Signal Multiplier
MCR-FL-C-UI-2UI-DCI
1. Description
• 4-way isolation
• Configurable inputs and outputs
Signal conversion and amplification
• Adjustable signal combinations
• 17.5 mm ME housing
Isolation
OUT1
FL
U,I
IN
U, I
U,I
OUT2
POWER
The MCR-FL-C-UI-2UI-DCI signal multiplier is used
to multiply and electrically isolate analog signals.
The module inputs, outputs, and the power supply
are electrically isolated from one another (4-way
isolation). In this way, the modules can be used for
electrical isolation, signal conversion, and amplification
both locally and close to the control system. The
auxiliary voltage required is indicated by a green power
LED.
DIP switches can be used to switch between a signal
selected within the limits of the order key or for the fixed
signal conversions
provided in the configuration table.
If no entry is made in the specified order key, the
devices are supplied with the default configuration
(input signal 0…20 mA, output signals 0…20 mA/
0…10 V).
Adjustment following configuration is not necessary,
as each transmission variant is calibrated and stored in
the device.
1 1 4 ,5
9 9
Headquarters: © Phoenix Contact GmbH & Co. KG • Flachsmarktstraße 8 • 32825 Blomberg • Germany
Phone +49 - 52 35 - 30 0 • Fax +49 - 52 35 - 34 12 00 • www.phoenixcontact.com
Local Contact: www.phoenixcontact.com/salesnetwork
1 7 ,5
Signal Multiplier – MCR-FL-C-UI-2UI-DCI
2. Technical Data
OUT
OUT I2
OUT U2
GND 2
IN I
IN U
GND 3
1
2
3
OUT
A
D
D
4
5
6
A
7 OUT I1
8 OUT U1
9 GND 1
0 +24V DC
! GND 4
" GND 4
A
D
IN
MCR-FL-C-UI-2UI-DCI
with configurable input and output
8 mm
M3
Solid
Connection data
Stranded
[mm2]
AWG
0.2 - 2.5
uU
0.2 - 2.5 25 - 14
Description
MCR signal multiplier,
for doubling and electrical
isolation of analog signals
Preconfigured
Not configured
Type
Order No.
MCR-FL-C-UI-2UI-DCI
MCR-FL-C-UI-2UI-DCI-NC
28 14 85 4
28 14 86 7
Pcs.
Pkt.
Technical Data
Input
Input signal range
Measuring range span
Maximum input signal
Input resistance
0…24 mA/0…12 V, freely selectable in increments of 0.1 (mA/V)
8 mA/4 V, minimum
50 mA or 30 V
50 Ω at I input/200 kΩ at U input
Output
Output signal per channel
Maximum output signal per channel
Load per channel
See order key/configuration table
35 mA or 15 V
≤ 600 Ω at I output/≥ 10 kΩ at U output
General Data
Supply voltage
Current consumption (without load)
Transmission error
Temperature coefficient
Limit frequency (3 dB)
Step response (10 - 90%)
Test voltage
Protective circuit
Ambient operating temperature range
Degree of protection
Connection method
Mounting position/mounting
Electromagnetic compatibility:
• Noise emission
• Noise immunity
20…30 V DC
< 25 mA
< 0.15% of the final value; 0.05% of the final value, typical
< 0.015%/K, 0.0075%/K, typical
30 Hz
12 ms
1.5 kV AC, 50 Hz, 1 minute
Transient protection
-20°C to +55°C
IP20
Plug-in COMBICON screw terminal block
Any
c Conformance with EMC Directive 89/336/EEC
EN 50 081-2
EN 50 082-2
PHOENIX CONTACT page 2 of 5
1
1
Signal Multiplier – MCR-FL-C-UI-2UI-DCI
c
Conformance With EMC Directive 89/336/EEC and
the Low Voltage Directive 73/23/EEC
EMC (Electromagnetic Compatibility)
Noise Immunity According to EN 50082-2
• Electrostatic discharge (ESD)
8 kV air discharge 2)
EN 61000-4-2
• Electromagnetic HF field
Amplitude modulation
Pulse modulation
EN 61000-4-3
• Fast transients (burst)
EN 61000-4-4
Input/output/supply
2 kV/5 kHz 2)
• Surge current loads (surge)
EN 61000-4-5
Input/output: 2 kV/42 Ω 2)
Supply: 0.5 kV/2 Ω/12 Ω 2)
• Conducted interference
EN 61000-4-6
Input/output/supply
10 V 1)
10 V/m 1)
10 V/m 1)
EN 55011
Noise Emission According to EN 50081-2
Class A
EN 61000 corresponds to IEC 1000/
EN 55011 corresponds to CISPR11
1)
Criterion A: Normal operating characteristics within the specified
limits.
