Temperature measuring transducer - MCR-T-UI-NC
2814100
https://www.phoenixcontact.com/us/products/2814100
Please be informed that the data shown in this PDF document is generated from our Online Catalog. Please find the complete data in the user
documentation. Our General Terms of Use for Downloads are valid.
MCR-T module, programmable temperature transducer, unconfigured, for thermocouple sensors and
resistance temperature detectors, in 2-, 3- or 4-conductor technology
Your advantages
• Freely programmable via MCR/PI-CONF-WIN
• With transistor switching output
• Inverse output signal ranges as an option
• For resistance thermometers and thermocouples
• Measure differential temperatures
Commercial Data
Item number
2814100
Packing unit
1 pc
Minimum order quantity
1 pc
Note
Made to Order (non-returnable)
Sales Key
C01
Product Key
CK1821
Catalog Page
Page 136 (C-7-2013)
GTIN
4017918139421
Weight per Piece (including packing)
140.5 g
Weight per Piece (excluding packing)
118.5 g
Customs tariff number
85437090
Country of origin
DE
Oct 18, 2022, 4:23 PM
Page 1 (9)
Temperature measuring transducer - MCR-T-UI-NC
2814100
https://www.phoenixcontact.com/us/products/2814100
Technical Data
Product properties
Product type
Temperature transmitter
Electrical properties
Typical cold point errors
1.5 K
Cold point error, max.
≤3K
Maximum power dissipation for nominal condition
1.52 W
Test voltage input/output
1 kV AC (50 Hz, 60 s)
Test voltage input/power supply
1 kV AC (50 Hz, 60 s)
Maximum temperature coefficient
≤ 0.01 %/K
Temperature coefficient, typical
0.005 %/K
Maximum transmission error
≤ 0.1 % (of maximum range, ±6 mV or ±12 µA at output)
Supply
Supply voltage range
18 V DC ... 30 V DC
Typical current consumption
40 mA
Max. current consumption
≤ 60 mA
Input data
Signal:
Input signal
Temperature
Measurement
Configurable/programmable
Yes, unconfigured
Sensor types (RTD) that can be used
Pt, Ni, Cu sensors
Sensor types that can be used (TC)
U, T, L, J, E, K, N, S, R, B, C, W, HK
Temperature measuring range
Depending on sensor type used
Temperature measuring range
min. 20 K (RTD, excluding CU10 - 100 K)
min. 50 K (TC, except type B 100 K)
Sensor type:
-200 °C ... 850 °C (freely adjustable)
-60 °C ... 180 °C (freely adjustable)
-70 °C ... 500 °C (freely adjustable)
-50 °C ... 160 °C (freely adjustable)
-50 °C ... 200 °C (freely adjustable)
-50 °C ... 180 °C (freely adjustable)
-55 °C ... 150 °C (freely adjustable)
-200 °C ... 600 °C (freely adjustable)
-200 °C ... 400 °C (freely adjustable)
-200 °C ... 900 °C (freely adjustable)
-210 °C ... 1200 °C (freely adjustable)
-226 °C ... 1000 °C (freely adjustable)
-200 °C ... 1372 °C (freely adjustable)
Oct 18, 2022, 4:23 PM
Page 2 (9)
Temperature measuring transducer - MCR-T-UI-NC
2814100
https://www.phoenixcontact.com/us/products/2814100
-200 °C ... 1300 °C (freely adjustable)
-50 °C ... 1760 °C (freely adjustable)
-50 °C ... 1760 °C (freely adjustable)
500 °C ... 1820 °C (freely adjustable)
-18 °C ... 2316 °C (freely adjustable)
-18 °C ... 2316 °C (freely adjustable)
-200 °C ... 800 °C (freely adjustable)
-200 °C ... 850 °C (freely adjustable)
-200 °C ... 850 °C (freely adjustable)
-200 °C ... 850 °C (freely adjustable)
-200 °C ... 850 °C (freely adjustable)
-60 °C ... 180 °C (freely adjustable)
-60 °C ... 180 °C (freely adjustable)
-60 °C ... 180 °C (freely adjustable)
-60 °C ... 180 °C (freely adjustable)
Sensor input current
250 µA (resistance thermometer)
Linear resistance measuring range
0 Ω ... 8000 Ω (freely adjustable, min. measuring range 100 Ω)
Linear mV signal range
-20 mV ... 2400 mV (freely adjustable, minimum measuring range
span of 10 mV)
