https://www.phoenixcontact.com/us/products/2814715
Current transducers - MCR-S-1-5-UI-DCI-NC - 2814715
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
MCR current transducer, programmable and configurable, for measuring direct, alternating and distorted currents,
input current 0...0.2 to 0...11 A, unconfigured
The illustration shows version MCRS-1-5-UI-DCI
Product Features
■
■
■
True r.m.s. value measurement
Device can be set via DIP switches or MCR/PI-CONF-WIN configuration software
3-way isolation
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
192.1 g
Custom tariff number
85437090
Country of origin
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
22.5 mm
Height
99 mm
Depth
114.5 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 60 °C
03/13/2016 Page 1 / 6
https://www.phoenixcontact.com/us/products/2814715
Current transducers - MCR-S-1-5-UI-DCI-NC - 2814715
Technical data
Ambient conditions
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Degree of protection
IP20
Input data
Input
Current measuring input
Number of inputs
3
Configurable/programmable
Yes, unconfigured
Input current range
0 A ... 11 A (AC/DC)
Operate threshold
2 % (of measuring range nominal value 1/5/10 A)
Setting range for min. input current
0 A ... 200 mA
Setting range for max. input current
0 A ... 11 A
Impulse form
AC, DC or distorted currents
Overload capacity
2 x IN (continuous)
Surge strength
20 x IN (1 s)
Frequency measuring range
15 Hz ... 400 Hz
Connection method
Screw connection
Output data
Output name
Voltage output / current output
Configurable/programmable
Yes, unconfigured
Voltage output signal
0 V ... 10 V
2 V ... 10 V
-10 V ... 10 V
0 V ... 5 V
1 V ... 5 V
-5 V ... 5 V
10 V ... 0 V
10 V ... 2 V
10 V ... -10 V
5 V ... 0 V
5 V ... 1 V
5 V ... -5 V
Current output signal
0 mA ... 20 mA
4 mA ... 20 mA
20 mA ... 0 mA
20 mA ... 4 mA
Load/output load voltage output
> 10 kΩ
Load/output load current output
< 500 Ω
03/13/2016 Page 2 / 6
https://www.phoenixcontact.com/us/products/2814715
Current transducers - MCR-S-1-5-UI-DCI-NC - 2814715
Technical data
Switching output
Output name
No switching output
Power supply
Supply voltage range
20 V DC ... 30 V DC
Max. current consumption
< 40 mA (without load)
Connection data
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Stripping length
8 mm
Screw thread
M3
General
Maximum transmission error
< 0.5 % (of nominal range value under nominal conditions)
Temperature coefficient, typical
< 0.025 %/K
Step response (10-90%)
330 ms (with AC)
40 ms (with DC)
Status display
Green LED
Overvoltage category
III
Degree of pollution
2
Rated insulation voltage
300 V AC (to earth)
Test voltage input/output
4 kV (50 Hz, 1 min.)
Test voltage input/power supply
4 kV (50 Hz, 1 min.)
Test voltage output/power supply
500 V (50 Hz, 1 min.)
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Noise emission
EN 61000-6-4
Noise immunity
EN 61000-6-2
Color
green
Housing material
Polyamide PA non-reinforced
Mounting position
any
Conformance
CE-compliant
UL, USA / Canada
Class I, Zone 2, AEx nC IIC T6, Ex nC IIC T6
Standards and Regulations
03/13/2016 Page 3 / 6
https://www.phoenixcontact.com/us/products/2814715
Current transducers - MCR-S-1-5-UI-DCI-NC - 2814715
Technical data
Standards and Regulations
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Noise emission
EN 61000-6-4
Noise immunity
EN 61000-6-2
Connection in acc. with standard
CUL
Low Voltage Directive
Conformance with Low Voltage Directive 2006/95/EC
Conformance
CE-compliant
UL, USA / Canada
Class I, Zone 2, AEx nC IIC T6, Ex nC IIC T6
Classifications
eCl@ss
eCl@ss 4.0
27200303
eCl@ss 4.1
27200303
eCl@ss 5.0
27200303
eCl@ss 5.1
27200303
eCl@ss 6.0
27200303
eCl@ss 7.0
27142316
eCl@ss 8.0
27210123
eCl@ss 9.0
27210123
ETIM
ETIM 2.0
EC001440
ETIM 3.0
EC001440
ETIM 4.0
EC001440
ETIM 5.0
EC002475
UNSPSC
UNSPSC 6.01
30211506
UNSPSC 7.0901
39121008
UNSPSC 11
39121008
UNSPSC 12.01
39121008
UNSPSC 13.2
39121008
Approvals
Approvals
03/13/2016 Page 4 / 6
https://www.phoenixcontact.com/us/products/2814715
Current transducers - MCR-S-1-5-UI-DCI-NC - 2814715
Approvals
Approvals
UL Recognized / cUL Recognized / EAC / cULus Recognized
Ex Approvals
UL Listed / cUL Listed / cULus Listed
Approvals submitted
Approval details
UL Recognized
cUL Recognized
EAC
cULus Recognized
Drawings
Dimensional drawing
99
Dimensional drawing
22,5
22,5
114,5
114,5
99
03/13/2016 Page 5 / 6
https://www.phoenixcontact.com/us/products/2814715
Current transducers - MCR-S-1-5-UI-DCI-NC - 2814715
Circuit diagram
5
6
7
12 1
11 2
14 3
NC 4
OUT
DAC
µC
SPAN
8
IN
ADC
SET
TIME POINT ZERO
10A
5A
1A
OUT
I
DAC
U
Po
wer
=
9 O UT I
10 O UT U
11 GND 2
12 GND 2
13 24VDC
14 GND 1
15 SW
16 GND 1
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
03/13/2016 Page 6 / 6
很抱歉,暂时无法提供与“2814715”相匹配的价格&库存,您可以联系我们找货