https://www.phoenixcontact.com/us/products/2816399
Type 2 surge protection plug - VAL-MS 400 ST - 2816399
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Surge protection connector type 2 with high-capacity varistor for VAL-MS base element, thermal monitoring,
visual fault warning. Design: 400 V AC
Product Features
Single-channel, DIN-rail mountable protective devices
Mechanical coding of all slots
Optical, mechanical status indication for the individual arresters
Disconnect device on each individual plug
Consists of base element and plug
Base element with/without floating remote indication contact
Key Commercial Data
Packing unit
1 pc
GTIN
Weight per Piece (excluding packing)
49.3 g
Custom tariff number
85363010
Country of origin
Germany
Technical data
Dimensions
Height
52.4 mm
Width
17.5 mm
Depth
55.3 mm
Horizontal pitch
1 Div.
02/01/2016 Page 1 / 6
https://www.phoenixcontact.com/us/products/2816399
Type 2 surge protection plug - VAL-MS 400 ST - 2816399
Technical data
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-40 °C ... 80 °C
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Altitude
≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)
5 % ... 95 %
Shock (operation)
25g (half sinus / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)
5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
General
Standards/specifications
IEC 61643-11 2011
EN 61643-11 2012
IEC test classification
II
T2
EN type
T2
IEC power supply system
TN
TT
IT
SPD design
Voltage-limiting type
Mode of protection
L-PEN
L-PE
L-N
Mounting type
On base element
Color
jet black RAL 9005
Housing material
PA 6.6
Degree of pollution
2
Flammability rating according to UL 94
V-0
Type
DIN rail module, two-section, divisible
Number of positions
1
Arrester can be tested with CHECKMASTER from software version:
From SW rev. 1.10
Surge protection fault message
optical
Additional descriptions
Note
Usable in all low-voltage systems between L-N or L-PEN.
Only usable in IT Systems between L-PE, if the exposed-conductive-parts
(bodies) of the equipment of the low-voltage installation is connected to
the earthing arrangement of the transformer substation. (interconnected
earthing arrangement of the HV-transformer substation with the bodies
of the LV-installation. RE = RA accordance to IEC 60364-4-442 / VDE
0100-442 Fig. 44D / Example a)
Protective circuit
02/01/2016 Page 2 / 6
https://www.phoenixcontact.com/us/products/2816399
Type 2 surge protection plug - VAL-MS 400 ST - 2816399
Technical data
Protective circuit
Nominal voltage UN
240/415 V AC (TN)
240/415 V AC (TT)
230 V AC (IT)
Nominal frequency fN
50 Hz (60 Hz)
Maximum continuous voltage UC
440 V AC
Residual current IPE
≤ 0.45 mA
Standby power consumption PC
≤ 200 mVA
Nominal discharge current In (8/20) µs
20 kA
Maximum discharge current Imax (8/20) µs
40 kA
Short-circuit current rating ISCCR
25 kA
Voltage protection level Up
≤ 2.2 kV
Residual voltage Ures
≤ 2.2 kV (at In)
≤ 1.8 kV (at 10 kA)
≤ 1.5 kV (at 5 kA)
≤ 1.4 kV (at 3 kA)
TOV behavior at UT
440 V AC (5 s / withstand mode)
440 V AC (120 min / withstand mode)
Response time tA
≤ 25 ns
Max. backup fuse with branch wiring
125 A (gG)
Connection data
Connection method
VALVETRAB plug-in system
UL specifications
SPD Type
4CA
Maximum continuous operating voltage MCOV (L-N)
440 V AC
Nom. voltage
400 V AC
Mode of protection
L-N
Power distribution system
1
Nominal frequency
50/60 Hz
Measured limiting voltage MLV (L-N)
2280 V
Nominal discharge current In (L-N)
20 kA
Classifications
eCl@ss
eCl@ss 4.0
27140201
eCl@ss 4.1
27130801
02/01/2016 Page 3 / 6
https://www.phoenixcontact.com/us/products/2816399
Type 2 surge protection plug - VAL-MS 400 ST - 2816399
Classifications
eCl@ss
eCl@ss 5.0
27130801
eCl@ss 5.1
27130801
eCl@ss 6.0
27130805
eCl@ss 7.0
27130805
eCl@ss 8.0
27130805
ETIM
ETIM 2.0
EC000941
ETIM 3.0
EC000941
ETIM 4.0
EC000941
ETIM 5.0
EC000941
UNSPSC
UNSPSC 6.01
30212010
UNSPSC 7.0901
39121610
UNSPSC 11
39121610
UNSPSC 12.01
39121610
UNSPSC 13.2
39121620
Approvals
Approvals
Approvals
IECEE CB Scheme / UL Recognized / KEMA-KEUR / ÖVE / cUL Recognized / GL / CCA / CSA / EAC / EAC / cULus Recognized
Ex Approvals
Approvals submitted
Approval details
IECEE CB Scheme
02/01/2016 Page 4 / 6
https://www.phoenixcontact.com/us/products/2816399
Type 2 surge protection plug - VAL-MS 400 ST - 2816399
Approvals
UL Recognized
KEMA-KEUR
ÖVE
cUL Recognized
GL
CCA
CSA
EAC
EAC
cULus Recognized
Drawings
02/01/2016 Page 5 / 6
https://www.phoenixcontact.com/us/products/2816399
Type 2 surge protection plug - VAL-MS 400 ST - 2816399
Dimensional drawing
Circuit diagram
52,4
17,5
43,3
55,3
44,8
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
02/01/2016 Page 6 / 6