0
EC001485
ETIM 4.0
EC001485
ETIM 5.0
EC002653
UNSPSC
UNSPSC 6.01
30211506
UNSPSC 7.0901
39121008
UNSPSC 11
39121008
UNSPSC 12.01
39121008
UNSPSC 13.2
39121008
05/16/2016 Page 4 / 6
https://www.phoenixcontact.com/us/products/2813525
Signal conditioner - MINI MCR-SL-U-I-4 - 2813525
Approvals
Approvals
Approvals
UL Recognized / cUL Recognized / GL / EAC / cULus Recognized
Ex Approvals
ATEX
Approvals submitted
Approval details
UL Recognized
cUL Recognized
GL
EAC
cULus Recognized
Drawings
05/16/2016 Page 5 / 6
https://www.phoenixcontact.com/us/products/2813525
Signal conditioner - MINI MCR-SL-U-I-4 - 2813525
Block diagram
Dimensional drawing
93,1
1
+ 1
IN U
OUT I
5 +
5
active
4-wire
GND
2
– 2
+ 3
– 4
passive
GND 2
GND 1
6 –
+24V
+24V
GND 3
6,2
PLC / DCS
6
7 +
GND 3
8 –
102,5
OUT U
US
OUT
IN
Sensor / Field
+24V
GND 3
Zone 2
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
05/16/2016 Page 6 / 6
很抱歉,暂时无法提供与“2813525”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格 香港价格
- 1+2801.445271+362.40972