2) Criterion B: Temporary adverse effects on the operating
characteristics which the device corrects automatically.
Class A:
Approval
Industrial application, without special
installation measures.
U
PROCESS CONTROL EQUIPMENT FOR HAZARDOUS LOCATIONS 31ZN
LISTED
Cl. I, Zn. 2, AEx nC IIC T6 / Ex nC IIC T6
Cl. I Div. 2, Groups A, B, C and D
A) This equipment is suitable for use in Class I, Division 2,
Groups A, B, C and D or non-hazardous locations only.
B) Warning - explosion hazard - substitution of components may impair suitability for Class 1, Division 2.
C) Warning - explosion hazard - do not disconnect equipment unless power has been switched off or the area is
known to be non-hazardous.
MCR-FL-C-UI-2UI-DCI – Signal Multiplier
2
I
4
R
E
W
O
P
I-2
-U
-C
FL
R-
MC
U
CI
D
UI-
R D
E GN
1
W 4
D
N
O D
P GN T1 G
U
O
4V
+2
1
1 Upper housing part, can be removed to set
DIP switches
2
I
U
T
U
O
I
2 Plug-in screw terminal blocks
G
IN
D
U
N
2
G
N
D
3
I
DC
UII-2 4
-U 85
-C 14
FL 8
R-r.: 2
C
N
Mrt.T
OU
A
OU
7 OU
8 GN
9
D A
0
!
"
1
2
3 Metal lock for fastening on the DIN rail
3
OU
4
T
5
6
2
A
I2
U2
2
1
2
3
A
4
5
6
IN
1
2
3
IN
4
IN
5
I1
8
T
1
OU
U
9
T
OU 1
10
D
N
DC 1
G
1
4V
2
+
4
D
12
N
G
4
D
GN
D
I2
T
2
OU
U
T
OU
2
D
GN
S
AL
OV
I
PR
U
D
GN
6
D
7
D
3
N
/
AP
NE
TIO
BA
O
PR
AP
3
Fig. 06
PHOENIX CONTACT page 3 of 5
Signal Multiplier – MCR-FL-C-UI-2UI-DCI
3. Configuration
-D
UI
I-2
-U
-C
FL
R-
MC
O
I
3.1. Opening the Device (Fig. 07)
The fastenings on both sides of the upper housing
part can be released using a screwdriver 1. The upper
housing part and the electronics can now be pulled out
about 3 cm 2.
U
U
2
T
I
G
IN
N
D
U
2
G
N
D
3
1
2
FL
R-r.:
N
MrC
t.-
3
A
2
Ensure you take sufficient measures
against electrostatic discharge
OU
4
T
5
6
1
A
I2
U2
2
D
1
2
3
A
D
D
4
5
6 N
I
I2
T
2
OU
U
T
OU
2
2
D
GN
3
I
IN
P
4
AP
U
/
IN
3
5
EN
D
1
Fig. 07
3.2. Setting (Fig. 08)
Changes to the ordered connection method settings
are made via DIP switches S1 to S10.
In addition to the preconfigured signal, which is
preset by the order key, the remaining 9 DIP switches
and their signal behavior can be enabled using DIP
switch 10.
