Extract from the online
catalog
TT-EX(I)- 24DC
Order No.: 2832124
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2832124
Modular terminal block with three-stage surge protection for a floating
Ex-i signal circuit, separate PE connection, nominal voltage: 24 V DC,
for mounting on NS 35/7.5, terminal block width: 6.2 mm, terminal
block height: 54.6 mm
Product notes
WEEE/RoHS-compliant since:
06/28/2006
Commercial data
GTIN (EAN)
4
017918
172831
sales group
J305
Pack
10 pcs.
Customs tariff
85363010
Catalog page information
Page 101 (TT-2009)
http://
www.download.phoenixcontact.com
Please note that the data given
here has been taken from the
online catalog. For comprehensive
information and data, please refer
to the user documentation. The
General Terms and Conditions of
Use apply to Internet downloads.
Technical data
General
Housing material
PA 6.6
Inflammability class acc. to UL 94
V0
Color
blue
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 1 / 6
Feb 9, 2011
TT-EX(I)- 24DC Order No.: 2832124
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2832124
Standards for air and creepage distances
EN 50020
VDE 0110-1
DIN EN 60079-11
Total surge current (8/20) µs
10 kA
Ambient temperature (operation)
-40 °C ... 85 °C
Mounting type
DIN rail: 35 mm
Design
Double-level terminal block with PE foot – separate PE
connection
Degree of protection
IP20
Direction of action
Line-Line & Line-Earth Ground
Width
6.20 mm
Height
54.60 mm
Length
79.60 mm
Protective circuit
IEC category
C1
C2
C3
D1
VDE requirement class
C1
C2
C3
Nominal voltage UN
24 V DC
17 V AC
Maximum continuous operating voltage UC
30 V DC
21 V AC
Maximum continuous voltage UC (wire-wire)
30 V DC
21 V AC
Nominal current IN
250 mA (40°C)
Operating effective current IC at UC
≤ 5 µA
Ground conductor current IPE
≤ 1 µA
Nominal discharge surge current In (8/20) µs
(Core-Core)
5 kA
Nominal discharge surge current In (8/20) µs
(Core-Earth)
5 kA
Total surge current (8/20) µs
10 kA
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 2 / 6
Feb 9, 2011
TT-EX(I)- 24DC Order No.: 2832124
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2832124
Max. discharge surge current Imax (8/20) µs
maximum (Core-Core)
5 kA
Max. discharge surge current Imax (8/20) µs
maximum (Core-Earth)
5 kA (per path)
Nominal pulse current Ian (10/1000) µs (CoreCore)
100 A
Nominal pulse current Ian (10/1000) µs (CoreEarth)
100 A (per path)
Lightning test current (10/350) µs, peak value limp
500 A (per path)
Output voltage limitation at 1 kV/µs (Core-Core)
spike
≤ 50 V
Output voltage limitation at 1 kV/µs (Core-Earth)
spike
≤ 1.7 kV
Output voltage limitation at 1 kV/µs (Core-Core)
static
≤ 50 V
Output voltage limitation at 1 kV/µs (Core-Earth)
static
≤ 1.7 kV
Residual voltage at In, (conductor-conductor)
≤ 40 V
Protection level UP (Core-Core)
≤ 75 V (C2 (10 kV/5 kA))
≤ 50 V (C3 - 25 A)
Protection level UP (Core-Earth)
≤ 2 kV (C2 - 10 kV / 5 kA)
Response time tA (Core-Core)
≤ 1 ns
Response time tA (Core-Earth)
≤ 100 ns
Input attenuation aE, sym.
1 dB (≤ 1 MHz)
0.3 dB (≤ 200 kHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 50 Ohm
system
Typ. 6 MHz
Cut-off frequency fg (3 dB), sym. in 150 Ohm
system
Typ. 2 MHz
Capacity (Core-Core)
2.5 nF
Resistance in series
4.7 Ω ±10 %
4.7 Ω
Surge carrying capacity in acc. with IEC 61643-21
(Core-Core)
C2 (10 kV/5 kA)
C1 (1 kV / 500 A)
C3 (25 A)
Surge carrying capacity in acc. with IEC 61643-21
(Core-Earth)
C2 (10 kV/5 kA)
C3 (25 A)
D1 (500 A)
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 3 / 6
Feb 9, 2011
TT-EX(I)- 24DC Order No.: 2832124
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2832124
Connection data
Type of connection
Screw terminal blocks
Connection type IN
Screw terminal blocks
Connection type OUT
Screw terminal blocks
Screw thread
M3
Tightening torque
0.8 Nm
Stripping length
8 mm
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
4 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
14
Connection, protective circuit
Standards/regulations
IEC 61643-21
EN 50020
General
Maximum inner capacitance Ci
2 nF
Maximum inner inductance Li
1 µH
Maximum inner time factor (Ri/Li)
0.1 µs
Insulation voltage to ground
500 V 10 %
Conformity / approvals
ATEX
Ex II 1G, Ex ia IIC T4...T6
Ex II 1 D, Ex iaD 20 T95...135 °C
Certificates / Approvals
Certification
GOST, UCIEE, UL
Certification Ex:
CUL-EX LIS, KEMA-EX, UL-EX LIS
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 4 / 6
Feb 9, 2011
TT-EX(I)- 24DC Order No.: 2832124
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2832124
Accessories
Item
Designation
Description
D-DEK 1,5 BU
Cover for setting the end of a TERMITRAB TT-EX(I)... row of
terminal blocks, color: blue
Assembly
2838982
Additional products
Item
Designation
Description
D-DEK 1,5 BU
Cover for setting the end of a TERMITRAB TT-EX(I)... row of
terminal blocks, color: blue
Assembly
2838982
Diagrams/Drawings
Dimensioned drawing
Circuit diagram
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 5 / 6
Feb 9, 2011
TT-EX(I)- 24DC Order No.: 2832124
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2832124
Address
PHOENIX CONTACT Deutschland GmbH
Flachsmarktstr. 8
32825 Blomberg,Germany
Phone +49 5235 3 12000
Fax +49 5235 3 41200
http://www.phoenixcontact.de
© 2011 Phoenix Contact
Technical modifications reserved;
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 6 / 6
Feb 9, 2011
很抱歉,暂时无法提供与“2832124”相匹配的价格&库存,您可以联系我们找货