Connection technology
2-, 3-, 4-conductor
Connection method
Pluggable screw connection
Protective circuit
Transient protection
Surge protection 30 V DC
Output data
Frequency:
Configurable/programmable
no
Switching: Transistor
Output description
Can carry a load of 100 mA, switches supply voltage (not
protected against short-circuit); locked in case of order-specific
configuration, otherwise freely programmable through MCR/PICONF-WIN
Continuous load current
100 mA
Output voltage range
18 V DC ... 30 V DC (switches supply voltage, not short-circuit
resistant)
Signal:
Configurable/programmable
Yes, unconfigured
Voltage output signal
0 V ... 10 V
0 V ... 5 V
-5 V ... 5 V
-10 V ... 10 V
10 V ... 0 V
5 V ... 0 V
10 V ... -10 V
Oct 18, 2022, 4:23 PM
Page 3 (9)
Temperature measuring transducer - MCR-T-UI-NC
2814100
https://www.phoenixcontact.com/us/products/2814100
5 V ... -5 V
1 V ... 5 V
Max. voltage output signal
± 12 V
Current output signal
0 mA ... 20 mA
4 mA ... 20 mA
20 mA ... 0 mA
20 mA ... 4 mA
Max. current output signal
24 mA
Output voltage range with wire break
-12 V ... 12 V
Output voltage range with overrange/underrange
-12 V ... 12 V
Output current range with wire break
0 A ... 24 mA
Output current range with overrange/underrange
0 A ... 24 mA
Load/output load voltage output
≥ 10 kΩ
Load/output load current output
≤ 500 Ω
Ripple
< 20 mVPP
Protective circuit
Transient protection
D/A converter resolution
± 12 bit
Connection data
Connection method
Pluggable screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section solid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Dimensions
Dimensional drawing
Width
17.5 mm
Height
99 mm
Depth
114.5 mm
Material specifications
Housing material
Polyamide PA non-reinforced
Environmental and real-life conditions
Ambient conditions
Ambient temperature (operation)
-20 °C ... 65 °C
Oct 18, 2022, 4:23 PM
Page 4 (9)
Temperature measuring transducer - MCR-T-UI-NC
2814100
https://www.phoenixcontact.com/us/products/2814100
Approval data
CE
Certificate
CE-compliant
UL, USA / Canada
Identification
Class I, Div. 2, Groups A, B, C, D or Non-Hazardous Locations
GL
Identification
DNV GL
Mounting
Mounting type
DIN rail mounting
Mounting position
any
Oct 18, 2022, 4:23 PM
Page 5 (9)
Temperature measuring transducer - MCR-T-UI-NC
2814100
https://www.phoenixcontact.com/us/products/2814100
Drawings
Dimensional drawing
17,5
114,5
99
Circuit diagram
Oct 18, 2022, 4:23 PM
Page 6 (9)
Temperature measuring transducer - MCR-T-UI-NC
2814100
https://www.phoenixcontact.com/us/products/2814100
Classifications
ECLASS
ECLASS-9.0
27210129
ECLASS-10.0.1
27210129
ECLASS-11.0
27210129
Oct 18, 2022, 4:23 PM
Page 7 (9)
Temperature measuring transducer - MCR-T-UI-NC
2814100
https://www.phoenixcontact.com/us/products/2814100
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the
manufacturer’s declaration available under “Downloads”
Oct 18, 2022, 4:23 PM
Page 8 (9)
Temperature measuring transducer - MCR-T-UI-NC
2814100
https://www.phoenixcontact.com/us/products/2814100
Accessories
Adapter cable
Adapter cable - MCR-TTL-RS232-E - 2814388
https://www.phoenixcontact.com/us/products/2814388
Software adapter cable (Stereo jack connector/D-SUB 25-pos.), 1.2 m length, for
programming MCR-T-..., MCR-S-... and MCR-f-... modules
Cable
Cable - CM-KBL-RS232/USB - 2881078
https://www.phoenixcontact.com/us/products/2881078
Connecting cable D-9-SUB to USB, with adapter D-9-SUB to D-25-SUB.
Phoenix Contact 2022 © - all rights reserved
https://www.phoenixcontact.com
Phoenix Contact USA
586 Fulling Mill Road
Middletown, PA 17057, United States
(+717) 944-1300
info@phoenixcon.com
Oct 18, 2022, 4:23 PM
Page 9 (9)