DIP
10
9
Configuration
S10
8
Signal range specification via DIP switches
OFF
7
Signal ranges preset by order key
ON
6
5
Input (IN)
S1
S2
S3
4
0…20 mA
OFF
OFF
OFF
3
0…10 mA
OFF
OFF
ON
2
4…20 mA
OFF
ON
OFF
1
2…10 mA
OFF
ON
ON
0…10 V
ON
OFF
OFF
1…5 V
ON
OFF
ON
0…5 V
ON
ON
OFF
2…10 V
ON
ON
ON
Output 1: Setting the
output signal ranges
Setting the
input signal range
Fig. 08
The current and voltage channel can be used in
parallel at each output so that up to four signal outputs
with full load capability are provided.
Please note: Where possible, output 1 should be
used as a current output.
Output:
Current/Voltage
Signal
DIP Switch Function
Signal range specification according
to the order key or DIP switches
Output 2: Setting the
output signal ranges
Output 1
(OUT 1)
Output 2
(OUT 2)
S4
S5
S6
S7
S8
S9
0…20 mA / 0…10 V
OFF
OFF
OFF
OFF
OFF
OFF
0…20 mA / 1…5 V
OFF
OFF
ON
OFF
OFF
ON
0…20 mA / 0…5 V
OFF
ON
OFF
OFF
ON
OFF
0…10 mA / 0…5 V
OFF
ON
ON
OFF
ON
ON
4…20 mA / 0…10 V
ON
OFF
OFF
ON
OFF
OFF
4…20 mA / 1…5 V
ON
OFF
ON
ON
OFF
ON
4…20 mA / 0…5 V
ON
ON
OFF
ON
ON
OFF
4…20 mA / 2…10 V
ON
ON
ON
ON
ON
ON
If the value is outside the measuring range, a linear
transmission response is triggered.
PHOENIX CONTACT page 4 of 5
Signal Multiplier – MCR-FL-C-UI-2UI-DCI
4. Application Example (Fig. 09)
Level measurement with ultrasound
and subsequent signal multiplication
15 m3
0…20 mA
0…10 V
Control system
IN
OUT2
1 I2
5 U
2 U2
6 GND3
3 GND2
MCR-FL-C-UI-2UI-DCI
POWER
4 I
OUT1
I1
7
POWER
+24V 10
U1
8
GND4 11
GND1 9
GND4 12
Ultrasonic transmitter/sensor
0…20 mA
24V
24V
5. Order Key
Mains voltage
MCR-FL-C-UI-2UI-DCI
The standard configuration will be supplied if
customer order details are incorrect or not provided
(provided in the order key as an example).
Input Signal
28 14 85 4
Standard
configuration
I
I = Current
U = Voltage
Input Signal (Standard and Special Signals)
Start Value
Final Value
0.0
I = 0.0 mA
I: Freely selectable
between
U: Freely selectable
between
20.0
I = 20.0 mA
I: Freely selectable
between
U: Freely selectable
between
• Minimum measuring range span 8.0 mA/4.0 V 2)
• Increment 0.1 mA/0.1 V
) Order examples:
28 14 85 4
Input Signal (Standard and Special Signals)
Start Value
Final Value
I
I = Current
5.3
I = 5.3 mA
13.3
I = 13.3 mA
OUT01
OUT01 = 0...20 mA
OUT02 = 4...20 mA
OUT03 = 0...10 V
OUT04 = 2...10 V
OUT05 = 0...5 V
OUT06 = 1...5 V
OUT16 = 0...10 mA
Output Signal
Output 1
OUT01
OUT01 = 0...20 mA
OUT02 = 4...20 mA
OUT03 = 0...10 V
OUT04 = 2...10 V
OUT05 = 0...5 V
OUT06 = 1...5 V
OUT16 = 0...10 mA
Output 2
OUT01
OUT01
OUT01
OUT03
Measuring range span 8.0 mA, i.e., can be ordered.
7.8
11.8
I = 7.8 V
I = 11.8 V
Measuring range span 4.0 V, i.e., can be ordered.
TNR: 5106352-01
U
U = Voltage
03/15/05
28 14 85 4
PHOENIX CONTACT
2
Output Signal (Standard Signals)
Output 1
Output 2
http://www.phoenixcontact.com
Order No.
Fig. 09
PHOENIX CONTACT page 5 of 5