MCR 3-way signal conditioner, for galvanic isolation of analog signals, input signal: 0 ... 10 V /
(+/-) 10 V, output signal: 0 ... 10 V / (+/-)10 V. Replacement part: 2902042 MINI MCR-2-U-U.
Your advantages
• 3-way isolation
• Processing of standard signals
• Fixed setting of input and output signals
Commercial Data
Item number
2814469
Packing unit
1 pc
Minimum order quantity
1 pc
Note
Made to Order (non-returnable)
Sales Key
C01
Product Key
CK1811
Catalog Page
Page 131 (C-7-2013)
GTIN
4017918156169
Weight per Piece (including packing)
79.88 g
Weight per Piece (excluding packing)
74.96 g
Customs tariff number
85437090
Country of origin
DE
Oct 27, 2022, 7:27 AM
Page 1 (9)
Signal conditioner - MCR-C-U-U-DC
2814469
https://www.phoenixcontact.com/us/products/2814469
Technical Data
Notes
Utilization restriction
EMC note
EMC: class A product, see manufacturer's declaration in the
download area
Product properties
Product type
Signal conditioner
No. of channels
1
Electrical properties
No. of channels
1
Electrical isolation between input and output
yes
Limit frequency (3 dB)
30 Hz
Maximum power dissipation for nominal condition
450 mW
Test voltage, input/output/supply
1.5 kV AC (50 Hz, 60 s)
Protective circuit
Transient protection
Step response (10-90%)
11 ms
Maximum temperature coefficient
< 0.015 %/K
Maximum transmission error
≤ 0.2 % (of final value)
Transmission error, typical
< 0.1 % (of final value)
Supply
Supply voltage range
20 V DC ... 30 V DC
Typical current consumption
< 15 mA (without load)
Input data
Signal:
Description of the input
Voltage input
Number of inputs
1
Configurable/programmable
no
Voltage input signal
0 V ... 10 V
-10 V ... 10 V
Max. voltage input signal
30 V
Input resistance of voltage input
100 kΩ
Output data
Signal:
Number of outputs
1
Configurable/programmable
no
Voltage output signal
0 V ... 10 V
-10 V ... 10 V
Oct 27, 2022, 7:27 AM
Page 2 (9)
Signal conditioner - MCR-C-U-U-DC
2814469
https://www.phoenixcontact.com/us/products/2814469
Max. voltage output signal
15 V
Load/output load voltage output
≥ 10 kΩ
Linear transmission range (in reference to the output range end
value)
-110 % ... 110 % (Bipolar signals)
Connection data
Connection method
Pluggable screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section solid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Interfaces
Data communication (bypass)
Limit frequency (3 dB)
30 Hz
Dimensions
Dimensional drawing
Width
12.5 mm
Height
99 mm
Depth
114.5 mm
Material specifications
Housing material
Polyamide PA non-reinforced
Environmental and real-life conditions
Ambient conditions
Ambient temperature (operation)
-25 °C ... 60 °C
Approval data
CE
Certificate
CE-compliant
Mounting
Mounting type
DIN rail mounting
Mounting position
any
Oct 27, 2022, 7:27 AM
Page 3 (9)
Signal conditioner - MCR-C-U-U-DC
2814469
https://www.phoenixcontact.com/us/products/2814469
Drawings
Dimensional drawing
99
114,5
12,5
Circuit diagram
IN
IN I/U 1
GND 1 2
OUT
U,
U
5 OUT I/U
6 GND 2
7 +20...30V
8 GND 3
Oct 27, 2022, 7:27 AM
Page 4 (9)
Signal conditioner - MCR-C-U-U-DC
2814469
https://www.phoenixcontact.com/us/products/2814469
Approvals
cUL Recognized
UL Recognized
Approval ID: FILE E 238705
Approval ID: FILE E 238705
EAC
Approval ID: RU*DE.*08.B.01536/19
cULus Recognized
Oct 27, 2022, 7:27 AM
Page 5 (9)
Signal conditioner - MCR-C-U-U-DC
2814469
https://www.phoenixcontact.com/us/products/2814469
Classifications
ECLASS
ECLASS-9.0
27210120
ECLASS-10.0.1
27210120
ECLASS-11.0
27210120
ETIM
ETIM 8.0
EC002653
UNSPSC
UNSPSC 21.0
39121000
Oct 27, 2022, 7:27 AM
Page 6 (9)
Signal conditioner - MCR-C-U-U-DC
2814469
https://www.phoenixcontact.com/us/products/2814469
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the
manufacturer’s declaration available under “Downloads”
Oct 27, 2022, 7:27 AM
Page 7 (9)
Signal conditioner - MCR-C-U-U-DC
2814469
https://www.phoenixcontact.com/us/products/2814469
Accessories
Wire bridge
Wire bridge - DB 50- 90 GY - 2820929
https://www.phoenixcontact.com/us/products/2820929
Flexible wire loop bridge, 50-pos., conductor cross-section: 0.5 mm2, loop length:
90 mm, ferrule length: 8 mm, color: gray
Wire bridge
Wire bridge - DB 50- 90 BK - 2820916
https://www.phoenixcontact.com/us/products/2820916
Flexible wire loop bridge, 50-pos., conductor cross-section: 0.5 mm2, loop length:
90 mm, ferrule length: 8 mm, color: black
Oct 27, 2022, 7:27 AM
Page 8 (9)
Signal conditioner - MCR-C-U-U-DC
2814469
https://www.phoenixcontact.com/us/products/2814469
Wire bridge
Wire bridge - DB 50- 90 BU - 2821180
https://www.phoenixcontact.com/us/products/2821180
Flexible wire loop bridge, 50-pos., conductor cross-section: 0.5 mm2, loop length:
90 mm, ferrule length: 8 mm, color: blue
Phoenix Contact 2022 © - all rights reserved
https://www.phoenixcontact.com
Phoenix Contact USA
586 Fulling Mill Road
Middletown, PA 17057, United States
(+717) 944-1300
info@phoenixcon.com
Oct 27, 2022, 7:27 AM
Page 9 (9)